6ES5 923-3UA11
Siemens 6ES5 923-3UA11 – 923A coordinator, bus arbitration for 2–4 CPUs
Siemens 6ES5 923-3UA11 is the 923A coordinator for S5-135U systems in the SIMATIC S5 family. It allocates shared S5 bus access to two to four CPUs and supports data exchange through IPC flags. In this Siemens S5 architecture, the module operates from 5 V DC with 0.5 A typical consumption.
923A and 923C have different functions. The central PG connection provided by the 6ES5 923-3UC11 923C is absent on the 923A. The system manual describes suitable multiprocessor configurations using CPU 922, CPU 928 and CPU 928B. Review exact CPU codes and access methods in projects using a CPU 922 or CPU 928A. The 923A cannot be used for multiprocessor operation when a CPU 948 is fitted.
Bus arbitration and shared memory
The coordinator cyclically grants each CPU access to the common bus. Its communication memory is RAM backed up through the central system. Keep this memory separate from CPU program memory and S5 memory module capacity. Document which CPU reads and writes each shared variable in the STEP 5 application.
The IPC flag area occupies F200H–F2FFH, totalling 256 bytes, in 32-byte sections. For example, F200H–F21FH corresponds to bytes 0–31 and F220H–F23FH to bytes 32–63. Check the shared-data map using suitable programming software. Where a CP uses an IPC section, that section must be masked on the coordinator.
CPU count, jumpers and operating mode
The CPU count is selected at jumper location EP62; IPC sections are enabled or masked at EP7. Photograph the existing settings and compare them with the actual CPU count before replacement. Match the board revision rather than copying a similar-looking module.
The front selector provides RUN, STOP and TEST. TEST is intended for multiprocessor commissioning and affects BASP behaviour. Verify the normal operating configuration after commissioning, together with CPU selectors and outstanding STOP requests.
Programmer access and I/O checks
The 923A has no central PG multiplexer. Select the PG cable for the relevant CPU connection. Assess interface modules and communications modules separately from the coordinator’s bus-arbitration function.
Confirm which CPU accesses each digital input and digital output module. Multiprocessor global-memory access to 0000H–EFFFH with CPU 928/928B requires the 923C coordinator. Review this access method before choosing a replacement.
Supply, installation and dimensions
The supply specification is 5 V DC ±5%. RAM backup comes from the central system, so inspect the S5 power supply and backup circuit together. The instructions specify slot 3 in the S5-135U. Match the actual rack arrangement to the central controller being used.
Dimensions are 20.32 × 233.4 × 160 mm (W × H × D), weight approximately 0.3 kg, protection IP00 and operating temperature 0…+55 °C. Two 48-pin backplane connectors connect the board to the S5 bus. Switch off the central controller before removing or inserting the module.
Diagnostics, revisions and used-unit checks
During PLC troubleshooting, inspect all CPU states, shared-data exchange and supply conditions together. Assess a used PLC module through its required functions. For used Siemens equipment, request the complete label, jumper photographs, selector condition and a functional check in a suitable system.
Preserve the 923A/923C distinction in model and revision comparisons. If assessing Derell PLC options for modernization, redesign multiprocessor task allocation, shared variables and I/O access for the new project.
Editor's Note
Check the 923A designation and complete 3UA11 code first. This module handles bus arbitration and shared data; it does not provide the 923C central programmer connector.
Record the CPU count and EP62 settings together. A board from a two-CPU system needs its configuration checked before installation in a four-CPU system. Keep photographs of the original arrangement.
Compare the F200H–F2FFH IPC map with both application and CP settings. Establish which device owns each section before enabling overlapping address areas.
Check the TEST configuration carefully. Its effect on BASP can change output behaviour during commissioning. Verify the normal operating settings before returning the machine to service.
Recheck coordinator selection if the system uses a CPU 948 or global-memory access. Inspect the battery and 5 V supply, preserve program and setting backups, and remove the module only with power off.
OtomasyonAVM resources and PDFs
6ES5 923-3UA11 main page · Used Siemens S5 models · Siemens S5 PDF archive
The main reference is 923A Coordinator Instructions, C79000-B8576-C263-08, section 6 of the CPU 921/922 manual. CPU restrictions and specifications were cross-checked against sections 6.4 and 6.6 of the S5-135U/155U System Manual, C79000-G8576-C199-07. These documents are in English.
Related topics
6ES5 923-3UC11 – 923C · 6ES5 922-3UA11 · 6ES5 928-3UA21 · Derell PLC options
Navigation
SIMATIC S5 · Siemens S5 models · Used Siemens · S5 racks · S5 communications modules
Siemens and external references
Siemens 923A Coordinator Instructions – C263-08, English
CPU count and F200H–F2FFH IPC addressing, printed 7 · Supply, installation and technical data, printed 5
923A application and CPU 948/global-access restrictions, printed 6-15 · 923A/923C technical comparison, printed 6-28