6ES5 476-3AA11
6ES5 476-3AA11 Siemens SIMATIC S5 476 Analog Output Module, 4 × 0–20 mA
The Siemens 6ES5 476-3AA11 is a compact K-format analog output module for the SIMATIC S5-150K and S5-150S. It converts STEP 5 commands into four non-isolated, unipolar 0–20 mA outputs with 8-bit value representation. Each output can drive a resistive load of up to 350 Ω.
In service, the card can provide a reference to a drive or positioner with a matching current input. The 6ES5 475-3AA11 in the same compact family has four ±10 V voltage outputs. When selecting a spare, check the receiving device’s label and wiring diagram for the required signal type.
Which rack and supplies does the compact card use?
A 32-pin rear connector connects the card to the compact S5 rack. The 925-3KA12 and 927-3KA13 are examples of S5-150K CPUs. The 925-3SA11 and 927-3SA11 are examples for the S5-150S. Check the existing rack, backplane connection and CPU order number when selecting the card.
Siemens specifies +5 V ±5% and 0.25 A for the internal supply, and 24 V DC (20–30 V DC) and 0.2 A for the external supply. The outputs are non-isolated, so check the receiving device’s return against the 0 V reference in the wiring diagram. Terminate shielded signal cables according to the cabinet installation guide.
How are STEP 5 addresses and current values set?
The address coding plug sets the starting byte independently of the slot number. For four outputs, the starting address is a multiple of eight from 128 to 248. Each channel occupies two bytes. With a base address of 128, the SIMATIC S5 CPU program uses 128, 130, 132 and 134 as the first byte addresses for channels 0–3.
With factory scaling, Byte 0 carries a current command from 0 to 255. Siemens gives 64 ≈ 5 mA, 128 ≈ 10 mA and 255 ≈ 19.922 mA. For the nominal 0–20 mA range, Siemens lists a linearity error limit of ±0.3% and a separate tolerance of ±0.4%.
Siemens documents hardware selection of full-scale current per channel at R86–R89. Record the fitted resistors and scaling if a card has been modified. On the feedback side, check the order number of the 465-3 analog input module and the applicable input range hardware. The 498-1AA41, 498-1AA51 and 498-1AA71 are examples of S5 input range modules.
How does it differ from other analog output cards?
The A-format 475-5AA11 supplies ±10 V. The 470-4UC11 is a U-format analog output card. The 470-8MC12 and 477-8EC11 are separate families with 4–20 mA outputs. Use the full order number to compare the rack, channel count, signal range and isolation requirements.
Editor’s note
Photograph the 476-3AA11 label, address coding plug and jumper positions before removing the card. If the rack is also being changed, record the S5 interface module labels separately.
If all four outputs have lost current, check the external 24 V DC supply, the 0 V return and the card’s rear connection first.
If just one channel reads low, check the receiving input and the total series resistance. Include the receiver and line resistance when checking the 350 Ω load limit.
For a maintenance test, put the process in a safe state before applying a known STEP 5 command. 128 counts gives about 10 mA with factory scaling. Check the channel’s resistor setting if the reading differs.
Isolate power to the central unit, expansion units and connected field devices before replacing the card. Before restarting, match the output addresses in the Siemens S5 program to the four channels on the cabinet drawing.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog modules · S5 racks and mounting hardware · About Siemens S5 PLCs
Related topics
6ES5 475-3AA11 compact ±10 V output card · 6ES5 465-3AA13 analog input card · 6ES5 470-8MC12, 4–20 mA output card
S5 navigation
SIMATIC S5 › S5 analog modules
External references
Siemens compact analog I/O manual, C79000-B8500-C234-5, pp. 1–4 and 10 (German) · Siemens compact S5 cabinet installation guide, C79000-B8500-C252-03 (German)