Siemens V20 Error Codes and Solutions:
F1 - Overcurrent:
- Cause: Motor power does not match inverter power, motor cable short circuit, ground faults.
+ Solution: Ensure motor power matches inverter power, do not exceed cable length limits, ensure there are no short circuits or ground faults in the motor cable and motor, ensure motor parameters match the used motor, ensure the stator resistance value is correct, ensure the motor is not blocked or overloaded, increase acceleration time, reduce start boost level.
F2 - Overvoltage:
- Cause: Main supply voltage is too high, motor in regenerative mode.
+ Solution: Ensure supply voltage is within limits specified on the plate, ensure deceleration time is compatible with load inertia, ensure required braking power is within specified limits, ensure Vdc controller is enabled and properly parameterized.
F3 - Undervoltage:
- Cause: Main supply failed, shock load outside specified limits.
+ Solution: Check supply voltage.
F4 - Inverter Overheating:
- Cause: Inverter overloaded, insufficient ventilation, pulse frequency too high, ambient temperature too high, fan not working.
+ Solution: Check if load or load cycle is too high, ensure motor power matches inverter power, ensure pulse frequency is set to default value, check if ambient temperature is too high, ensure the fan is spinning while the inverter is operating.
F5 - Inverter I2t:
- Cause: Inverter overloaded, load cycle too demanding, motor power exceeds inverter power capacity.
+ Solution: Ensure the load cycle is within specified limits, ensure motor power matches inverter power. F5 error, inverter overuse (r0036) cannot be cleared until inverter I2t warning (P0294) is lower.
F6 - Chip Temperature Rise Exceeds Critical Levels:
- Cause: Startup load is too high, load step is too high, acceleration rate is too fast.
+ Solution: Check if the load or load step is too high, increase acceleration time, ensure motor power matches inverter power, use P0290 setting 0 or 2 to prevent F6.
F11 - Motor Overheating:
- Cause: Motor overloaded.
+ Solution: Check if the load or load step is too high, ensure motor nominal overheating temperatures (P0626 - P0628) are correct, ensure motor temperature warning level (P0604) is appropriate, small motors (≤ 250 W, 4 or 2 poles) operated at a frequency below 15 Hz may trigger this error, even if the motor temperature is within limits. Ensure the motor current does not exceed the motor nominal current specified on the motor plate and the physical temperature of the motor is within limits. If these two conditions are met, set parameter P0335 to 1.
F12 - Inverter Temperature Signal Lost:
- Cause: Wire break of inverter temperature (heat sink) sensor.
F20 - DC Ripple Too High:
- Cause: Calculated DC ripple level exceeded the safety threshold. This commonly occurs due to the loss of one of the main input phases.
+ Solution: Check the main supply wiring.
F35 - Maximum Number of Automatic Restart Attempts Exceeded:
- Cause: Automatic restart attempts exceeded the P1211 value.
F41 - Motor Data Identification Failure:
- Cause: Motor data identification failed.
+ Solution: Ensure the motor is connected to the inverter for r0949 = 0, ensure motor data is correct in P0304 - P0311 for r0949 = 1 - 49, check which type of motor wiring is required (star, delta).
F51 - Parameter EEPROM Fault:
- Cause: Read or write failure when accessing EEPROM. This can also be due to the EEPROM being full, too many parameters have been changed.
+ Solution: A power cycle should be done to cancel this error, some parameters may not be read correctly, a factory reset and new parameterization should be done, if the power cycle does not remove the error, if the EEPROM is full, change some parameters back to their default values, then do a power cycle, replace the inverter.