Siemens 6ES5 944-7UB11 CPU 944B – SIMATIC S5-115U Processor

Siemens 6ES5 944-7UB11 is a CPU 944B processor for SIMATIC S5-115U, featuring 96 KB of internal RAM and one serial interface. It executes the SIMATIC S5 program using STEP 5 instructions and controls digital and analog modules. In Siemens S5 PLC installations, it handles machine sequences, interlocks and process control tasks.

This complete order number identifies the single-interface version. 6ES5 944-7UB21 is the CPU 944 version with two serial interfaces. Where an installation uses the second interface for communication, review the existing connections and project before selecting UB11.

Program memory and memory submodules

The technical table specifies 49,152 instructions of internal program memory. At the usual two bytes per instruction, this corresponds to 96 KB. When choosing S5 memory modules, distinguish CPU RAM capacity from the capacity of the fitted EPROM/EEPROM. 6ES5 375-0LC31 is an 8 KB EEPROM option and 6ES5 375-0LC41 is a 16 KB option; neither stores the full 96 KB capacity of the CPU RAM.

CPU 944 copies the program from a suitable memory submodule into internal RAM for execution. Retaining RAM contents during a power interruption depends on battery backup. Before replacement, compare a PG backup of the running program with the version stored in the memory submodule.

Serial interface and programming connection

The front 15-pin serial connector uses a 20 mA TTY current-loop interface. For PG/OP or suitable SINEC L1 connections, verify the electrical compatibility of the adapter and S5 cables and connectors. Connector shape alone does not justify using a direct RS-232 cable. Review S5 interface modules and S5 communication modules separately against the installation’s communication requirements.

Instruction processing and software resources

Binary operation execution takes approximately 0.8 µs; word operations take approximately 0.8–3.6 µs. These are instruction times, not the overall machine scan time. The CPU provides 128 timers, 128 counters and 2,048 flag bits. Scan monitoring is approximately 500 ms and can be modified.

Field signal voltage and channel count depend on the installed S5 digital input, S5 digital output and S5 analog modules. Software timer and counter quantities do not represent physical I/O channels. Check module addresses together with the corresponding program accesses when replacing hardware.

Power consumption and rack installation

Allow for a typical CPU load of 0.2 A from the internal 5 V rail. Consumption from the 24 V rail is 0.04 A without a programmer and 0.06 A with a programmer. Weight is approximately 0.8 kg. Assess the S5 power supply and existing units such as 6ES5 951-7LB14 PS 951 against the combined load of all installed modules.

On central racks such as 6ES5 700-0LA12 and 6ES5 700-1LA12, the processor occupies the designated CPU position. I/O slot addresses cannot be derived from the CPU order number. Record the rack arrangement, connectors and any expansion connections before removal.

Related codes and fault diagnosis

Related codes such as 6ES5 944-7UA11, 6ES5 944-7UA12 and 6ES5 944-7UA22 should not be proposed as UB11 replacements without checking the complete version. Include the operating system submodule, memory hardware and serial interface requirements in the decision. Front-panel RN/ST, QVZ, ZYK and BASP indicators support diagnosis; STOP alone does not establish a defective processor.

Editor’s Note

Start by checking the number of connectors. This UB11 has one serial interface. If a second communication cable is connected to the original CPU, do not order from the “944B” designation alone; compare the full label and connection arrangement.

Secure the backup before touching the battery or memory. The latest program running in RAM may differ from an older EEPROM copy. Verify the PG backup, check battery condition and review causes of memory data loss.

A failed PG connection does not immediately condemn the CPU. Have the TTY adapter, cable and connector pins checked. Where possible, try a known working connection set; an ordinary serial cable is not sufficient for this interface.

Do not finish the test at the RUN light. Read the program, check controlled RUN/STOP transitions and test operation with the existing I/O. Record the operating system submodule code and make the scope of the supplied CPU clear.

Keep an overall reset as a considered step. Record QVZ and ZYK conditions, the BASP indication and PG diagnostics first. An overall reset affects RAM and can reload the program from fitted memory. Check the supply and connections before declaring the board faulty; remove or insert modules with power switched off.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLC for series information and the S5 PDF archive for documents. The main reference for this model is S5-115U Programmable Controller Manual, EWA 4NEB 811 6130-02b, Edition 04. The exact 6ES5 944-7UB11 technical table is on printed page 15-18, PDF page 546.

Related topics

CPU 944-7UB21 · CPU 944-7UA11 · CPU 944-7UA12 · CPU 944-7UA22 · S5 memory options. These pages support comparison and do not confirm direct interchangeability.

Navigation: 6ES5 944-7UB11 main page | Used Siemens models | Siemens S5 PLC | SIMATIC S5

Siemens and external references

Siemens S5-115U system manual – EWA 4NEB 811 6130-02b, Edition 04 (English). Memory selection is covered on printed page 2-28, program transfer on 4-3 and the TTY connection diagram on C-2.