6ES7 120-2AH00-0AA0

6ES7 120-2AH00-0AA0 – Siemens SIMATIC SC Two-Tier Supplementary Terminal

Series: SIMATIC SC / ET 200L-SC
Category: Two-tier supplementary terminal with screw connections for TB 16SC and TB 16IM-SC

Function and system role

6ES7 120-2AH00-0AA0 is a two-tier, 16-channel supplementary terminal with screw connections for the Smart Connect architecture within Siemens ET 200. It attaches to TB 16SC and TB 16IM-SC terminal blocks to provide additional field-wiring connections. Siemens describes this accessory family as a way to extend two-wire termination to a three- or four-wire arrangement.

The “16-channel” description refers to the physical connection arrangement. This part does not add 16 inputs or outputs to the PLC; electronic modules perform the signal processing. The supplementary terminal has no PROFIBUS address and requires no separate GSD entry.

Internal bridges and potential distribution

All terminal points within each tier are electrically connected internally. This allows one potential to be distributed to several connections. Do not treat the points on the same tier as independent feed-through terminals or connect separate signal outputs from different sensors to that common tier.

The manual describes the upper tier as suitable for distributing M or another single selected potential. Its label must match the actual wiring. When replacing a power supply or DIN rail power supply, verify the terminal plan rather than relying solely on existing wire colours. An old label may no longer describe the installed connections correctly.

Lower tier, protective earth and shielding

The manual describes the lower tier for protective conductors and shield terminals. When AC modules are used, or when the relay module switches circuits without safe isolation, Siemens requires a screw-type supplementary terminal for the protective-conductor connection. Keep the PE marking visible and assess the application against section 3.8 of the manual.

Shield termination requires a suitable shield terminal element. Mechanically clipping the plastic assembly onto the base does not by itself establish the required electrical ground connection. For a used part, separately confirm whether shield terminal elements, connecting conductors and labels are included.

Installation and dimensions

The supplementary terminal engages with the mounting grooves underneath the TB 16SC or TB 16IM-SC terminal block and locks into position. The manual specifies 115 mm width, 38 mm height and 40 mm installation depth for the two-tier assembly. The Siemens data sheet gives an approximate weight of 154 g.

Allow room for cable bends and screwdriver access in the cabinet. When inspecting a removed part, look for cracks, damaged locking features, missing screws and deformed clamping surfaces. An acceptable external appearance alone does not establish that a screw connection is sound.

Relationship to analog modules

In an SC station using 4–20 mA sensors, an electronic module such as 6ES7 123-1GB10-0AB0 performs the current measurement. 6ES7 123-1FB00-0AB0 is a voltage input module. The 6ES7 120-2AH00-0AA0 supports the wiring arrangement around these modules; it does not change their measurement type, channel count or resolution. Trace signal connections, common potentials and shielding separately in the terminal plan.

Distinction from related order codes

6ES7 120-1AH00-0AA0 is the single-tier screw-terminal version, while 6ES7 120-2BH00-0AA0 is the two-tier spring-terminal version. The 2AH00 described here has two tiers and screw connections. Check the number of tiers, connection method and especially the protective-conductor requirements when selecting a replacement.

Editor’s Note

The feature most easily overlooked is the internal bridging within each tier. Before removing wires, record the potential assigned to each tier. With the part de-energized and disconnected from the relevant circuits, check continuity to verify that the labels match the connections. When buying a replacement, inspect the screws and clamping parts, locking features and signs of overheating as well as the order-code label.

Manuals and PDF documents

Visit Siemens ET 200 manuals and PDF documents for related documentation. Technical sources: Siemens ET 200L, ET 200L-SC and ET 200L-SC IM-SC Distributed I/O Device, EWA 4NEB 780 6009-02c, sections 2.7, 3.8, 3.9 and 7.7; and the model-specific Siemens data sheet dated 6 March 2017.

Related topics

About Siemens ET 200 · PLCs and accessories · PLC and HMI systems · ET 200 terminal blocks

Navigation

Home · Siemens · Siemens S7 PLC · SIMATIC S7 · Siemens ET 200 · ET 200 manuals