6ES7 154-2AA00-0AB0

6ES7 154-2AA00-0AB0 is the Siemens IM 154-2 DP High Feature interface module for SIMATIC ET 200pro. It provides PROFIBUS DP communication between the station’s electronic modules and the higher-level PLC. The control program runs in the higher-level controller, while the interface transfers station I/O data and diagnostic information. Its field-mounted design forms part of the machine-level installation options available within the Siemens ET200 product family.

Product Description

The IM 154-2 DP High Feature connects the distributed I/O station to the network as a PROFIBUS DP slave. Data from the installed electronic modules is exchanged with the master using the addresses defined in the project. Field connections can therefore be collected at a local station. For background information, see PROFIBUS and PROFINET explained. Other interfaces are listed in the Siemens communication modules section.

Choose suitable ET 200pro electronic modules for the connected sensors and other field devices. Depending on the signals, this may involve digital input modules, digital output modules or analog input modules. These categories also contain products from other ET200 families, so check ET 200pro compatibility for each selected item.

Technical Data

Manufacturer: Siemens
Product family: SIMATIC ET 200pro
Order number: 6ES7 154-2AA00-0AB0
Module: IM 154-2 DP High Feature
Communication: PROFIBUS DP, RS-485, DP slave
Transmission rate: 9.6 kbit/s to 12 Mbit/s
Rated supply: 24 V DC
Supply range: 20.4–28.8 V DC
Module consumption, 1L+: Maximum 200 mA
Address space: 244 bytes inputs / 244 bytes outputs
Expansion: Up to 16 electronic modules
DPV1 support: Yes
Protection: IP65 / IP66 / IP67
Catalogue operating temperature: −25 to +55 °C
Dimensions, W × H × D: 90 × 130 × 59.3 mm
Approximate weight: 415 g

The address space describes the station’s communication capacity; the installed electronic modules determine the physical channel count. Likewise, distinguish the interface’s consumption from the total station demand. Operating temperature and protection requirements must account for the connection module, cables and all other station components.

High Feature and PROFIsafe Support

An important feature of this High Feature version is its support for suitable fail-safe ET 200pro modules. In a PROFIsafe application, the safety program runs in an appropriate F-controller, while the IM 154-2 provides station communication. The F-modules, controller, software packages and project settings must be compatible as a complete system.

During maintenance, the HF marking alone is insufficient to assess the installation. Where safety inputs or outputs are present, record the F-addresses, module types and safety parameters. Complete the required functional and acceptance checks after hardware replacement.

Connection Module Options

The CM module carrying the field connections is selected separately for the IM 154-2 DP. Siemens catalogues list the following options for this interface family:

6ES7 194-4AA00-0AA0: CM IM DP ECOFAST; ECOFAST connections.
6ES7 194-4AC00-0AA0: CM IM DP Direct; direct wiring.
6ES7 194-4AD00-0AA0: CM IM DP M12, 7/8"; 2 × M12 and 2 × 7/8" connections.

Check the complete connection-module code when retaining existing machine wiring. A mechanical fit alone does not establish suitability for cables and connectors; pin assignment, communication requirements and environmental protection must also match. Maintain the IP rating by fitting suitable caps to unused connections and checking seals and mating surfaces.

Station Termination and the PROFIBUS Network

The manufacturer’s ordering description includes a station terminating module; the CM connection module is a separate ordering item. Confirm the actual delivery contents, particularly when purchasing used equipment.

The station terminating module completes the ET 200pro backplane bus. The PROFIBUS terminating resistor terminates the communication segment at its ends. Having the station terminating module installed does not establish that the PROFIBUS segment is correctly terminated. Check these separately during fault investigation.

Configuration and Commissioning

Use a device definition matching the actual order number in STEP 7 hardware configuration. The Siemens system manual lists SIEM8119.GSG for the earlier 2AA00 version and a different GSD file for 2AA01. Check the product code, language and revision against the manufacturer’s GSD package.

Before commissioning, compare the PROFIBUS address, electronic-module sequence and assigned I/O addresses with the project. Back up the existing configuration before modifying an operating station. Similar-looking modules can have different data lengths or parameters, so identification should include the full part number.

Check both the electronics/sensor supply 1L+ and the load supply 2L+. Assess power supply capacity using the connected electronic modules, sensors and output loads. Any DIN-rail power supply and panel components used for power distribution should match the installation’s protection and wiring design.

LED Indicators and Troubleshooting

SF: Group fault.
BF: PROFIBUS communication fault.
ON: Electronics/sensor supply.
DC 24V: Load supply.

When BF is indicated, examine the station address, master configuration, cable continuity and termination arrangement. For SF, read the module diagnostics to identify the affected component. Steady and flashing indications can have different meanings; use the manual’s LED combination table.

Record the fault condition, LED indications and PLC diagnostic information before removing equipment. Corrosion, loose connections or damaged seals may accompany communication problems. After a power interruption or replacement, verify that the I/O data updates correctly as well as checking the indicators.

Practical Selection Notes and Related Products

When comparing this module with the related 6ES7 154-1AA00-0AB0 IM 154-1, consider the application’s High Feature and F-module requirements. Siemens documentation identifies 6ES7 154-2AA01-0AB0 as a compatible later version of this module. Still review the project, connection module and functions in use when planning replacement.

For a replacement enquiry, photographs of the interface label, CM module and complete station help establish the required equipment. Clarify whether the interface, connection module, bus base and terminating module are included in the quotation.

User Manuals and PDF Documents

+ Siemens ET200 PLC User Manuals — PDF archive page.

+ Siemens IM 154-1 / IM 154-2 Specifications and Connection Options — Siemens IK PI 2007 catalogue, PDF pages 147–148; this section includes 6ES7 154-2AA00-0AB0.

+ Siemens ET 200pro System Operating Instructions — September 2015; installation, connections, GSD selection and diagnostics. This edition also covers later hardware, so follow the information applicable to the specific order number.

+ Siemens S7 F ConfigurationPack — F-Module Compatibility Notes — interfaces supported with ET 200pro fail-safe modules.

++ Siemens Automation Main Page >
++ Siemens Product Enquiries — contact Otomasyon AVM.
++ About Siemens ET200 PLC Systems >

Reminder: Confirm current availability, condition and delivery contents with Otomasyon AVM for the Siemens 6ES7 154-2AA00-0AB0 and other SIMATIC products. Some items are used equipment; take this into account before purchasing. Products will not be restocked once sold out. This page provides general information; check the product label, hardware version and applicable manufacturer documentation for your installation.

Note: Manuals, commissioning suggestions and troubleshooting descriptions are provided for reference and are not binding. Content may be updated or expanded. The Otomasyon AVM Community welcomes practical feedback. You can share your operating and maintenance experience with us.

Technical references: Siemens IK PI 2007, IM 154-1 / IM 154-2 section; ET 200pro Distributed I/O System, A5E00335544-AJ; S7 F ConfigurationPack hardware compatibility notes. Numerical product data is taken from the catalogue table identifying the 2AA00 order number.