6ES5 700-0LB11
Siemens 6ES5 700-0LB11 CR 700-0LB central mounting rack
The 6ES5 700-0LB11 is a CR 700-0LB mounting rack for the power supply, CPU and I/O modules of a SIMATIC S5 central controller. Siemens lists the same order number in separate layouts for the S5-115U, 115H and 115F. Use the S5 rack range and S5 CPU family to match the installed hardware by its order number.
Slot layout and dimensions
The physical layout is PS · CPU · 0 · 1 · 2 · 3 · IM. Siemens lists dimensions of 353 × 303 × 47 mm (W × H × D) and a weight of 4 kg. The CPU 942-7UB11 is an S5-115U example. When selecting a PS 951 power supply, check the full code, such as 951-7ND41, against the table for the installed system.
How the S5-115U fits six modules
In a permitted S5-115U arrangement, positions 0 and 3 can take adapters holding two single-width modules each. This allows up to six I/O modules with suitable digital inputs, digital outputs and analog I/O. Verify the adapter casing code and the permitted positions for the boards. Siemens requires fan cooling when two modules share a casing. In the S5-115U layout, slot 3 provides no interrupt processing.
The CR 700-0LA12 is a separate rack version. Use the individual slot diagrams for the CR 700-1 and CR 700-2F. When choosing a spare, compare photos of the nameplate, backplane and positions 0, 3 and IM.
S5-115H and S5-115F layouts
ST 50 shows up to four I/O modules in the S5-115H and S5-115F with this rack. The CPU 942H and CPU 942F have separate system tables. Verify the A/B interface and slot arrangement against the manual for the installed H or F system.
The S5-115F diagram shows an IM 304 and IM 324 for the A/B link. With centralized expansion, the IM 306 occupies the separate IM position. If an expansion rack such as the ER 701-1 is present, record the interface modules and connecting cables by the markings at both ends.
Editor’s note
1. Record the rack layout. Safely isolate power. Photograph the rack nameplate, CPU and PS codes, slots 0–3 and the IM position.
2. Count the boards inside each adapter. On an S5-115U, record both boards if slot 0 or 3 contains a two-board casing. Check the fan and airflow for the dual-board arrangement.
3. Isolate an interrupt fault. If an input reads correctly but its interrupt fails on an S5-115U, check whether the module is in slot 3. Verify the permitted slot and address before moving it.
4. Match the IM position. Record the position of any existing interface module or terminator. In an H or F system, label the A and B cable ends separately.
5. Separate a slot fault from a rack fault. If one position is affected, inspect the guide and backplane socket. If several modules are affected, check the power-supply indicators and shared backplane.
6. Verify before returning to service. Restore the recorded module positions and check I/O addressing. For an H or F system, have the A/B link and relevant safety functions tested under the site procedure.
Manuals and PDF archive
See S5-115U Figure 3-3, S5-115H Figure 3-2 and S5-115F Figure 3-3 for the slot diagrams. Compare ST 50 pages 3/59, 3/67 and 3/72 for capacity. Siemens S5 PDF archive.