6ES5 095-8MA05
Siemens SIMATIC S5-95U 6ES5 095-8MA05 Compact PLC
The 6ES5 095-8MA05 is the 24 V DC basic S5-95U in the Siemens SIMATIC S5 family. This compact PLC combines the processor with 16 digital inputs, 16 digital outputs, 8 analog inputs and 1 analog output. It handles sequencing, measurement and pulse counting in existing machines.
Power supply and digital connections
The CPU uses a nominal 24 V DC supply with an allowable range of 20–30 V DC. Siemens lists the PS 931 6ES5 931-8MD11 as an external supply option with a 24 V DC / 2 A output. If the same supply feeds the output loads, size it for the combined current.
The onboard digital inputs use I32.0–I33.7. The onboard transistor outputs use Q32.0–Q33.7 and are rated 0.5 A per channel. Siemens lists the 40-pin 6ES5 490-8MB11 screw-terminal front connector as a wiring option. Figure 3-22 shows the load supply terminals for both groups of eight outputs.
Analog signals, interrupts and high-speed counters
The 15-pin Sub-D port provides eight 0–10 V analog inputs at IW40, IW42, IW44, IW46, IW48, IW50, IW52 and IW54. These inputs accept compatible 0–10 V sensors. The single analog output at QW40 provides 0–10 V or 0–20 mA, depending on the terminal used. Check the difference between voltage and current signals and verify the receiving device’s scaling. Compatible S5 analog modules can add channels.
A separate 9-pin Sub-D port provides four interrupt inputs and two high-speed counter inputs. With no communications load, Siemens specifies limits of 5 kHz for counter A and 2 kHz for counter B. Enable the counters in DB1. For faster pulse measurement, compare the frequency ratings of compatible S5 counter and positioning modules.
STEP 5, memory and expansion
The basic unit has one 20 mA TTY programmer interface. Use a compatible PG cable or TTY adapter for STEP 5 programming and backup. The controller has 16 KB of internal program and data memory. A compatible 375-series EPROM or EEPROM submodule can store the program.
The side bus connection supports up to 32 compatible S5-100U modules. Examples include the 6ES5 421-8MA12 digital input module and the 6ES5 441-8MA11 digital output module. Record the existing module order and addresses with the backup.
When selecting a spare, compare the full order number and hardware label with nearby basic variants such as the 6ES5 095-8MA04. The 6ES5 095-8MB03 has a SINEC L2 interface. The 6ES5 095-8ME03 has a PROFIBUS-DP master interface.
Editor’s Note
On a used 8MA05, bench-test the Q32 and Q33 output groups separately under load. If the entire Q33.0–Q33.7 group is inactive, check for 24 V DC between a11 (L+) and a20 (M) on the output row of the 40-pin front connector. Back up the STEP 5 program and DB1 settings before resetting a unit removed from a machine.
To sell a used 6ES5 095-8MA05, send the quantity, working condition or fault details, a label photo and your asking price to otomasyonavm@gmail.com.
Related topics
S5-95U 8MA01 | S5-95U 8MA02 | S5-95U 8MA03
Navigation
Shared SIMATIC S5 PDF archive | S5 CPU 90U–115U | Used SIMATIC S5 | Siemens second-hand main page | Second-hand automation
References
Siemens 6ES5095-8MA05 data sheet (PDF, EN) · Exact order number, p. 1.
Siemens ST 50, 1998 catalog (PDF, RU) · Technical data on pp. 2-27–2-30, exact order number and accessories on p. 2-31.
Siemens S5-90U/S5-95U System Manual (PDF, EN) · 6ES5 998-8MA22, Edition 03. Basic S5-95U coverage starts at 8MA04, Edition 01. Wiring on pp. 3-22–3-24, counter settings and frequency limits on pp. 11-3 and 11-9.