6ES7 134-4MB02-0AB0

6ES7 134-4MB02-0AB0 – Siemens ET 200S 2AI I High Feature

6ES7 134-4MB02-0AB0 is a two-channel analog current input module for Siemens ET 200S. Designated 2AI I 2/4WIRE High Feature, this electronic module is 15 mm wide. It transfers pressure, temperature and similar measurements to the control system through suitable current-output transmitters. Check the output type when choosing products from the pressure sensors and temperature sensors sections.

Measuring ranges and resolution

The input ranges are ±20 mA and 4–20 mA. Resolution is specified as 15 bits plus sign for ±20 mA and 15 bits for 4–20 mA. Check the channel setting, transmitter output range and scaling in the PLC program together.

Cycle time and measurement error

The 0.5 ms module cycle applies with interference frequency suppression disabled. The operational error limit, relative to the input range, is ±0.1% with suppression enabled and ±0.2% with it disabled. Evaluate speed and error limits at the same parameter settings, and review the required process response when changing measurement filtering.

Two-wire and four-wire transmitter connections

A two-wire transmitter uses the same pair for its supply and measurement current. A four-wire transmitter has separate supply and signal connections. The module receives its nominal 24 V DC load supply through the ET 200S power module. Once the transmitter type is established, match the terminal wiring to the channel parameter.

The manual lists TM-E15S24-01 and TM-E15S26-A1 among the suitable terminal modules. Record the complete codes of the installed connection components and verify terminal functions against the wiring diagram. Isolation from the L+ load supply is absent in two-wire operation and present in four-wire operation. The channels are not galvanically isolated from each other.

Use within an ET 200S station

The interface module determines the station’s higher-level network connection. IM 151-1 High Feature is a PROFIBUS example, while IM 151-3 PN High Feature is a PROFINET example. Match the PROFIBUS or PROFINET arrangement to the existing project, checking hardware revisions and configuration. Browse ET 200 analog and interface modules for other station options.

Diagnostics and commissioning

A front-panel red SF LED indicates group faults. Group, underflow/overflow and wire-break diagnostics are disabled by default. Wire-break diagnostics can only be selected for the 4–20 mA range. Deactivate unused channels in the hardware configuration.

Related modules and spare selection

6ES7 134-4LB02-0AB0 handles voltage inputs, while 6ES7 134-4NB50-0AB0 handles RTD inputs. Verify the complete order number, field signal and terminal arrangement together when selecting a spare.

For a used unit, inspect the nameplate, contacts and mechanical latches. Ask which current values were applied to both channels and which wiring and filter settings were used. A test record showing the applied current alongside the PLC reading makes the results easier to assess.

Editor’s Note: Before checking the module with a current calibrator, identify which device powers the loop. The calibrator’s current-source or two-wire transmitter simulation mode must suit the existing circuit. Recording the transmitter label, loop supply and channel setting together makes commissioning after a module change easier.

Manuals and PDF documents

Use the Siemens ET 200 manuals section for documentation. In this model’s 04/2007 manual, A5E01076111-01, pages 7–11 cover technical data, 13–16 cover parameters and diagnostics, and 21–25 cover connections. Check that the cover identifies 6ES7134-4MB02-0AB0.

Related topics

Browse PLC and HMI, PLCs and modules, Siemens S7-300 and S7-300 CPU modules for other control-system components. Base your selection on the hardware list for the installed station.