6ES5 945-7UA13
Siemens 6ES5 945-7UA13 CPU 945 — S5-115U, 256 KB RAM
Siemens 6ES5 945-7UA13 is the CPU 945 central processing unit with 256 KB of internal RAM for the S5-115U. It executes the STEP 5 program in a SIMATIC S5 system; the CPU 945 family provides 256 timers and 256 counters. This S5 CPU manages program execution, data and access to the installed peripherals.
7UA13 is the 256 KB version; 6ES5 945-7UA23 is the separate 384 KB RAM variant. Keep external memory-card capacity distinct from internal CPU RAM. Record the hardware and operating-system versions alongside the complete order code when selecting a replacement.
Program memory and protection during power loss
The CPU 945 copies the program from a Flash EPROM card into internal RAM for execution. Assess MC 374 cards such as 374-1KG11 and 374-1KH21 by code, capacity and programming requirements. RAM retention during power loss depends on the backup arrangement at the PS 951 power supply. Preserve the card program and current RAM data as separate backup items.
SI1 programming connection and SI2 module slot
SI1 is a 15-pin, 20 mA TTY connection used for a PG, a suitable operator panel or SINEC L1. The second serial interface, SI2, is provided by an installed interface module. Select the programming cable against the electrical interface and wiring documentation, rather than the connector shape alone.
Siemens lists the 752-0LA12 20 mA module, 752-0LA52 PG module and 752-0LA62 SINEC L1 module as separate items. An SI2 slot does not establish that any of these modules is included with the CPU. A communication offer should identify the fitted module, cable and connection function tested.
Supply requirements, weight and rack checks
The CPU 945 manual specifies consumption, excluding the interface module, of typically 0.5 A from the internal 5 V rail and 0.06 A from 24 V. Typical module losses are 4.2 W and approximate weight is 0.8 kg. These are CPU figures, distinct from the power supply’s mains input rating. Assess total load against the actual rack configuration and additional equipment.
Execution time and I/O testing
ST 50 lists a 0.1 µs bit-operation execution time for the CPU 945. This is not the execution time of every instruction or a complete PLC scan. When checking digital inputs and digital outputs, compare program states with field signals and measure actual scan time with the installed program and hardware.
Record scaling, data format and addressing for analog modules, and the FB versions used by function modules. After CPU replacement, extend acceptance testing beyond the RUN indicator. Check program access, data blocks, communication and the relevant machine functions separately.
Hardware version and Siemens product information
Siemens product information EWA 4NEB 811 6706-10b covers specific MBA usage conditions for this order code and timing changes with Z05 firmware. In an older Siemens S5 system, the order code and firmware version are separate identification details. Review the applicable product note against the installed software, particularly where special OB 250 services are used.
Editor’s note
Ask for a photograph showing both the 945-7UA13 marking and the SI2 slot. A description such as “CPU with two communications ports” should make clear whether the second module is actually fitted.
Back up the installed program before the replacement arrives. Updated RAM values and an older Flash-card image may differ. Finding the card does not establish that every current machine value has been recovered.
If a battery warning is present, resolve the backup situation before removing power. Substituting modules can lose unprotected RAM contents. Plan the maintenance step against both the power-supply and memory instructions.
SI1 needs the correct 20 mA TTY connection, not an ordinary serial cable chosen by appearance. Use a suitable converter and a known working cable before attributing a failed PG connection to the CPU.
A used-unit test record should identify the CPU, firmware, fitted interface and memory card. Add whether the program was readable, which communication functions were checked and the operating conditions. A RUN indication alone leaves too much of the test scope uncertain.
OtomasyonAVM resources and PDFs
+ 6ES5 945-7UA13 product and information page, S5 CPU series pages and Siemens S5 models.
+ OtomasyonAVM SIMATIC S5 PDF archive. Use the CPU 945 manual 6ES5 998-3UF21 alongside the exact-code data sheet and firmware-related product information.
Related topics
+ MC 374-1KH21 memory card, 752-0LA52 PG interface, 752-0LA62 SINEC L1 module and CPU 945-7UA23 comparison.
Browse SIMATIC S5
S5 CPU | SIMATIC S5 | S5 interfaces | Siemens second-hand homepage
Siemens and external references
+ Siemens 6ES5945-7UA13 data sheet, 28 April 2018, English — third-party archive copy: exact code, CPU 945, S5-115U and 256 KB identification.
+ Siemens S5-115U CPU 945 Manual, 6ES5 998-3UF21, Edition 06, English: section 2.3.1 for memory; chapter 12 for serial interfaces; printed page 15-15 / PDF page 600 for consumption and weight.
+ Siemens ST 50, 1998, English catalogue — third-party archive copy: printed pages 3/24–3/25 / PDF pages 110–111, exact-code ordering data and CPU 945 technical comparison.
+ Siemens CPU 945 Product Information, EWA 4NEB 811 6706-10b, 1997: German, English and French; English section on PDF pages 3–4. Read hardware markings and firmware scope against the applicable page.