6ES7 193-0CD40-7XA0
6ES7193-0CD40-7XA0 Siemens ET 200B Shield Connection for Analog Signals
Siemens 6ES7 193-0CD40-7XA0 is a shield connecting element for analog signal cables used with the TB8 terminal block in the ET 200B system. It belongs to the SIMATIC ET 200 family. Suitable clamps secure the cable braid to the element, providing an organised shield termination directly beside the station.
Within the ET 200 assembly, this component supports the shielding connection. Measuring or generating the analog value remains the task of the electronics module. Siemens identifies the part as an ET 200B accessory and lists an approximate weight of 411 g.
Relationship to the TB8 terminal block
6ES7193-0CD40-0XA0 identifies the TB8 terminal block. The 6ES7193-0CD40-7XA0 covered here is the shield connecting element used with it. Although most of the order number is shared, these are different components. Check the 0XA0 / 7XA0 ending when identifying or ordering a part.
The main terminal block, shield connecting element and cable shield clamps are separate items. When completing an existing station, establish which component is missing or damaged. A shielding accessory from another ET 200 subfamily should not be assumed to fit merely because it looks similar.
Why analog cable shielding matters
A stable reading from a sensor depends on the cable route, supply and reference connections as well as the shield termination. With signals such as 4–20 mA or 0–10 V, the sensor and analog module determine the supported measurement range. This shield connecting element does not change that range; it provides the physical arrangement for terminating the cable shield.
Electromagnetic interference around motor drives, switched loads and power cables can affect a poorly installed measurement circuit. The braid needs adequate, lasting metal contact with the shield connection. A clamp pressing only on the outer plastic jacket does not establish an electrical connection to the shield.
Suitable shield clamps
The Siemens ET 200B manual specifies the 6ES7390-5BA00-0AA0 single version for one cable with a 3–8 mm clamping diameter, and the 6ES7390-5AB00-0AA0 double version for two cables with a 2–6 mm clamping diameter. Select the clamp to suit the cable at the shield contact area.
These clamps have their own order numbers. When assessing an existing assembly, check whether the required clamps are present, whether the clamping mechanism is sound and whether the size matches the cable. The diameter in millimetres is a different quantity from the conductor cross-section in square millimetres used for signal or PE wiring.
Mounting arrangement and PE connection
The shield connecting element can be mounted on a 35 × 7.5 mm or 35 × 15 mm standard rail, or on a flat mounting surface, with TB8 fitted onto it. Siemens requires horizontal installation of the ET 200B when TB8 and the shield connecting element are mounted together on a standard rail. Allow for that requirement in the cabinet layout.
For this arrangement, the manufacturer specifies a PE conductor cross-section of 4–10 mm². The cable shields are secured with suitable metal clamps, and the shield connecting element is connected to PE. Isolate the relevant circuits during installation. Check that loose strands of braid cannot touch signal terminals and that the cable does not place strain on the connection.
Cable shielding, the analog reference and protective earthing serve different purposes. The shield connection at the sensor end must also follow the sensor and measurement-circuit instructions. Avoid applying one universal single-ended or double-ended rule to every analog cable; use the specified arrangement and account for potential differences in the installation.
Assessing an unstable analog reading
If a reading changes when a motor starts or a load switches, that timing is a useful reason to inspect shielding and cable routing. It does not prove that the shield connection is faulty. Check the power supply, sensor supply, measurement reference, wiring continuity and analog channel settings as part of the same investigation.
Maintenance checks can reveal a loose clamp, damaged braid, oxidised contact surface or a cable route changed during earlier work. Compare readings under the same operating conditions before and after a correction. A line EMC filter, cable shielding and reference connections perform different jobs; the presence of one does not confirm that the others have been installed correctly.
Manuals and technical documentation
Use the Siemens ET 200 user manuals and PDF documents page to locate the ET 200B documentation. In manual EWA 4NEB 812 6089-02c, printed page 3-5 covers the mounting arrangement and clamp options, page 3-25 shows the analog shield connection, and page 8-3 identifies the TB8 terminal block.
Editorial note: The 6ES7193-0CD40-7XA0 shield connecting element and the 6ES7193-0CD40-0XA0 TB8 terminal block are separate products. Check the complete order number, the intended TB8 assembly and the required cable shield clamps together.
Related topics
Connections and station components: ET 200 terminal blocks · connection modules · additional modules and accessories · power supply modules · power distribution components
Control and communication: What is a PLC? · What is PROFIBUS? · ET 200 communication interfaces
Technical references: Siemens 6ES7193-0CD40-7XA0 data sheet, 17 March 2017; Siemens ET 200B Distributed I/O Station, EWA 4NEB 812 6089-02c, mechanical and electrical installation sections. General shielding explanations draw on Phoenix Contact’s “Shielding basics” and control-cabinet shield connection guidance. Related-topic links do not establish direct parts compatibility between different systems.
Navigation: Siemens Automation · Siemens S7 PLC · SIMATIC S7 · Siemens ET 200 · ET 200 manuals