6ES5 945-7UA21

Siemens 6ES5 945-7UA21 – S5-115U CPU 945, 384 KB Memory

Siemens 6ES5 945-7UA21 is the CPU 945 central processing unit for S5-115U in the SIMATIC S5 family. It provides 384 KB of internal user memory and executes STEP 5 programs. Within an S5 system, it handles program execution, data exchange with digital and analog modules, and serial communication.

The Siemens technical table gives consumption without an interface module as typically 0.5 A from the internal 5 V supply and 0.06 A from 24 V. Assess the S5-115U power supply, rack arrangement and additional module loads together. These figures are not the complete installation’s total consumption.

Internal memory and memory-card capacity

The CPU’s 384 KB internal memory and the capacity of a removable memory card are separate specifications. Installing a larger card such as 6ES5 374-1FJ21 does not automatically increase the CPU’s usable internal memory. Check card capacity, type and programmer-software support together.

CPU 945 executes its program from internal RAM; the Flash EPROM card stores and transfers the program. Compare the backup read from the running controller with the card contents. Later application changes should not be assumed to have been written to the archive card.

SI1 and optional SI2 connections

SI1 is a 15-pin serial port using a 20 mA current loop. Assess PG/OP and SINEC L1 use against the applicable settings. Match the programming cable to the electrical interface and pin assignment, rather than connector shape alone.

SI2 depends on the installed interface module. The manual lists the 6ES5 752-0LA52 programmer module and 6ES5 752-0LA62 SINEC L1 module as separate options. Other serial connection types and protocols require suitable modules. Check the interface hardware together with DB1 parameters. Insert or remove the interface module only with power switched off.

DB1 parameters and operating-system version

The Siemens COM DB1 table identifies 945-7UA21 as the 384 KB version. Its starting compatibility entry pairs CPU revision A01 with the 6ES5 816-5AA01 operating-system module, A01. Record the CPU and operating-system module labels separately during maintenance.

Back up the existing DB1 before changing parameters. Match communications, retention and startup behaviour to the machine’s own project. An old example DB1 should not be transferred wholesale to an operating machine.

Distinguishing related CPU references

Do not confuse the memory capacities of 6ES5 945-7UA11 and 7UA21: the COM DB1 table specifies 256 KB for 7UA11 and 384 KB for 7UA21. Check the complete reference and operating-system suitability for other versions such as 6ES5 945-7UA13 and 6ES5 945-7UA23 as well.

If replacement with a two-interface CPU 943 or two-interface CPU 944 is being considered, review memory, instruction use, communications and program structure together. Membership of the S5-115U family alone does not establish direct replacement suitability.

Commissioning and fault checks

Trace digital-input, digital-output and analog-module addresses, wiring and diagnostics through the existing project. Record RUN/STOP and fault indications, and establish when the problem occurs before changing the program or parameters.

Editor’s Note

Obtain clear photographs of the 945-7UA21 reference, CPU revision and operating-system module. With used Siemens CPUs, a generic “CPU 945” description is insufficient for matching the actual assembly.

If a second connection is required, request a photograph of the SI2 receptacle. A receptacle does not establish that the required interface module is fitted. Check the installed module reference and cable together.

Store the RAM backup and Flash-card contents separately. An older card may lack the machine’s latest changes. Cosmetic condition does not establish that its program is current.

Check retention settings and backup condition before any power-interruption test. Save the program, data blocks and existing settings first. A test should not put the machine’s operating data at risk.

In Siemens S5 maintenance, a RUN indication is only a limited check. Establish what was actually tested for PG access, program loading, the installed SI2 function and peripheral communication.

OtomasyonAVM resources and PDFs

Start with the 6ES5 945-7UA21 product page, S5 memory cards and the SIMATIC S5 overview. Use the OtomasyonAVM S5 PDF archive to locate relevant documents. In the English CPU 945 manual, Chapter 2 covers memory and hardware, Chapter 12 covers communications, and printed page 15-15 contains technical specifications. Table 1-1 of the COM DB1 manual provides the exact CPU and operating-system compatibility entry.

Related topics

+ 945-7UA11 · 945-7UA13 · 945-7UA23 · CPU 943, two interfaces · CPU 944, two interfaces

Browse SIMATIC S5

+ SIMATIC S5 · Siemens S5 PLC · S5 racks · Used Siemens overview