6ES5 405-7AB11

Siemens 6ES5 405-7AB11 – 8-Channel, 115 V AC/DC Digital Input Module

6ES5 405-7AB11 is a galvanically isolated digital input module with eight 115 V AC/DC inputs for S5-110A and S5-110S systems in the SIMATIC S5 range. The Siemens manual explicitly defines 115 V UC as AC/DC. Logic 0 is 0–40 V AC/DC; logic 1 is 85–132 V AC/DC.

The module reads relay contacts, limit switches and suitably rated photoelectric sensors in a machine’s 115 V control circuit. Input current at the nominal signal is 10 mA AC or 5.7 mA DC. These are input-circuit values, not load-switching output ratings.

115 V signal levels and sensor selection

The region between 40 V and 85 V is not a defined logic state. With the contact closed, measure across the two terminals of the relevant input circuit as well as checking the panel source. Do not apply 24 V input thresholds to this model, or connect a 220/230 V field signal to it.

The Siemens table lists suitable AC BERO proximity switches. The stated sensor conditions are off-state I0 ≤ 5 mA AC and on-state I1 ≥ 10 mA. Check leakage and required load current as well as the voltage rating.

Independent input circuits and installation

The S5-110A connection instructions allow the eight inputs to be used as independent two-terminal circuits. Suitable jumpers distribute a common potential where required. Match the S5 wiring arrangement to the markings on the upper and lower terminals. Do not copy another series’ common-M wiring, and do not use protective earth as a signal return.

The 115 V AC/DC field signal is separate from internal system power. The S5-110A specification gives 1 mA consumption from the internal 5 V supply, approximately 6 W power loss and 0.4 kg weight. Check the S5 power supply, field circuit and mounting base separately.

Addressing and monitoring the inputs

On the S5-110S, these I/O modules use location-coded bases. Do not assign the same input address to two input modules. The eight channels are monitored as bits .0–.7 of the selected input byte. During PLC programming, verify the address against the rack and base arrangement, then match the PLC bit to the physical channel.

A similar appearance in the S5 module directory does not establish a common base or addressing method. Use the appropriate S5-110A/110S system manual to check the rack, base and wiring. Record cable labels and the original module position before replacement.

Delay, thermal loading and related models

Both English Siemens manuals give a 0→1 delay of 2.3–13 ms. For turn-off, the S5-110A manual specifies 2–35 ms, while the S5-110S manual specifies 2–20 ms. Use the applicable system documentation when assessing short pulses; ordinary input polling does not make this a high-speed counter.

The technical table specifies 75% total input load capability at 1.2 × UN. This does not establish unrestricted operation with all eight inputs active at every voltage and temperature. Retain the specified 132 V upper limit for logic 1; the load-capability entry is not permission to raise the operating voltage.

Permissible cable length depends on adjacent-circuit voltage and whether cables run together. When investigating electromagnetic interference, consider neighbouring power circuits, contact condition and voltage remaining across an inactive input, as well as the total cable length.

6ES5 405-7AB21 is the 220 V AC/DC version. 6ES5 400-7AA13 is a 24 V DC input module, and 6ES5 401-7AA13 is a 24 V DC version with a group signal. Do not attribute the 401 group-signal function to 405-7AB11. S5 digital output modules perform a separate load-control function.

Editor’s note

Start with the suffix: 7AB11 is the 115 V model. When selecting a Siemens S5 spare, do not rely on the similar appearance of 7AB21. Compare the original label with the machine’s control voltage before fitting another board. A voltage mismatch can create a second fault instead of resolving the first.

If the input remains on after a contact opens, check the circuit before condemning the module. Use a suitable multimeter across the input’s two terminals. Investigate cable capacitance, sensor leakage and suppression components across contacts. An unloaded voltage reading alone is insufficient to identify the fault.

If the LED changes but the program bit does not, begin PLC troubleshooting with the address mapping. Check that rack position, base coding and the programmed input byte agree. Resolve an addressing mismatch before attempting work on the board electronics.

For a used module, exercise all eight inputs in both directions. Check that the input clears after signal removal, rather than only confirming that its LED lights. Use equipment suitable for the 115 V circuit and prevent machine movement during the test. Do not reuse another module’s test wiring without checking it.

Inspect the upper and lower terminals, base contacts and existing jumpers. Heat marks, a cracked housing or loose contacts deserve investigation before another module is fitted. Where independent inputs have been linked to a common potential, confirm that those jumpers belong to the installed circuit design.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLC and S5 digital input modules for the system and module groups.

+ OtomasyonAVM shared S5 PDF and manual archive. The technical references for this model are the English S5-110A and S5-110S documents below.

Related topics

+ 6ES5 405-7AB21: eight-input, 220 V AC/DC version; do not select it solely as a replacement for the 115 V model.

+ 6ES5 400-7AA13: eight-input, 24 V DC module.

+ 6ES5 401-7AA13: eight-input, 24 V DC module with a group signal.

+ S5 digital output modules: the separate product group for switching loads.

Browse SIMATIC S5

+ S5 digital input modules · S5 90/110 module directory · SIMATIC S5 · Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens S5-110A Operating Instructions — GWA 4NEB 807 0690-02 / 6ES5 998-0AA22, English manufacturer document hosted by ADEGIS. Printed 1.12 / PDF 16: exact-model specifications and the definition of 115 V UC as AC/DC. Printed 2.6 / PDF 25: independent input circuits and connection jumpers.

+ Siemens S5-110S Operating Instructions — GWA 4NEB 807 2121-02, English. Printed 9 / PDF 11: exact 405-7AB11 specification column. Printed 15–16 / PDF 17–18: location-coded bases and I/O installation.