6ES5 435-7LC11

Siemens 6ES5 435-7LC11 — 8-Channel 115 V AC/DC Digital Input Module

The Siemens 6ES5 435-7LC11 provides eight 115 V UC, or AC/DC, digital inputs in the SIMATIC S5 family. Within the S5 digital input range, it has individually optocoupler-isolated channels, arranged as 8 × 1 input groups. Siemens lists it for S5-115U/H/F systems in the ST 50 catalog.

It transfers contact states from 115 V control circuits to a Siemens S5 PLC. A pushbutton, limit switch or relay contact switches the appropriate external signal voltage; the module does not detect an unpowered dry contact by itself. Check the complete order number against the existing S5 rack and CPU configuration.

115 V UC, input thresholds and current

Nominal signal voltage is 115 V AC/DC. AC operation requires 47–63 Hz. The specified logic-0 range is 0–40 V, and the logic-1 range is 85–135 V. Do not assume a defined state between these ranges. 24 V is not a valid logic-1 signal for this module.

Typical input current at logic 1 is 10 mA on AC and 6 mA on DC. Select a signal source that can supply the required input current as well as the correct voltage.

Individual isolation and connection checks

Isolation is arranged in single-input groups. Wire each channel’s signal and return according to its circuit diagram. The exact module page, 15-27 of the S5-115U manual, prohibits connecting different phases; individual channel isolation does not permit unrestricted phase selection. Match the front connector and wiring to the module drawing, and do not use protective grounding as a signal-return conductor.

Internal consumption from the 5 V rail is 5 mA, with typical module power loss of 5.5 W. In S5 power-supply calculations, distinguish internal consumption from field input currents. The 115 V signal voltage is separate from the internal 5 V supply.

Response time and two-wire sensors

Input delay is 2–13 ms for a 0 → 1 transition and 10–25 ms for a 1 → 0 transition. Turn-on and turn-off are therefore asymmetric. For short pulses, account for CPU scan time as well as the input delay; this module should not be treated as a high-speed counter input.

The manufacturer permits two-wire BERO proximity switches and specifies a 5 mA quiescent-current figure. When selecting a two-wire sensor, check voltage rating and off-state current together. The PNP/NPN distinction matters for many 24 V DC sensors, but it does not by itself make a sensor suitable for this 115 V UC input.

Addressing and tracing an input

Match the input address used in the PLC program to the actual CPU, rack and hardware configuration. A channel number printed on the module is not an absolute PLC address by itself. During troubleshooting, compare field voltage, the channel LED and the program’s input bit for the same signal.

Differences within the 435 and 436 ranges

The 435-7LA11 has 16 inputs in groups of four at 115 V UC; the 435-7LB11 has 16 inputs in groups of two. The 435-7LC11 has eight inputs in individual groups. A change in channel count also requires reviewing wiring and address usage.

The 436-7LA11, 436-7LB11 and 436-7LC11 are 230 V UC models. The 430-7LA12 provides 32 inputs at 24 V DC, while the 434-7LA12 provides eight 24 V DC inputs with interrupt/group-signal functionality. Similar channel counts do not establish direct interchangeability.

Editor’s note

Start a bench check by writing down the 115 V rating on the label. If the input does not turn on with your usual 24 V test supply, give the board a fair chance: this model is not supposed to recognize that voltage as logic 1.

Do not connect different phases simply because each channel is isolated. This model’s manual includes a specific restriction. Number the wires and photograph the original connections before removal; that small record can save a long fault-finding session.

If an input stays on with a two-wire sensor switched off, check the sensor’s quiescent current first. An unloaded voltage reading does not tell the whole story. Measure across the correct signal and return terminals with the input connected.

When the machine occasionally misses a short pulse, leave room to check the hardware timing too. This module is slower on the transition back to zero. Knowing how long a signal lasts is more useful than knowing only that it arrived.

When buying a used Siemens 435-7LC11, ask for all eight inputs to be checked both on and off at a suitable voltage. Request clear photographs of the label, front connections and board surface. One illuminated LED is a start, not a complete eight-channel check.

OtomasyonAVM resources and PDFs

+ Siemens S5-115 PDF files and manuals. Use the connection drawing for the complete 6ES5 435-7LC11 order number.

Related topics

+ 435-7LA11 · 435-7LB11 · 436-7LC11 · Two-wire sensors · PLC troubleshooting.

Browse SIMATIC S5

+ S5 digital input modules · S5 cables and connectors · SIMATIC S5 · Siemens S5 PLCs · Siemens second-hand main page.

Siemens and external references

+ Siemens S5-115U manual — EWA 4NEB 811 6130-02b; printed page 15-27: exact 435-7LC11 specifications, terminal drawing and phase restriction.

+ Siemens ST 50, 1998 — printed pages 3/30–3/32: digital input comparisons and S5-115U/H/F ordering data; externally archived copy.

+ Siemens S5 to S7-1500 migration guide — 105106251, 04/2015; page 40: 435-7LC11, eight inputs, 115 V UC and 8 × 1 grouping.