6ES5 453-4UA12

Siemens 6ES5 453-4UA12 — 16-Channel Isolated 24 V DC / 2 A Digital Output

The Siemens 6ES5 453-4UA12 is a 16-channel digital output module with individual galvanic isolation and 24 V DC / 2 A outputs in the SIMATIC S5 family. Its wiring arrangement supports L+ or L− switching. Within the S5 digital output range, it provides separate output circuits, an enable input and common short-circuit signaling.

It is used in suitable S5-135U/155U Siemens S5 PLC and S5 rack arrangements. The nominal load supply is 24 V DC, with a permissible range of 20–30 V DC. Match each channel’s separate +/− terminal pair to the existing connection drawing.

Load current and ventilation conditions

The channel switching-current range for resistive and inductive loads is 10 mA–2 A. Section 8.4.11 of the system manual also specifies a maximum total switching current of 4 A per eight outputs. This total-current limit does not make those channels a common-potential isolation group. Ventilation and temperature conditions must also be included in the load assessment.

The manufacturer specifies 49 W power dissipation at rated operation. Apply the manual’s separate coincidence-factor conditions for ventilated and unventilated operation. Distinguish the internal S5 power supply from the field-load supply; typical consumption from the 5 V system bus is 120 mA.

For inductive loads such as relay and valve coils, the manual specifies maximum switching frequencies of 0.2 Hz at 1 A and 0.1 Hz at 2 A; the resistive-load limit is 100 Hz. Inspect existing diodes and other suppression components together with the intended switching duty.

F+/F− enable input and X20 jumper

F+/F− is the 24 V DC enable input. With jumper X20 fitted, the input is active; this is the manufacturer’s factory setting. If the PLC program issues a command but the output remains off, inspect the existing enable circuit and jumper position. Preserve the machine’s enable arrangement instead of changing the jumper to work around the fault.

Short-circuit indication and H+/H− signaling

The module provides short-circuit protection, green channel-status LEDs and a common red fault LED for all 16 outputs. H+/H− is a floating short-circuit signaling circuit shared by all channels; it generates a logic-1 signal when a short circuit occurs.

The H circuit needs a separate supply and its signaling output is limited to 10 mA. Do not use it to drive a valve or relay load. During troubleshooting, check the output command, F enable circuit, channel load supply and H fault information separately.

42-pin front connector and EMC arrangement

The module is 40 mm wide and occupies two slots, with an approximate weight of 0.6 kg. Within the S5 cable and connector range, match the 497-4UA12 crimp or 497-4UB31 screw-terminal 42-pin front-connector option to the existing installation. Preserve the individual channel connections rather than assuming a common return.

Siemens’ CE installation notes for this exact order number require a shielded signal cable and a SIFI C or equivalent filter in the 24 V DC load supply. Maintain shield contact and grounding connections in accordance with the manufacturer’s installation arrangement. Isolate power before removal or installation.

Comparison with similar order numbers

The 454-4UA14 also has sixteen 24 V DC / 2 A outputs, but they form one isolation group. The 451-4UA14 is a 32-channel / 0.5 A module, while the 457-4UA12 is rated 24–60 V DC / 0.5 A. Sharing a rack family does not establish the same electrical function.

Do not assume interchangeability with the 453-4UA11 from the similar code alone. The 454-7LA12 belongs to a different S5-115U/F module family. Match channel isolation, enable arrangement, connector and load limits when selecting a replacement.

Editor’s note

Start by tracing both terminals of each channel. Do not assume that all output returns are shared. Individual isolation remains useful only when the field wiring preserves the intended arrangement.

If the board is fitted and the program runs but there is no output, remember the F enable input. Photograph the X20 jumper and front connector before removing the old board. Installing a sound replacement does not automatically establish its enable condition.

Do not let the 2 A label distract you from cabinet temperature. Check the fan, airflow and which loads operate together. A modest ventilation problem can become a lengthy investigation once the module is loaded.

The H output reports a fault; it is not a load output. When the red LED appears, record the affected channel and connected load. Recording the symptom is more useful than repeatedly replacing the same board.

When buying a used Siemens 453-4UA12, seek a suitable test of every channel together with the enable and fault-signaling circuits. Inspect the label, connector and evidence of previous intervention. A few working outputs do not establish all of the board’s functions.

OtomasyonAVM resources and PDFs

+ OtomasyonAVM S5 PDF archive. Detailed specifications and the connection drawing appear on pages 8-52 and 8-53 of the S5-135U/155U manufacturer manual below.

Related topics

+ 453-4UA11 · 454-4UA14 · 451-4UA14 · 457-4UA12 · 497-4UA12 connector · PLC troubleshooting.

Browse SIMATIC S5

+ S5 digital output modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-135U/155U system manual — English; C79000-G8576-C199-07; section 8.4.11, pages 8-52–8-53: specifications and wiring; 8.1.2: enable; 1-5: EMC.

+ Siemens S5-135U/155U system manual — German; C79000-G8500-C199-07; section 8.4.11: total current per eight outputs and loading conditions.

+ Siemens ST 50, 1998 catalog — English; pages 4/39 and 4/41: 453-4UA12 features, EMC footnotes and connector ordering data; externally archived copy.