Siemens V20 fault codes 2

Siemens V20 Error Codes and Solutions:

F52 - Inverter Software Failure:

- Cause: Reading failure or invalid data for inverter information.
- Solution: Power cycle the inverter, contact the service department, or replace the inverter.

- F60 - Asic Timeout:

- Cause: Internal communication failure.
- Solution: Check the inverter, communication failure may be due to EMC issues, check and improve EMC if necessary, use an EMC filter.

- F61 - MMC/SD Card Parameter Cloning Failed:

- Cause: Parameter cloning failed.
- Solution: Use an MMC/SD card formatted in FAT16 or FAT32 or insert an MMC/SD card into the inverter, check the MMC/SD card (e.g., is the card memory full?) - reformat the card in FAT16 or FAT32, place the correctly named file in the correct directory: /USER/SINAMICS/DATA, ensure the file is accessible - if possible, recreate the file, if the file has been modified - recreate the file.

- F62 - Parameter Cloning Content Invalid:

- Cause: File exists but content is not valid control word corruption.
- Solution: Recopy and ensure the process is complete.

- F63 - Parameter Cloning Content Incompatible:

- Cause: File exists but not the correct inverter type.
- Solution: Clone from a compatible inverter type.

- F64 - Inverter Attempted Auto Cloning at Startup:

- Cause: No Clone00.bin file in the correct directory: /USER/SINAMICS/DATA.
- Solution: If auto cloning is required, insert an MMC/SD card containing the correct file and power cycle. If auto cloning is not required, remove the card if not needed and power cycle. Reset P8458 to 0 and power cycle. The error can only be cleared with a power cycle.

- F71 - USS Setpoint Fault:

- Cause: Setpoint values from USS are missing during the telegram off time.
- Solution: Check the USS host.

- F72 - USS/MODBUS Setpoint Fault:

- Cause: Setpoint values from USS/MODBUS are missing during the telegram off time.
- Solution: Check the USS/MODBUS host.

- F80 - Signal Loss at Analog Input:

- Cause: Broken wire, signal outside limits.

- F85 - External Fault:

- Cause: External fault triggered via command input through control word 2, bit 13.
- Solution: Check P2106, disable control word 2 bit 13 as command source, disable terminal input for fault triggering.

- F100 - Watchdog Reset:


- Cause: Software Error
- Solution: Contact the service department or replace the inverter.

- F101 - Stack Overflow:

- Cause: Software error or processor failure.
- Solution: Contact the service department or replace the inverter.

- F221 - PID Feedback Below Minimum Value:

- Cause: PID feedback below minimum value P2268.
- Solution: Change P2268 value, adjust feedback gain.

- F222 - PID Feedback Above Maximum Value:

- Cause: PID feedback above maximum value P2267.
- Solution: Change P2267 value, adjust feedback gain.

- F350 - Configuration Vector for Inverter Failed:

- Cause: At startup, the inverter checks if the configuration vector (SZL vector) is correctly programmed and if the hardware matches the programmed vector. If not, the inverter faults.
- Solution: Ensure the correct power module is installed. Internal faults cannot be corrected. r0949 = 13 - Ensure the correct power module is installed. r0949 > 1000: Incorrect I/O card installed.

- F395 - Acceptance Test/Confirmation Pending:

- Cause: This error occurs after a startup clone. It can also be due to a faulty read from the EEPROM, see more details for F51.
- Solution: The current parameter set should be checked and confirmed with the clearing of the error.

- F410 - Cavitation Protection Fault:

- Cause: Conditions for cavitation damage are present. Cavitation damage is damage to a pump in pumping systems where the liquid is not flowing adequately. This can lead to heating and subsequent damage to the pump.
- Solution: If cavitation is not occurring, reduce the cavitation threshold or increase the cavitation protection delay. Ensure sensor feedback is working.

- F452 - Load Monitoring Fault:

- Cause: The load conditions of the motor indicate belt failure or mechanical failure.
- Solution: Ensure there is no breakage, jamming, or clogging in the inverter train, apply lubrication if necessary, if an external speed sensor is used, check the following parameters for correct function: P2192 (delay time for allowed deviation), P2182 (threshold frequency f1), P2183 (threshold frequency f2), P2184 (threshold frequency f3), if a specific torque/speed range is used, check the parameters: P2182 (threshold frequency 1), P2183 (threshold frequency 2), P2184 (threshold frequency 3), P2185 (upper torque threshold 1), P2186 (lower torque threshold 1), P2187 (upper torque threshold 2), P2188 (lower torque threshold 2), P2189 (upper torque threshold 3), P2190 (lower torque threshold 3), P2192 (delay time for allowed deviation).

 + V20 User Manuals
+ V20 Error Index
+ V20 Error Codes 1
+ V20 Error Codes 2
+ V20 Error Codes 3

++ Siemens Homepage 

"All the guides and error codes on this page have been created by members of our community. The information has been prepared as faithfully as possible to the original; however, the error codes and technical specifications of devices can be subject to interpretation. Official manufacturer guides should be considered the primary source. Do not hesitate to contact our community if you notice any inaccuracies or if you wish to contribute."