6ES5 440-8MA11
Siemens 6ES5 440-8MA11 — 4-Channel 24 V DC / 0.5 A Digital Output Module
The Siemens 6ES5 440-8MA11 is a non-isolated digital output module with four 24 V DC / 0.5 A outputs in the SIMATIC S5 family. Within the S5 digital output range, it switches suitable DC loads. Maximum permitted total current across all four outputs is 2 A.
The manufacturer lists this exact order number in its ET 100U and ET 200U module tables. Match load voltage, bus unit, address identifier and wiring diagram to the existing Siemens S5 PLC and distributed I/O arrangement.
24 V supply and common reference
The external load supply is nominally 24 V DC, with a permissible range of 20–30 V DC including ripple. Check the S5 power supply separately from the L+ load supply. The non-isolated design requires common reference connections to follow the manufacturer’s drawing.
Inspect S5 cables and connection accessories and terminal contacts on bases such as the 700-8MA11 bus unit. Check L+, M, supply returns and protective grounding. Isolate the relevant circuits before removing the module or bus unit.
Load current, lamps and inductive loads
Nominal channel current is 0.5 A, with a specified range of 5–500 mA. Maximum lamp load is 5 W, and maximum off-state residual current is 0.5 mA. Include minimum load and off-state behavior when assessing low-consumption relay and indicator loads.
Maximum switching frequency is 100 Hz for resistive loads and 2 Hz for inductive loads. If an external diode is fitted across a coil, check its polarity and effect on release time. The manufacturer specifies a 0.8 A maximum for parallel output operation; do not treat this as 0.5 + 0.5 = 1 A, and follow the manual’s connection conditions.
Short-circuit protection and the red F LED
The outputs are short-circuit protected and switch on again automatically once the short circuit is removed. The red F LED can indicate either a short circuit or missing L+ load voltage. When F is lit, measure the module’s supply terminals as well as checking the load.
Automatic recovery means that an output may resume conduction as the fault is cleared. Typical consumption from the CPU’s +9 V supply is 15 mA; no-load consumption from L+ is 25 mA. Typical module power dissipation is 3 W.
Program, station identifier and troubleshooting
During troubleshooting, follow the PLC program’s output command, L+–M supply and load terminals together. If all four channels are affected, inspect the shared supply, return path and bus-unit contacts too. Observe the 2 A total limit even when each individual load is suitable.
The ET 100U address designation is 4DQ. The ET 200U table gives 048 for DP-Siemens and 8DQ or 032 for DP Standard. Match the protocol and configuration used by station interfaces such as the IM 318-B 318-8MB11. An “8DQ” identifier does not mean that the physical module has eight outputs; this model has four channels.
Similar order numbers and output-type differences
The 440-8MA12 has a closely related revision code; check the complete number and application conditions before substitution. The 440-8MA21 and 440-8MA22 are four-channel 2 A types. Do not apply their higher current rating to the 440-8MA11.
The 441-8MA11 has eight non-isolated 24 V DC / 0.5 A outputs; the 450-8MB11 has four isolated 24–60 V DC / 0.5 A outputs. The 451-8MA11 has eight isolated 24 V DC / 1 A outputs. Match channel count, isolation and load current together.
Editor’s note
Do not condemn the board as soon as the F light comes on. On this model, it may be asking you to check its load supply. Start by measuring L+ against M; without that shared supply, four healthy channels cannot do their job.
Know what the coil connected to a half-amp output actually draws. A small housing is no substitute for a rating; check its label or technical data. When four loads operate together, check their combined demand too.
Remember that the output can recover automatically once a short circuit clears. Think through the machine’s response before measuring or intervening. Finding the fault should not bring an unexpected movement.
If the station screen says 8DQ, do not look for eight physical channels on this board. That is a configuration identifier; the module has four outputs. Read the label, wiring drawing and project identifier together to avoid an unnecessary search.
When buying a used Siemens 440-8MA11, ask for all four channels to be checked with suitable loads. Include bus-unit contacts and the red F indicator’s behavior. A sound board also needs the correct connections to work properly in the machine.
OtomasyonAVM resources and PDFs
+ OtomasyonAVM S5 PDF files and manuals. See page 2-24 of the ET 100U manual below for this model’s specifications and connection drawing.
Related topics
+ 440-8MA12 · 440-8MA21 · 440-8MA22 · 441-8MA11 · 700-8MA11 bus unit · PLC troubleshooting.
Browse SIMATIC S5
+ S5 digital output modules · S5 cables and connections · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.