6ES7 131-4BB01-0AB0

Siemens 6ES7 131-4BB01-0AB0 – ET 200S 2DI DC 24V HF Digital Input Module

Siemens 6ES7 131-4BB01-0AB0 is a two-channel, 24 V DC High Feature digital input module for SIMATIC ET 200S. It brings signals from sensors, pushbuttons and position switches into the control system. Its two-input layout can suit machine sections where only a small number of additional signals are required. Explore the Siemens ET 200 family and our ET 200 digital input modules for related products.

The HF version combines configurable input filtering with sensor-supply short-circuit diagnostics. Typical applications include two photoelectric sensors monitoring different points on a conveyor, or switches reporting the two end positions of a mechanism. Selection should consider how long each signal remains active as well as the number of channels required.

Input Signals and Sensor Compatibility

The inputs follow IEC 61131 Type 1 characteristics. The specified ranges are +11 to +30 V for logic “1” and −30 to +5 V for logic “0”, with a typical active-input current of 8 mA. Two-wire proximity sensors are supported with a maximum quiescent current of 1.5 mA. Check this value when replacing an existing sensor, particularly where the replacement uses a different output circuit.

For a signal obtained through a relay contact, the field circuit must establish the voltage expected by the input. During commissioning, compare the sensor output, the module indicator and the corresponding PLC address. This helps distinguish a wiring problem from an incorrect address assignment.

Input Filtering and Event Handling

Input delay settings are 0.1, 0.5, 3 and 15 ms. The default is 3 ms. This setting applies to both channels and to both signal transition directions. Consider the timing requirements of the two connected devices together: a brief detection pulse and a mechanical switch affected by contact bounce may need different filtering strategies.

Rising-edge hardware interrupts can be enabled by channel in supported configurations. Isochronous operation is also supported, subject to the interface, controller and project configuration. Check the relevant ET 200 PROFIBUS and PROFINET interface documentation before relying on these functions. A 0.1 ms filter setting does not establish the response time of the complete system. For continuous high-speed pulse counting, assess suitable ET 200 function modules as well.

Power Supply and Sensor-Circuit Protection

The nominal 24 V DC supply comes through the appropriate ET 200 power module. The electronically protected sensor supply has a 500 mA limit shared by the complete module. This rating concerns power supplied to the sensors; it is not a digital output rating for switching an actuator.

Assess both sensors’ consumption alongside the capacity of the power supply, other devices in the potential group and the selected fuses. Measuring voltage while the sensors are operating is more informative than checking an unloaded supply alone.

Terminal Modules, Dimensions and Addressing

The electronics require a compatible TM-E terminal module. Siemens lists TM-E15S24-A1 and TM-E15C24-A1 among the supported options. Review our ET 200 terminal blocks when comparing connection methods and auxiliary terminal requirements. For a replacement, compare the terminal assignment and hardware configuration as well as the physical width.

Dimensions are 15 × 81 × 52 mm, approximate weight is 35 g and typical power loss is 0.4 W. Input addressing occupies one byte without packing or two bits with a supported packed configuration. The inputs are electrically isolated from the backplane bus, but the two channels are not isolated from each other. Include sensor connectors and grounding connections in the installation check.

Status Indication and Diagnostics

Green LEDs indicate individual input states, while the red SF LED indicates a group fault. Sensor-supply short-circuit-to-M diagnostics can be enabled through parameter settings. Although this diagnostic is reported through channel 0, it applies to the entire module. Troubleshooting should therefore cover the common sensor supply and both field circuits. A clear alarm description on the HMI or SCADA screen can help maintenance staff interpret the message correctly.

Order Code and Scope of Supply

Use the complete order number, 6ES7131-4BB01-0AB0, when matching a replacement. Siemens specifies five modules per manufacturer packaging unit; each individual module has two inputs. The quotation should separately identify whether the offer covers one module or a complete pack and whether a terminal base is included.

Editor's Recommendation

Consider the two connected devices as a pair when choosing this module. A photoelectric sensor producing brief pulses and a vibrating mechanical switch will share one input-delay setting. Observe the actual signals before selecting the filter. If both inputs unexpectedly become inactive, measure their common sensor supply as part of the investigation. For replacement enquiries, photographs of the module label and terminal base, together with the hardware configuration, provide a useful basis for checking the match.

Technical Documentation

Visit our Siemens ET 200 manuals page for documentation. The relevant module manual is 2DI DC24V HF – 6ES7131-4BB01-0AB0. Read it alongside the manual for the interface installed in the station.

Related Topics

About Siemens ET 200 · ET 200 digital output modules · ET 200 connection modules

Siemens > SIMATIC S7 > ET 200