6ES5 700-8EA11
6ES5 700-8EA11 Siemens SIMATIC S5 Ex I/O Bus Unit
The Siemens 6ES5 700-8EA11 is a SIMATIC S5 bus unit for two compatible Ex I/O modules. In the S5 rack and bus-unit range, it has blue SIGUT screw terminals and blue coding keys. Within the S5 module system, it connects the Ex cards to the backplane bus and field terminals.
Slots and system compatibility
The unit provides two Ex module slots with 10 terminals per slot. It mounts on the standard sectional rail, with a ribbon cable linking it to an adjacent unit, CPU, interface or PS 935. Siemens documents S5-95U, S5-100U configurations with CPU 100, CPU 102 or CPU 103, and suitable ET stations. Distributed examples use ET 100U IM 318-8 and ET 200U IM 318-B interfaces.
For digital inputs, the 6ES5 437-8EA12 is a NAMUR example. For digital outputs, the 6ES5 457-8EA12 drives compatible field loads. Analog I/O examples include the 6ES5 467-8EE11 4–20 mA input and the 6ES5 477-8EC11 4–20 mA output. When 4–20 mA cards exceed the backplane current budget, supported systems use a PS 935. For CPU 100, calculate the load against the CPU’s own backplane limit.
Separating Ex and standard terminals
In the Siemens arrangement, the bus unit and Ex I/O cards sit outside the hazardous area. The field device connects to the Ex i circuit. Fit the specified 6ES5 497-8EA11 partition between the Ex bus unit and a standard unit or device with non-intrinsically safe circuits. Siemens specifies a 50 mm separation measured along the contour between the two sets of terminals. Verify the field device, I/O module and cable as a combination against the installation’s Ex documentation.
The 8MA11 is a standard SIGUT screw-terminal base, and the 8FA11 adds enhanced EMC protection. The 8MA21 and 8MA22 use crimp terminals. For an Ex I/O spare, match the complete 8EA11 order number and the blue slot coding keys.
Editor’s note
1. Record the layout before removal. Photograph the bus-unit label, both module numbers, the slot order and the partition position.
2. Check the partition and cable routing. Confirm that the 497-8EA11 sits at the boundary between Ex and standard terminals and that the cable routing follows the approved drawing.
3. If both cards go offline, check the shared connection. Follow the plant isolation procedure, then inspect the ribbon cable, connector latch and adjacent bus unit.
4. If one channel fails, trace that field loop. Compare the module part number, channel address and field label with the loop drawing. Use the site-approved test method for the Ex circuit.
5. Check the supply budget when analog signals drop out. If readings disappear after adding a card, compare the backplane load and any PS 935 connection with the documented configuration.
6. Ask for a separate test of each used slot. Request the Ex module types and slots tested, plus close-up photos of the screw threads, blue coding keys and ribbon cable.
To offer a used 8EA11 for sale, send the label, terminal and ribbon-cable photos with the test status to otomasyonavm@gmail.com.
PDF and Siemens documents
S5-100U Ex I/O manual, 6ES5 998-0EX22 (English PDF). See section 11.5 for the bus unit, 11.6 for the partition and Appendix F for the slots and terminals. Shared S5-115 PDF archive.
Related topics
S5 Interface Modules · S5 Cable Types · About Siemens S5 PLC
Navigation