6ES7 138-4FR00-0AA0

Siemens 6ES7 138-4FR00-0AA0 – ET 200S 1F-RO Fail-Safe Relay Module

Siemens 6ES7 138-4FR00-0AA0 is the 1F-RO fail-safe relay output module for ET 200S within the SIMATIC ET 200 family. It provides one relay output with two normally open contact paths. The manufacturer specifies a load voltage of 24 V DC or 24–230 V AC and an output current of 5 A.

When selecting this product from the ET 200 safety module range, consider the control and feedback arrangements alongside the electrical load. Review the module reference, terminal base, controlling F-DO and power module together.

How do the two contact paths operate?

OUT1 and OUT2 share a common control signal. They should therefore not be treated as two independently programmable standard outputs.

A relay contact switches the load circuit, while the control circuit determines when switching takes place. When evaluating a contactor coil, another control circuit or a suitable load-group supply, trace these two sides separately.

For example, if a contactor fails to release, inspecting the relay module alone is insufficient. Review the external supply, contact wiring, coil suppression and feedback circuit on the same drawing.

F-DO control and feedback monitoring

The stated maximum capability of SIL3 / Category 4 / PL e depends on control through a suitable fail-safe output and compliance with the system requirements. Siemens lists 6ES7138-4FB02-0AB0 as an example F-DO in the product description.

When selecting a digital output module, distinguish standard output operation from the required F-DO function. Review the PROFIsafe architecture, safety program and physical output connections together.

The relay feedback must be compared with the commanded state in the safety program. A mismatch can indicate a fault such as a welded contact. Siemens application documentation uses feedback-circuit monitoring for this purpose.

An output command visible in the PLC does not by itself prove that the load circuit has reached the intended state. Commissioning should verify the command, feedback and actual machine response together.

Power module selection affects the safety level

Siemens product information A5E36397089-AA, 07/2015 specifies a limit of SIL2 / Category 3 / PL d when this F-RO is supplied using PM-E DC24V versions up to 6ES7138-4CA01-0AA0.

The module’s maximum safety capability must therefore not be assigned automatically to every ET 200S installation. Check the exact power module reference and potential-group arrangement. This remains relevant when replacing just one component in an existing automation system.

Terminal bases and dimensions

The supported terminal bases are TM-E30S44-01, TM-E30C44-01, TM-E30S46-A1 and TM-E30C46-A1. Module dimensions are 30 × 81 × 52 mm, given as width, height and depth.

Selecting a terminal block requires more than matching its 30 mm width. Compare the terminal style, auxiliary connections and existing wiring. The same approach applies when reviewing other connection modules: use the complete type reference.

The 5 A rating and aggregate load

The 5 A continuous thermal contact rating does not permit an unrestricted combined current through both contact paths. For horizontal installation, the aggregate limit is 8 A up to 40 °C and 6 A up to 50 °C. For vertical installation, it is 6 A up to 40 °C. Further derating conditions apply at higher temperatures.

Consider cabinet temperature, mounting orientation and load inrush current together. Inductive loads also require attention to switching frequency and coil suppression. An adequate power supply does not establish that the relay contacts can switch every load under the same conditions.

Contact protection and wiring conditions

The manual specifies an external 6 A gL/gG fuse for contact protection. Additional conditions for special applications must also be checked. Select the fuse using the protection requirements as well as the normal operating current.

At 50% or more of the channel’s rated current, the manual requires parallel use of the duplicated terminals belonging to the same contact path. Follow the applicable terminal diagram.

If one contact path carries SELV/PELV, the other must also carry SELV/PELV. Review protective conductors, grounding and load supplies against the cabinet design.

Maintenance and replacement assessment

Alongside the complete 6ES7 138-4FR00-0AA0 reference, provide the terminal base, controlling F-DO and power module details. Instead of describing a fault only as “no output,” record the command, feedback and connected load behaviour separately.

Siemens lists this product as a spare part. When replacing it in an existing station, verify the safety function and feedback monitoring as well as the physical fit. A relay clicking during a bench check is insufficient evidence of suitability when its contact history and operating conditions are unknown.

Editor’s note: Selecting this module requires more information than “5 A safety relay.” Review the F-DO, power module, terminal base and feedback program as one arrangement. Overlooking the exact power module reference can lead to an incorrect conclusion about the achievable safety level.

Technical manuals and PDF documentation

The main references are ET 200S Fail-Safe Modules, A5E00103686-08, section 7.8, and product information A5E36397089-AA, which updates power-module assignments. Visit our Siemens ET 200 manuals and PDF documentation page to explore the documents.