6ES5 464-8MF11

Siemens 6ES5 464-8MF11 — 2-Channel Pt100 / ±500 mV Analog Input Module

The Siemens 6ES5 464-8MF11 is a two-channel Pt100 / ±500 mV analog input module for SIMATIC S5 installations using S5-90U, S5-95U, S5-100U, ET 100U or ET 200U. Within the S5 analog module range, it handles resistance and low-level voltage measurements. The nominal resistance range is 0–200 Ω, with an extended measuring limit of approximately 400 Ω.

It converts the resistance of a Pt100 temperature sensor or an external millivolt signal into a value for the CPU. Applications include temperature monitoring and PLC-based PID control. The 8MF11 does not linearize the Pt100 characteristic internally; conversion to °C must be provided by the appropriate processing in the application program.

Pt100 measurement and the 8MF21 distinction

For Pt100 measurement, the module supplies a 2.5 mA constant current. The nominal scale is 200 Ω = 2048 measurement units, with 100 Ω = 1024 units. These units are not the unprocessed decimal value of the input word. The selectable linearization available on the 6ES5 464-8MF21 must not be assumed for this module.

Check the sensor identification: a Pt1000 cannot simply replace a Pt100 within this input range. The difference between Pt100 sensors and thermocouples also matters; wire the Pt100 circuit for resistance measurement.

Four-wire connection and terminal assignments

Channel 0: 3 = M+, 4 = M−; 7 = IC+, 8 = IC−. Channel 1: 5 = M+, 6 = M−; 9 = IC+, 10 = IC−. A four-wire Pt100 connection separates excitation from voltage sensing. When checking S5 cables and connectors, match each conductor to its function in the wiring diagram.

For ±500 mV measurement, connect the signal to M+/M− and bridge IC+ to IC− on that channel. If a Pt100 signal converter is installed, identify its output first: a 4–20 mA or 0–10 V output must not be connected directly to this millivolt input.

Power, isolation and measurement timing

The electronics draw power from the system’s +9 V backplane supply, typically 70 mA. No separate L+ field supply is required at this module. Check the S5 power supply and bus connection as part of the installation containing the S5 90/110 module group. Inputs are isolated from the grounding reference, but the two channels are not galvanically isolated from each other. The permitted potential difference between inputs is ±1 V maximum.

The front switch selects 50/60 Hz, one/two active channels and wire-break signaling. Integration takes 20 ms at 50 Hz or 16.6 ms at 60 Hz. At nominal full scale, conversion takes up to 60/50 ms per channel, respectively. Integration time is not the complete channel update time.

STEP 5 processing and diagnostics

For PLC programming, the measurement format is 12 bits plus sign, left-justified; error and overflow information in the low bits must be handled separately. The applicable Siemens FB 30 / AE:464 version uses KD=13 for Pt100 and KD=7 for ±500 mV. Select the block and addresses for the actual CPU and local or distributed I/O arrangement.

During PLC troubleshooting, examine wire-break status, overflow and the measured value together. A red wire-break LED alone does not establish a faulty module. Check the analog signal, field wiring and source as well.

Selecting an S5 card for the actual signal

Check the input range before choosing a similar-looking card: the 6ES5 464-8MC11 accepts ±10 V, the 6ES5 464-8MD11 accepts ±20 mA, and the 6ES5 464-8ME11 accepts 4–20 mA. For thermocouple inputs with linearization, examine the 6ES5 464-8MA21. These are not automatic drop-in replacements.

Editor’s note

Start with a good look at the label and the complete 8MF11 suffix. The 8MF21 may look familiar, but the existing program’s expected value format matters. A photograph of the original switch settings is a small precaution that can save a lot of work later.

If the temperature looks wrong, work through it one step at a time. Isolate the temperature sensor and its cable, then test with a suitable Pt100 simulator at known points. That gives you a clear way to separate sensor, cable and module problems.

Take a moment to identify all four wires by function rather than colour alone. Confusing the excitation and sensing connections can still leave a number on the screen. A reading obtained with verified wiring is the useful starting point.

For a used module, test both channels with the same simulator and matching settings. Compare low, middle and high points, then repeat the checks after it has been running for a while. This helps reveal differences between channels and drift that appears as the card warms up.

When looking for a spare, bring a clear label photograph and the actual signal type. With the complete part number, switch settings and wiring available, the replacement decision becomes much easier. Establish what the circuit measures before choosing its card.

OtomasyonAVM resources and PDFs

+ Browse the Siemens S5 PLC information and model pages for the controller family and the S5 analog module section for related input cards.

+ OtomasyonAVM S5 PDF archive and system manuals. For this module, consult chapters 11 and 14 of the S5-100U manual and chapter 15 of the S5-90U/S5-95U manual. The manufacturer manuals linked below are in English.

Related topics

+ 6ES5 464-8MF21 — selectable Pt100 linearization · Pt100 measurement basics · Pt100 versus thermocouple selection.

Browse SIMATIC S5

+ S5 analog modules · S5 90/110 modules · SIMATIC S5 · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-100U system manual — English; 11-6, 11-11/12 and 14-50/51.

+ Siemens S5-90U/S5-95U system manual — English; 15-78–15-82.

+ Siemens ET 100U manual — English; Pt100 wiring and model distinction.

+ Siemens Basic Functions — English; FB 30, section 4.2.

+ Siemens ET 200U manual — English; analog value processing.

+ Siemens ST 50, 1998 — English; 2/38; third-party archive copy.