Siemens 6ES5 700-8MB21 – Interrupt-Capable Bus Unit with Crimp Connections
Siemens 6ES5 700-8MB21 is an interrupt-capable bus unit with crimp snap-in connections for the S5-100U local bus in the SIMATIC S5 family. It accommodates two I/O modules and provides 10 connection points per module position. Typical consumption from the CPU's internal +9 V rail is 11 mA. Interrupt operation depends on the correct CPU and installation position.
This component is the bus and field-wiring base for modules in a Siemens S5 PLC system, rather than a CPU, standalone input card or network communication processor. Two module positions do not mean two input channels. Channel count and signal type are determined by the fitted I/O modules.
CPU and position requirements for interrupts
Interrupt processing is supported by CPU 103 version 8MA02 and later. In systems using 6ES5 103-8MA02 or 6ES5 103-8MA03, the interrupt bus unit must be directly adjacent to the CPU, forming module positions 0 and 1. In later positions, the same unit operates as a normal bus unit; interrupt capability does not extend along the complete row.
Process interrupts require suitable four-channel digital input modules or the 461-8MA11 comparator module in these two positions. Other modules may be fitted but do not gain interrupt-generating capability. OB2 must be programmed, the PLC must be in RUN, and interrupt processing must not be disabled by the program. A rising or falling edge at a suitable input can initiate OB2 processing.
Crimp connections and bus supply
The connection system is crimp snap-in. The manual specifies 0.5–1.5 mm² stranded conductors. Use suitable contacts and a crimping tool when preparing S5 cables and connectors. Siemens accessories include 6XX3 070 contacts, the 6XX3 071 crimping tool and the 6ES5 497-8MA11 contact extraction tool.
The +9 V / 11 mA specification belongs to the bus electronics and must not be treated as a sensor or load-supply rating. Assess the S5 power supply, fitted I/O cards and field supplies together. Voltage and current ratings for digital output and analog modules come from their own technical specifications rather than the bus base.
Mounting, expansion and related order codes
The unit mounts on a 35 mm S5 DIN rail and connects to neighbouring bus units through ribbon connections. The manual specifies up to 16 bus units per controller; this does not mean 16 active interrupt bus units. Multi-row installations require checking interface modules and the IM 315 or IM 316 arrangement separately. The direct-adjacency requirement for interrupts remains applicable.
6ES5 700-8MB11 is the interrupt-capable version with screw terminals. 700-8MA21 and 700-8MA22 are normal bus units with crimp connections. 700-8MA11 is a normal screw-terminal unit, while 700-8FA11 provides screw terminals with increased EMC protection. Similar housings do not establish identical interrupt capability or terminal arrangements.
Editor's Note
When buying used Siemens equipment, ask for clear photographs showing the 8MB21 code and ALARM markings at both module positions. Check whether the contacts and terminal components are included. Missing crimp contacts can complicate installation.
If normal inputs can be read but interrupts do not operate, check the CPU version and bus-unit position first. An interrupt base moved away from the CPU may continue normal I/O operation; that does not prove that its interrupt path is working.
Inspect contacts for backing out of their housings, weak crimps and incorrect cavity positions. A loose or poorly crimped contact can cause intermittent field faults. Do not force the wiring into place.
If a ribbon connection is crushed, broken or corroded, inspect the downstream modules as well as this base. Record the module order and wire numbers before replacement to reduce addressing and wiring mistakes.
Test normal I/O communication at both positions and OB2 interrupt operation with a suitable input module separately. Confirm that OB2 exists and interrupts are enabled before declaring the bus unit faulty. Perform removal, insertion and wiring with power switched off.
OtomasyonAVM resources and PDFs
See About Siemens S5 PLC for the general architecture and our S5 PDF files section for available documents. Technical references are the S5-100U System Manual, 6ES5 998-0UB23 / EWA 4NEB 812 6120-02b, Chapter 10 and page 14-13, together with Siemens ST 50 / 1998, page 2/75. Both documents are in English.
Related topics
700-8MB11 screw-terminal interrupt bus unit · 700-8MA22 crimp bus unit · CPU 103 8MA03 · 461-8MA11 comparator. Their connection types, interrupt capabilities and system roles differ; they must not be treated as direct equivalents.
Browse SIMATIC S5: 6ES5 700-8MB21 main page · SIMATIC S5 · Siemens S5 PLC · Used Siemens models.