Siemens V20 fault codes 3
Alarm Codes and Solutions:
A501 - Current Limit:
- Cause: Motor power does not match inverter power, motor cables are too long, ground faults.
+ Solution: Refer to F1. Very small motors (120 W) can generate high current under FCC and under light load. Use V/f operation for very small motors.
A502 - Overvoltage Limit:
- Cause: Overvoltage limit reached. This warning can occur during deceleration when the Vdc controller is disabled (P1240 = 0).
+ Solution: If this warning is displayed continuously, check the input voltage of the inverter.
A503 - Undervoltage Limit:
- Cause: Main supply failed, main supply and thus DC link voltage (r0026) below specified limit.
+ Solution: Check the main supply voltage.
A504 - Inverter Overheating:
- Cause: Inverter heat sink temperature warning level, chip junction temperature warning level, or temperature change at the chip junction exceeded the allowed limits, as a result, pulse frequency will decrease and/or output frequency will decrease (depending on parameterization in P0290).
+ Solution: Ensure ambient temperature is within specified limits, ensure load conditions and load steps are appropriate, ensure the fan is spinning while the inverter is operating.
A505 - Inverter I2t:
- Cause: Warning level exceeded, current will be reduced if parameterized (P0610 = 1).
+ Solution: Ensure the load cycle is within specified limits.
A506 - IGBT Junction Temperature Rise Warning:
- Cause: Overload warning. The difference between the heat sink and IGBT junction temperature exceeds warning limits.
+ Solution: Ensure load steps and shock loads are within specified limits.
A507 - Inverter Temperature Signal Loss:
- Cause: Inverter heat sink temperature signal loss. The sensor may have fallen off.
+ Solution: Contact the service department or replace the inverter.
A511 - Motor Overheating I2t:
- Cause: Motor overloaded, load cycles or load steps too high.
+ Solution: Regardless of the temperature determination type, check P0604 motor temperature warning threshold, P0625 motor ambient temperature, check if plate data is correct, if not, perform quick commissioning, find correct equivalent circuit data by performing motor identification (P1900 = 2), check if motor weight (P0344) is reasonable, if necessary, replace, P0626, P0627, and P0628 can replace standard overheating if the motor is not a SIEMENS standard motor.
A535 - Brake Resistor Overload:
- Cause: Braking energy too large, brake resistor not suitable for application.
+ Solution: Reduce braking energy, use a higher rated brake resistor.
A541 - Motor Data Identification Active:
- Cause: Motor data identification (P1900) selected or running.
A600 - RTOS Overrun Warning:
- Cause: Internal time slice timeout
+ Solution: Contact the service department.
A910 - Vdc_max Controller Disabled:
- Cause: Occurs when the main supply voltage (P0210) is continuously too high, if the motor is driven by an active load, if the motor enters regenerative mode, if deceleration occurs when the load inertia is too high.
+ Solution: Ensure input voltage is within range, ensure load is appropriate, apply a brake resistor in certain cases.
A911 - Vdc_max Controller Active:
- Cause: The Vdc_max controller operates to keep the DC link voltage (r0026) below the level specified in r1242.
+ Solution: Ensure input voltage is within limits specified on the plate, ensure deceleration time (P1121) matches load inertia.
A912 - Vdc_min Controller Active:
- Cause: The Vdc_min controller is activated if the DC link voltage (r0026) falls below the level specified in r1246. The kinetic energy of the motor is used to buffer the DC link voltage, which results in deceleration of the inverter! Thus, short main interruptions do not necessarily lead to an undervoltage fault.
Note: This warning can also occur during rapid ramp-up increases.
A921 - Analog Output Parameters Incorrectly Set:
- Cause: Analog output parameters (P0777 and P0779) should not be set to the same values, as this produces nonsensical results.
+ Solution: Set P0777 and P0779 to different values.
A922 - No Load Applied to Inverter:
- Cause: No load applied to the inverter. As a result, some functions may not operate under normal load conditions.
+ Solution: Ensure the motor is connected to the inverter.
A923 - Both JOG Left and JOG Right Requested:
- Cause: Both JOG right and JOG left (P1055 / P1056) requested. This freezes the RFG output frequency at its current value.
+ Solution: Do not press JOG right and left simultaneously.
A930 - Cavitation Protection Warning:
- Cause: Conditions for potential cavitation damage are present.
+ Solution: Refer to F410.
A936 - PID Auto Tuning Active:
- Cause: PID auto tuning (P2350) selected or running.
+ Solution: Warning disappears when PID auto tuning is completed.
A952 - Load Monitoring Warning:
- Cause: The load conditions of the motor indicate belt failure or mechanical failure.
+ Solution: Refer to F452.