6ES7 193-4CB00-0AA0
6ES7 193-4CB00-0AA0 – Siemens ET 200S TM-E15S23-01 terminal module
6ES7 193-4CB00-0AA0 is the TM-E15S23-01 screw-terminal base for Siemens ET 200S electronic modules. It has a 15 mm width and 2×3 connection points. Field wiring connects to this base, with the signal-processing electronic module fitted above it. Select the part by checking terminal count, termination method and the intended electronic module’s wiring diagram together. See the ET 200 system overview for the station architecture.
Six-terminal arrangement
The front terminals are numbered 1, 2, 3 and 5, 6, 7; terminals 4 and 8 are absent. Six connection points do not establish six input or output channels. Whether a terminal carries a signal, common connection or sensor connection depends on the installed electronic module.
AUX1 passes continuously through the base without connecting to the front terminals. The power buses from the power module also continue through it. An internal AUX1 path does not make any numbered terminal an AUX1 or PE connection. When selecting power supply modules and connection components, check the station’s potential distribution against its own circuit diagram.
Differences from 4CB10 and 4CB20
6ES7 193-4CB10-0AA0 is the TM-E15C23-01 spring-terminal version with 2×3 connections. 6ES7 193-4CB20-0AA0 is the TM-E15S24-01 screw-terminal version with 2×4 connections, including terminals 4 and 8. When comparing other ET 200 terminal bases, check the actual wiring arrangement behind similar order numbers. A channel requiring four terminal points cannot simply be transferred to a three-terminal column.
Examples of supported electronic modules
The Siemens manuals for the 6ES7 134-4LB02-0AB0 voltage input and 6ES7 134-4JB01-0AB0 thermocouple input modules list 4CB00 as a usable base. For example, the 4LB02 uses terminal pairs 1/2 and 5/6 for its measurement inputs. That example must not be transferred directly to a different electronic module; terminal functions can change while the base remains the same.
Two-, three- and four-wire RTD connections
The Siemens system manual shows the TM-E15S23-01 base with the 6ES7 134-4NB50-0AB0 RTD High Feature module for two- and three-wire sensor connections. The same module’s four-wire diagrams use TM-E15S24-01 or TM-E15S26-A1 bases. Check the sensor’s wire count together with the channel setting. Do not infer suitability for another analog input module from this example.
Dimensions and packaging
The data sheet specifies 15 × 120 × 43 mm, in width × height × depth order, and an approximate weight of 55 g. The manufacturer’s packing unit contains five pieces. For a used offer, distinguish one terminal base from a five-piece pack and confirm quantity and completeness against the listing.
Installation and screw termination
The terminal base mounts on the ET 200S station’s 35 mm rail. Siemens specifies an 11 mm stripping length and a 0.4–0.7 Nm tightening torque for screw-terminal wiring. Select conductor size and ferrules using the system manual’s wiring table. Wire with the relevant supply and load voltages switched off, and inspect the rail latch, side contacts and electronic-module seating area.
During commissioning, compare wire numbers with the channel definitions in the PLC project. See ET 200 PROFIBUS and PROFINET when reviewing the station’s communication arrangement. Terminal-base selection should be considered alongside the network interface and electronic-module selection.
Editor’s Note: Request a clear photograph of the terminal face as well as the label when selecting a replacement. The 4CB00 numbering is 1–2–3 and 5–6–7. If the existing base has a wire on terminal 4 or 8, review the connection requirements before changing to this part. Inspect screw openings for damage and side contacts for discoloration.
Manuals and PDF documents
Use the documents in the Siemens ET 200 manuals section. Section 1.10, pages 23–24 of the 04/2007 Terminal Modules manual describes the base. The RTD wiring distinction appears on pages 12-83–12-84 of the 12/2004 ET 200S system manual. Usable bases for the 4LB02 and 4JB01 are listed on page 8 of their respective module manuals.
Related topics
Browse industrial communication, PLC and HMI and Siemens S7-300 for other system components and applications.
Navigation
Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home