6ES5 700-2BA11

6ES5 700-2BA11 Siemens ET 200B TB1/DC Screw Terminal Block

The Siemens 6ES5 700-2BA11 is an ET 200B TB1/DC terminal block listed under a SIMATIC S5 order number. In the ET 200 distributed I/O architecture, field wiring lands on the terminal block and the electronics module plugs on top. This is the three-tier screw-terminal TB1/DC version.

Matching the electronics module

The 16DE digital input example is the 6ES5 431-2BA11. The 16DA digital output example is the 6ES5 451-2BA11, and the 8RA relay output example is the 6ES5 458-2BR11. Use the specific 8RA electronics wiring diagram to identify the relay contacts.

The Siemens ET 200B manual shows the TB1/DC drawing under 6ES7 193-0CA10-0XA0. The TB1-4/DC has four screw-terminal tiers, and the TB3/DC has spring-latch terminals. Compare terminal numbering, the coding slide and the full electronics module number when selecting a spare.

For ET 200B electronics such as the 32-input 430-2BA11 and 16DO/2A 454-2BA11, check the terminal-block table for the specific module. Siemens shows different bases such as TB2/DC and TB2-4/DC for the 32DI and 16DO/2A classes. TB6/AC is a separate AC terminal block type, and TB8 is the analog type.

Connection and diagnostics

The ET 200B manual shows the station address setting and PROFIBUS-DP interface on the terminal block. If the station is unavailable, check its connection hardware and power feed, then compare the address on the base with the DP master project. Read BF and RUN on the electronics block.

Editor’s note
1. Record both labels. Before removal, photograph the 2BA11 base label, the electronics order number and the field wire labels.
2. Compare terminal numbering across all three tiers. Match each row to the module-specific pin table. Trace relay contacts separately from the DC load supply.
3. Check the coding if the module will not seat. Isolate logic and field supplies under the plant procedure. Inspect the coding slide and check the socket for bent pins.
4. For a lost station, check addressing and the DP link separately. Compare the base address with the project. The manual states that a new address takes effect after a STOP-to-RUN transition. If BF is on, check the DP plug and termination against the network drawing.
5. For a single-channel fault, trace that field circuit. Check the field wire, terminal screw and the common or relay contact shown on the module diagram.
6. Ask how a used base was tested. Request the electronics module number, confirmation that the DP master detected the station, and close-up photos of the terminals and socket.

To offer a terminal block for sale, send its full label code, the electronics module details and photos of the terminals and socket to otomasyonavm@gmail.com.

PDF and wiring drawings

Siemens ET 200B manual (English PDF). Section 2.1 shows the terminal block layout. Section 7 lists terminal assignments by electronics module. Shared S5 PDF archive.

Related topics

Siemens ET200 manuals · ET200 Terminal Blocks · About Siemens S5 PLC

Navigation

S5 Racks · SIMATIC ET200 · SIMATIC S5 · Second-hand Siemens

Sources

ADEGIS 2BA11 parts entry · TPCOVN SIMATIC S5 parts list