6ES7 157-0AC83-0XA0
6ES7 157-0AC83-0XA0 – Siemens FDC 157-0 DP/PA Coupler, 1 A
6ES7 157-0AC83-0XA0 is a Siemens SIMATIC DP FDC 157-0 field device coupler. It connects PROFIBUS DP to PROFIBUS PA, supplies the PA segment and provides integrated PROFIBUS diagnostics. Browse PROFIBUS and PROFINET for more about these networks.
Supply and PA output
The input supply is 24 V DC, with a permissible range of 20.4–28.8 V DC. The PA output provides 31 V DC ±1 V and a total of 1 A / 1000 mA. Up to 31 PA field devices can be connected, subject to the segment’s combined current demand and cable voltage drop.
Stand-alone operation and DP/PA Link
Stand-alone operation uses 45.45 kbit/s on DP and 31.25 kbit/s on PA. A DP/PA Link built with an IM 153-2 can connect to the upstream DP network at up to 12 Mbit/s. This rate applies to the complete Link arrangement.
For S7-300 installations, record the CPU model, DP master settings and Link hardware together. Keep a project backup, a field-device address list and the configuration files used for the installation.
Diagnostics and address settings
The factory setting is PROFIBUS address 0, which disables diagnostics and allows transparent operation. Diagnostics or redundancy require DP slave configuration. Select a unique address from 1–125 using the DIL switches and match it in the project. Configure the PA field devices separately.
Redundancy and PA termination
Coupler or ring redundancy requires two FDC 157-0 units and a BM FDC/FDC bus module. Use an AFS for coupler redundancy, or suitable AFD/AFDiS field distributors for a ring. The integrated PA terminator can be switched on or off; check its setting against the segment drawing.
Ex variants and other couplers
This model’s PA output is not intrinsically safe. 6ES7 157-0AD81-0XA0 and 6ES7 157-0AD82-0XA0 are separate versions with Ex [ia] outputs. For hazardous-area applications, assess the coupler, field distributors and device approvals as a complete system.
6ES7 158-0AD01-0XA0 is a DP/DP coupler that exchanges data between two DP networks. Other connection options are listed under network interface modules.
Replacement and purchasing checks
Siemens identifies 6ES7 157-0AC85-0XA0 as functionally compatible with 0AC83 and suitable as its replacement. When buying a used unit, check the complete order number, terminals, switches and test conditions. Include the installed bus module’s order number in the enquiry.
Editor’s Note: Check diagnostic interpretation when replacing 0AC83 with 0AC85: a PA redundancy error is reported with status code 24H by 0AC83 and 68H by 0AC85. Review any logic and alarm messages that compare this code. Photograph the existing address and termination settings before replacement.
Manuals and PDF documents
Use the Siemens ET 200 manuals section for documentation. The 07/2011 DP/PA manual covers commissioning on pages 111–120 and exact-model specifications on pages 232–233. The 08/2015 supplement, A5E35926358-AB, pages 8–9, explains replacement with 0AC85 and the status-code change.
Related topics
Browse other system components under power supply modules, connection modules, terminal blocks, PLCs and modules and PLC and HMI.
Measurement products are listed under temperature sensors and pressure sensors. Verify PA communication, power requirements and application suitability against the selected device’s own technical documentation.
Navigation
Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home