6ES5 700-8MB11
Siemens 6ES5 700-8MB11 – S5-100U Interrupt Bus Unit, 2 Module Positions
Siemens 6ES5 700-8MB11 is an interrupt-capable bus unit for the S5-100U in the SIMATIC S5 family. This component of the S5 bus and mounting arrangement provides two I/O module positions and SIGUT screw terminals. It connects the installed modules to field wiring and the internal bus.
Its distinguishing feature is process-interrupt transmission with a suitable CPU and module. The bus unit itself is not an independent I/O module; channel type, voltage and current ratings depend on the module fitted to it.
Conditions for interrupt operation
The Siemens manual specifies interrupt processing for CPU 103 version 8MA02 and later. With a 6ES5 103-8MA02 or 6ES5 103-8MA03, the interrupt bus unit must be directly beside the CPU, at module positions 0 and 1. In a later position it functions as a normal bus unit.
Process interrupts require a four-channel digital input module or suitable comparator module on this bus unit. Check the digital input module type as well as its mechanical fit. An eight-channel input module does not gain interrupt capability simply by being installed on this base.
The CPU must be in RUN, OB2 must be programmed, and interrupt processing must not be disabled by an IA instruction. Check the STEP 5 program and blocks accessed through the programming software against the hardware arrangement.
DIN rail mounting and bus connection
The unit mounts on a suitable 35 mm DIN rail; 6ES5 710-8MA11 is one rail option for this arrangement. Adjacent bus units are interconnected by a flat ribbon connection. Inspect cables and connectors for ribbon damage, bent contacts and loose retainers.
An S5-100U arrangement supports up to 16 bus units. This does not provide 16 interrupt positions; interrupt acquisition is restricted to the first unit beside the CPU. For multiple tiers, select IM 315, IM 316 and a suitable 712 connecting cable against the system configuration.
SIGUT terminals and field wiring
Each module position has 10 terminals. Siemens specifies conductor sizes of 2 × 0.5–1.5 mm² for stranded conductors with end sleeves and 2 × 0.5–2.5 mm² for solid conductors. Match terminal numbers to the wiring diagram of the installed module.
When fitting a digital output or analog module, select field voltage and signal wiring according to that module’s specifications. Distinguish the internal bus supply from the sensor or load supply.
Bus supply and dimensions
The manual specifies typical consumption of 11 mA from the CPU’s internal +9 V bus supply. Include the installed I/O modules when checking the power supply and available CPU bus capacity.
The S5-100U manual gives dimensions of 91.5 × 162 × 39 mm and a weight of approximately 320 g. ST 50 lists a depth of 41 mm including the rail; check the measurement basis when planning cabinet space.
Comparison with other bus units
6ES5 700-8MB21 is the interrupt-capable version with crimp connections. 6ES5 700-8MA11 is a normal screw-terminal bus unit; 6ES5 700-8FA11 has screw terminals and increased EMC protection; 6ES5 700-8MA22 has crimp terminals and increased EMC protection. Retain interrupt capability when replacing a unit in an interrupt position.
Editor’s Note
When buying a used Siemens component, check the full 700-8MB11 label and ALARM markings. Confirm the screw-terminal version against the installed wiring. Changing between screw and crimp connections creates additional wiring work.
If interrupts do not work, first check the CPU version, first bus-unit position and installed input module. An eight-channel input module cannot provide the required interrupt function. A working interrupt base installed farther along the bus performs only the normal bus function.
Inspect the housing for cracks, the rail latch for damage and the terminals for heat damage or looseness. Check the ribbon and bus contacts too. If moving a module changes the fault, inspect the base connection as well as the plug-in module.
Record wiring and module order before dismantling the S5 system. Switch off power before replacing the base or changing its wiring. Compare terminal numbers individually during transfer; cable colour alone is not a reliable identification method.
After assembly, check diagnostics and normal I/O operation, then use a controlled input event to confirm that OB2 is called. RUN indication alone does not verify interrupt operation. Record the CPU version, installed modules and changes for the next technician.
OtomasyonAVM resources
+ 6ES5 700-8MB11 model page · Siemens S5 second-hand models · S5 bus units and racks · About Siemens S5.
Related topics
+ 6ES5 700-8MB21 · 6ES5 700-8MA11 · 6ES5 700-8FA11 · 6ES5 700-8MA22. These links compare interrupt functions and terminal types; the versions do not all provide the same functionality.
Browse SIMATIC S5
+ SIMATIC S5 CPU models · S5 digital inputs · S5 digital outputs · S5 cables and connectors · Siemens second-hand main page.
Siemens and external references
+ Siemens S5-100U System Manual, English. EWA 4NEB 812 6120-02b; printed page 14-12: exact 700-8MB11 specifications; 10-1: CPU version, position, module and OB2 requirements; Appendix D: accessory order numbers.
+ Siemens ST 50 SIMATIC S5 Catalogue, English. Printed page 2/75: bus-unit connection types, terminals per module position and dimensions including the rail.