6ES5 982-3UA11
Siemens 6ES5 982-3UA11 OP 393 Panel Mounting Frame
The Siemens 6ES5 982-3UA11 is a mounting frame for installing an OP 393 operator panel in a control panel. Siemens lists 6ES5 982-3UA11 alongside the 6ES5 393-0UA15 OP 393-III in the manual's ordering information. For SIMATIC S5 applications, the specified cutout for installation with the frame is 214 mm high × 135 mm wide.
When installing an HMI or operator panel, assess the cutout, panel thickness and rear connection space together. A mechanical accessory for a Siemens operator panel must match the actual panel model. In a PLC and HMI application, choose a position that provides a clear view of the display and convenient access to the keys.
Panel cutout and mechanical dimensions
Figure 2.2 in the Siemens OP 393 manual specifies a 214 × 135 mm panel cutout for mounting with the frame; the first dimension is height and the second is width. The drawing shows external frame dimensions of 229 mm high × 148 mm wide. Do not use the external dimensions as the cutout dimensions.
The maximum control-panel thickness is 5 mm, and the manual states an installation depth of 45 mm. Allow additional rear clearance for cables and connectors. When adapting an existing opening, check both the cutout and seating surface against the actual part.
The same manual page illustrates installation without a frame separately. Do not mix the cutout and screw information for that arrangement with the dimensions for framed installation. The OP 393 housing dimensions and the 982-3UA11 frame's external dimensions are also separate specifications.
Understanding the IP54 specification
Siemens specifies IP50 for the OP 393 and IP54 with the mounting frame. This IP54 protection specification applies to the panel arrangement installed with the frame. When assessing the IP protection rating, check the panel housing, seating surface and sealing components together.
An old, distorted or incomplete frame cannot be assumed to meet the protection requirements solely from its order number. Inspect uneven mounting surfaces, cracks, damaged fixing points and gaps that could compromise sealing.
OP 393 family and other accessory codes
6ES5 393-0UA11, 6ES5 393-0UA12 and 6ES5 393-0UA13 are other panel records in the OP 393 family. Plan installation after checking the existing panel's complete code, housing and connection arrangement. Mechanical frame compatibility does not establish the panel's electrical or software compatibility with a CPU.
6ES5 982-3UB11 is a separate accessory code. Other operator panels, including OP 395 and OP 396, require assessment against their own housing and installation documentation. Similar order numbers or appearance do not guarantee an identical cutout or direct replacement.
Connections and maintenance planning
982-3UA11 is a mechanical mounting accessory. Power and communication connections follow the OP 393 panel's own connection requirements. Check S5 cables and connectors, interface connections and the S5 PLC requirements separately from frame selection. Support cables so that their weight does not load the panel connector or frame.
If the work also involves replacing the operator panel, record the existing project and parameters. Include CPU memory cards and program backups in the service plan, retaining recoverable copies to reduce the risk of data loss.
Editor's Note
Start by checking that the frame is straight. Cracked corners, broken fixing points or distortion can spoil the installation even if the panel appears to fit. Ask for photographs of both the front and rear.
Have the cutout measured carefully. Framed installation requires an opening 214 mm high and 135 mm wide; 229 × 148 mm describes the external dimensions. Compare the drawing with the actual part before cutting, and measure any existing opening.
An IP54 reference does not complete the inspection. Check that sealing components are present, the seating surface is flat and no gaps remain. The order number alone cannot describe the condition of an ageing or incomplete assembly.
After mounting, the panel should remain stable when its keys are pressed, without distorting the frame. Leave enough space for the rear connector and cable bend. A taut cable can gradually damage an otherwise sound connection.
When purchasing Siemens spare parts, clarify which fixing and sealing components are included. A frame being available does not establish that the complete mounting set is present. Compare the actual panel code and existing installation photographs as well.
OtomasyonAVM resources and PDF documentation
Use About Siemens S5 PLC for system information and the Siemens S5 PDF archive for documentation. For this part, refer to the ordering table on page 2-1 and mounting drawing on page 2-3 of OP 393 Handbuch, 6ES5 998-0UQ12 / EWA 4NEB 810 1180-01g.
Related topics
OP 393-III operator panel · 6ES5 393-0UA13 · 6ES5 982-3UB11 · IP54 protection · S5 cables and connectors
Navigation: 6ES5 982-3UA11 model page | Siemens HMI models | SIMATIC S5 main page | Siemens S5 PLC models | Used Siemens products
Siemens documents and external references
Siemens OP 393 Handbuch — German PDF: PDF page 15 / printed page 2-1 for the exact order code and protection information; PDF page 17 / printed page 2-3 for framed installation dimensions.