6ES7 142-3BF00-0XA0

Siemens Main Menu › SIMATIC S7 › ET 200 Modules

Siemens 6ES7 142-3BF00-0XA0 — ET 200eco BM142, 8-Channel 24 V DC / 2 A Output Module

6ES7 142-3BF00-0XA0 is an ET 200eco BM142 basic module in the Siemens ET 200 distributed I/O family. It provides eight 24 V DC / 2 A digital outputs through eight M12 load sockets. Among ET 200 digital output modules, it is used to control machine-mounted loads. Its protection rating is IP65/IP67 with the required installation and connections.

PROFIBUS-DP and the required connection block

The communication protocol is PROFIBUS-DP, supporting up to 12 Mbit/s. When reviewing ET 200 communication interfaces, start with the installed master and fieldbus wiring. Within the ET 200 system and product families, this device belongs to ET 200eco; do not assume wiring or project compatibility with ET 200eco PN devices.

Operation requires a separate 6ES7194-3AA00-0BA0 M12–7/8″ or 6ES7194-3AA00-0AA0 ECOFAST connection block. Select ET 200 connection modules to match the machine's power and bus connectors. Confirm whether the quotation includes just the BM142 or its connection block as well.

2 A per channel, two separate 4 A limits

Up to 55 °C, total output current is limited to 4 A for X1, X3, X5 and X7, and another 4 A for X2, X4, X6 and X8. Calculate power distribution and load groups using this socket arrangement. Four loads drawing 2 A within one group would total 8 A and exceed its limit; all eight outputs cannot deliver 2 A simultaneously.

1L+ powers the electronics and 2L+ powers the loads; both are nominally 24 V DC. When selecting industrial power supplies, consider steady consumption, inrush and cable losses. Check cable and connector capacity separately where power continues to additional modules.

M12 load connections and switching limits

Each socket carries one output on pin 4. Match M12 field cables and connectors to the wiring diagram. Fit suitable caps to unused sockets and inspect seals and threads during maintenance.

Electronic short-circuit protection is provided; outputs must not be paralleled to increase current capacity. Maximum switching frequency is 100 Hz for resistive loads, 0.5 Hz for DC-13 inductive loads and 1 Hz for lamps. Maximum lamp load is 10 W. When selecting contactors and coil loads, assess switching frequency and inrush as well as rated current.

Five checks before selection

1. Exact code: Confirm 6ES7142-3BF00-0XA0 on the label. A similar socket layout does not establish interchangeability with another ET 200 model.

2. Connection block: Match M12–7/8″ or ECOFAST to the installation. Check whether the block, caps and connection accessories are included.

3. Project and address: In the SIMATIC S7 hardware configuration, verify the device entry, PROFIBUS address and output mapping. Back up the project before replacement.

4. Simultaneous loads: Calculate odd-numbered and even-numbered socket groups separately. Compare load activation with the machine's actual operating cycle.

5. Functional test: Compare output commands with actual load movement. Where available, include position or running feedback from ET 200 digital input modules in the test record.

Editor's Note

Testing outputs individually may miss a fault that appears only when several loads operate together. List each socket and its load current, then record the operating sequence that triggers the fault. This helps distinguish a group-current overload from a single-channel problem.

PDF manuals and wiring diagrams: Visit the Siemens ET 200 manuals and PDF documents page. English manual A5E00158716-AD covers this model in section 8.6, pages 79–82. Connection blocks are covered in sections 8.2 and 8.3.