6ES5 946-3UR21
Siemens 6ES5 946-3UR21 – SIMATIC S5-155H CPU 946R
Siemens 6ES5 946-3UR21 is a CPU 946R processor module for the redundant SIMATIC S5-155H automation system. Siemens documentation associates this exact order number with the S5-155H. When sourcing parts for Siemens S5 and SIMATIC S5 systems, check the hardware version as well as the complete 3UR21 suffix.
CPU 946R forms part of the CPU 946R/947R processor arrangement and should be assessed together with the accompanying 6ES5 947-3UR21 CPU 947R. Do not assume the same application for standard S5-155U versions such as 6ES5 946-3UA11 and 6ES5 946-3UA21.
Redundant System and Rack Layout
In the manufacturer’s classic CPU 946R/947R arrangement, two central controllers are linked through an IM 304 interface module and an IM 324R interface module. One central controller acts as master and the other as standby. Assess the processor alongside the inter-controller connection and system configuration.
The Siemens central-controller table shows CPU 946R occupying two slots, 11 and 19, with CPU 947R in position 27. Check the existing S5 rack and chassis and S5 power supply against the equipment’s hardware documentation. This layout information applies to the classic 946R/947R arrangement.
Communication and Version Requirements
The CP 1430 TF compatibility table lists 6ES5 946-3UR21 version 3, CPU 947R 6ES5 947-3UR21 version 6 and PG software V6.3. Record the processor label’s version information when assessing existing S5 communication modules.
The access path is PG → SINEC H1 → CP 1430 TF → PLC backplane bus → CPU. This function requires a CP base SSNR of 232, 236 or 244. Check S5 interface modules and S5 cables and connectors against the installed network documentation; the CPU order number alone does not establish a built-in Ethernet port.
Program, Memory and Maintenance Checks
Before replacing the processor, record the user program, system settings and installed S5 memory modules. During PLC programming and debugging, secure backups first and then compare diagnostic information from both central controllers.
CPU 948R references such as 6ES5 948-3UR13 and 6ES5 948-3UR21 require separate assessment when planning an upgrade. Siemens specifies DX1 conversion using COM 155H V3.0 when moving from 946R/947R to 948R and identifies a changed error DB structure. Plan the program and configuration conversion before changing the hardware.
See the Siemens S5 PLC overview for system background and the S5 function modules section for further specialist modules. Recording the complete order number, version, rack position and accompanying processor helps future maintenance work.
Editor’s Note
Read the complete 3UR21 suffix and hardware version before choosing a replacement. Record the label of the accompanying 947R as well.
One central controller reaching RUN does not verify the complete redundant system. Check both controllers and standby readiness; carry out any changeover test under the plant’s maintenance plan.
Back up the program and configuration before removing the processor. Losing system data such as DX1 can make recovery difficult even when a suitable spare is available.
Inspect rear connectors for corrosion, bent contacts and previous repair work. A rack supply or cooling problem can remain after the processor has been replaced.
If communication fails, check the CP version, SSNR configuration, connection path and programmer software in sequence. Change one item at a time so that the original fault remains traceable.
Documentation and PDF Archive
Browse other S5 documents in our S5-115 PDF archive. Use the manufacturer references below for the classic CPU 946R/947R layout, exact communication requirements and migration to CPU 948R.
Related Topics and Nearby Models
6ES5 947-3UR21 · 6ES5 946-3UA21 · 6ES5 948-3UR13 · 6ES5 948-3UR21. These links support comparison and system assessment; select replacements against the complete configuration.
Siemens S5 Navigation
Used Siemens products · Siemens S5 main page · SIMATIC S5 · Racks and chassis · Memory modules · Communication modules
External References
Siemens CP 1430 TF, C79000-G8976-C056, §4.2.4 — CPU 946R order number, version requirements and SSNR; printed 4-21 / PDF 119.
Siemens S5-155U/155H central controller, C79000-B8576-C380-05, §1.2.2 — classic 946R/947R arrangement; printed 1-6 / PDF 72.
Siemens S5-155H Manual, C79000-B8576-C197-06 — DX1 conversion and error DB differences when moving from 946R/947R to 948R; I/1-17 / PDF 37.