6ES5 445-3AA11
Siemens 6ES5 445-3AA11 – 32-Channel 24 V DC Digital Output Module
6ES5 445-3AA11 is a 32-channel electronic digital output module rated at 24 V DC / 0.5 A in the Siemens SIMATIC S5 family. This S5 output board has no galvanic isolation. In addition to the individual channel limit, each of its two output groups is limited to 4 A total.
The model is documented in the compact I/O instructions for SIMATIC S5 S5-130K, S5-130W and S5-150K. Match the S5 system architecture, rack and addressing arrangement against the installed hardware.
Supply and load current
Nominal load supply is 24 V DC, with a permissible range of 20–30 V DC. Assess board power and field-load circuits separately during power supply and PLC supply checks.
The specified output operating-current range is 5 mA–0.5 A, with a maximum 5 W lamp load. For a contactor or control relay coil, check inrush current alongside continuous current. Inductive loads such as a relay coil require suitable suppression arrangements.
Group limit and fuse protection
The manufacturer's instructions specify two groups, each with one T4 A fuse. The combined output current in each group must not exceed 4 A. Include this limit when selecting fuses and calculating load current, rather than considering only the 0.5 A channel rating.
The outputs have electronic short-circuit protection; check the group fuses separately as well. If one group fails to operate, inspect its load supply, fuse and field wiring together.
Non-isolated construction and connections
Two separately fused groups do not imply two isolated circuits. Check S5 connection parts, the connector arrangement and shared reference connections against the machine diagram.
Before fitting the board into an S5 rack, check rack/slot suitability and board contacts. Dimensions are 19 × 244 × 202 mm (W × H × D), with an approximate weight of 0.3 kg.
Switching and addressing
Maximum switching frequency is 100 Hz for resistive loads, 2 Hz for inductive loads and 11 Hz for lamp loads. Select the applicable value according to the actual load.
The byte address is set through the board's addressing socket/coding plug. Compare this setting with the CPU project and output addresses in the PLC program. During troubleshooting, check the command state, group supply and output voltage under load together.
For intermittent faults, inspect electromagnetic interference, power-cable routing and earthing connections. Pay particular attention to reference-circuit faults in this non-isolated arrangement.
Related order numbers and used-module checks
6ES5 445-3AA12 is a different version. 6ES5 444-3AA11, 6ES5 450-3AA11 and 6ES5 451-3AA11 differ in output count, current rating or isolation. Verify the complete order number, wiring and addressing before selecting a spare.
On used Siemens equipment, inspect the label, fuse holders, connectors and signs of overheating. Test all 32 outputs with suitable loads while respecting channel and group current limits.
Editor’s note
Keep the 0.5 A channel limit and 4 A group limit together in your calculations. Every load may be suitable individually while the group total is too high. A group drawing 4.5 A needs its load distribution corrected even if no individual channel exceeds its rating.
Two fuses do not mean two isolated groups. This model is non-isolated. Follow the shared reference and return connections carefully in an older cabinet; a similar front connector is not enough to establish compatibility.
If one group stops working, check before condemning the whole board. Start with the fuse, load supply and field wiring. If a fuse has blown, find the cause instead of fitting a larger one to get past the fault.
Photograph the addressing socket and existing jumper positions before removing the board. A replacement with different settings can appear faulty even when it is sound. Use the machine records instead of guessing, and save yourself a search for addresses later.
With a used board, a few illuminated LEDs are only a start: check every output under a suitable load. Isolate the board and field-load supplies before removal or insertion. Finish by checking and tidying the wiring and fuse connections.
OtomasyonAVM resources and PDFs
Start with the OtomasyonAVM Siemens S5 PDF archive, About Siemens S5 and S5 digital output modules.
The technical values for this model come from the 6ES5 445-3AA11 section on page 16 of Siemens compact digital I/O operating instructions C79000-B8500-C233-3. The same page appears as page 158 in the online collection below.
Related topics
+ 6ES5 445-3AA12 · 6ES5 444-3AA11 · 6ES5 450-3AA11 · 6ES5 451-3AA11.
+ Fuse rating and load current · PLC troubleshooting · Connectors.
Browse SIMATIC S5
S5 digital output modules · S5 connection parts · S5 PDF archive · Used Siemens equipment
Siemens and external references
+ Siemens 6ES5 445-3AA11 technical table – online copy of the German manufacturer's instructions: channel/group current, fuses, supply, switching and mechanical specifications.
+ Siemens C79000-B8500-C233-3 – technical description and addressing: compact-module system scope, coding plug and byte/bit addressing.