6ES5 956-0AA12

Siemens 6ES5 956-0AA12 15 V Auxiliary Submodule for PS 955

The Siemens 6ES5 956-0AA12 is a +15 V auxiliary supply submodule fitted inside a PS 955 power supply. In SIMATIC S5 systems, 6ES5 956-0AA12 produces a stabilized 15 V output from the power supply's 24 V auxiliary rail. Siemens specifies a maximum output current of 0.5 A in the technical table for 6ES5 955-3NA12.

In Siemens S5 PLC installations, the submodule provides the additional 15 V rail where the application requires it. When assessing an S5 power supply, distinguish its main 5 V output current from the capacity of the 15 V auxiliary output. A high main-output current rating does not apply to the 956 submodule's 15 V output.

Input, output and current budget

Input: the power supply chassis's 24 V auxiliary voltage. Output: stabilized +15 V DC. The ST 50 table for 956-0AA12 with 955-3NA12 specifies 0.5 A maximum output current, with input current approximately equal to output current.

The 955-3NA12 system manual also specifies a combined 0.8 A current budget for the 24 V/15 V auxiliary outputs. Calculate the 15 V load together with the other auxiliary loads on the same power supply. The 0.5 A output limit does not mean that all auxiliary outputs can independently operate at full load simultaneously.

PS 955 compatibility and document scope

The technical table on page 4/136 of Siemens ST 50 gives the 956-0AA12 data specifically for 955-3NA12. The same catalogue's ordering list on page 4/156 also lists the submodule for 6ES5 955-3NF11 and 6ES5 955-3LF12 power supply chassis. Match the actual power supply's complete code and revision to its own installation documentation.

Other PS 955 models, including 6ES5 955-3LC41, 6ES5 955-3LF41, 6ES5 955-3NC41 and 6ES5 955-3NF41, require separate assessment of their output arrangements. Do not assume that every 955 model needs the same additional submodule or uses identical internal connections.

6ES5 956-0AA11 is a separate order code in the related family. Do not ignore the suffix when selecting a replacement; compare labels, connection arrangements and the relevant power supply documentation.

SINEC H1 and communication supply

The Siemens manual associates the 15 V auxiliary submodule with SINEC H1 operation. The ST 50 ordering description specifies a supply for the Industrial Ethernet bus connector. When reviewing CP 535 records such as 6ES5 535-3LB11, 6ES5 535-3LB12 and 6ES5 535-3MA12, assess the supply requirements of the communication processor and line connection as well.

When investigating communication faults, check interface modules, cables and connectors and the auxiliary supply together. For expansion-unit applications such as EG 185U, the rack family alone does not establish compatibility; verify the power supply and submodule combination.

Protection, indication and installation

The 955-3NA12 description states that the auxiliary submodule is short-circuit protected and its output voltage is monitored. A low voltage causes the power supply's 15/24 V o.k. indicator to go out, and overvoltage protection is provided. Treat the indicator as diagnostic information alongside voltage measurements under load.

The submodule fits in the designated location inside the power supply. Siemens requires the auxiliary submodule to be inserted only with power off. Check connector orientation and mechanical seating against the installation drawing; do not apply an external supply using an assumed pin assignment.

Before servicing the power supply, assess CPU memory cards, program backups and the existing backup-supply arrangement. Retain recoverable copies of the project and machine parameters to reduce the risk of data loss.

Editor's Note

Check the 956 submodule label first, then the complete code of the 955 power supply that will receive it. “Removed from an S5” is not enough information. Pay particular attention to 0AA11 versus 0AA12 and the power supply suffix.

Do not rely solely on a no-load 15 V reading. In a suitable test arrangement, confirm stable voltage within the permitted load limits. Keep the 0.5 A specification for the 955-3NA12 application separate from the main 5 V output rating.

If the 15/24 V o.k. lamp is off, do not immediately blame this submodule. Check the 24 V auxiliary rail, connected loads for short circuits or excessive consumption, and connector condition. Do not bypass the protection circuit to keep the system running.

Inspect burn marks, darkened connectors, corrosion and previous repair work. Remember that the submodule must be inserted with power off; internal power supply connectors are not intended for trial disconnection and reconnection while energized. Have qualified personnel follow the installation drawing.

If replacing the module to address a communication fault, verify actual communication as well as the restored 15 V supply. A second cable or connection fault may remain. Keep the old unit's label and measurement results in the service record.

OtomasyonAVM resources and PDF documentation

Use About Siemens S5 PLC for system information and the Siemens S5 PDF archive for documentation. For this model, assess Siemens ST 50, 1998, pages 4/136 and 4/156 alongside S5-135U/155U System Manual, C79000-G8576-C199-07, section 4.4.

Related topics

6ES5 955-3NA12 · 6ES5 955-3NF11 · 6ES5 955-3LF12 · 6ES5 956-0AA11 · CP 535 communication processor

Navigation: 6ES5 956-0AA12 model page | S5 power supplies | SIMATIC S5 main page | Siemens S5 PLC models | Used Siemens products

Siemens documents and external references

Siemens S5-135U/155U System Manual — English PDF: 955-3NA12 and the 15 V auxiliary submodule, printed pages 4-57–4-69; exact order code in Appendix A, page A-3.

Siemens ST 50, 1998 — English catalogue section: technical table on page 4/136 and ordering description on page 4/156; Siemens document hosted by E&M.