6ES5 434-4UA12

Siemens 6ES5 434-4UA12 — 32-Input TTL / CMOS / NAMUR Module

Siemens 6ES5 434-4UA12 is a 32-input digital module for TTL, CMOS and NAMUR signals in SIMATIC S5-135U/155U systems. This model in the S5 digital input range uses a 5–15 V DC LH+ interface for low-voltage logic signals. Galvanic isolation covers one group of all 32 inputs; the individual channels are not isolated from one another.

Connection arrangements are provided for NAMUR sensors and suitable two-wire sensors. However, Siemens explicitly states that the module is not intrinsically safe. Accepting NAMUR signals does not make it an Ex input barrier; distinguish it from the 6ES5 437-8EA12 Ex input module.

TTL, CMOS and NAMUR signal thresholds

For TTL inputs, logic “0” is 0–0.8 V and logic “1” is 2.4–5 V. CMOS thresholds are 0–0.3 × LH+ for “0” and 0.7 × LH+–LH+ for “1”. NAMUR current thresholds are at most 1.2 mA for “0” and at least 2.1 mA for “1”.

Power supply and 16-input connection sections

The module’s L+/L− supply is 24 V DC, with a permitted range of 20–30 V DC. Distinguish the LH+ sensor interface from the L+ supply. A 24 V power supply does not permit 24 V to be applied to a TTL input. Assess reference connections and measures against interference together with the sensor supply.

Sensor wiring is arranged in two sections of 16 inputs. For TTL/CMOS operation, LH+ receives a suitable external supply; in the NAMUR arrangement, LH+ serves as a sensor-supply output. These two wiring sections are not separate galvanic-isolation groups. Check front-connector jumpers against the manual’s sensor-selection table. For 42-contact crimp connectors such as 6ES5 497-4UA12, record contact positions and wire markings.

Response time and F+/F− enable input

Typical delay is 3 ms for both rising and falling edges, with a specified range of 1.4–5 ms. Maximum input frequency is 100 Hz. An open TTL/CMOS input is read as logic “1”, with its LED illuminated. Account for this behavior when testing.

The F+/F− enable input uses front-connector terminals 1 and 2. With jumper X20 inserted, the enable input is active; this is the factory setting. Its logic “1” range is 4–33 V. If all inputs fail together, check F+/F− and the supplies before replacing sensors. Establish the purpose of the jumper setting before changing it.

Addressing and related part numbers

32 inputs correspond to four input bytes. Establish the starting address from the rack arrangement, address setting and installed interface module. Compare byte/bit addresses in the PLC program with field-wire numbering.

6ES5 434-4UA11 is a different revision; check the complete number and wiring arrangement before replacement. 6ES5 434-7LA12 belongs to a different system and input specification. Do not select a spare from the “434” designation alone.

Editor’s note

Start by identifying whether the sensor in this Siemens S5 application is TTL, CMOS or NAMUR, then check the LH+ supply. An incorrect voltage level can turn a straightforward repair into an additional fault.

Illuminated LEDs with the wiring disconnected need not be surprising. An open TTL/CMOS input reads as “1”. Test each input in both states using the correct signal levels before judging the module’s condition.

A two-wire sensor being NAMUR does not establish Ex suitability. 434-4UA12 is not an intrinsically safe module. If the installation includes a separate barrier or isolator, identify its function from the circuit diagram.

Back up the program and memory arrangement, and photograph connector jumpers, F+/F− wiring and the X20 position before removal. Isolate the supply and verify that the equipment is de-energized. Clear records make the replacement much easier.

When buying a used Siemens module, ask for more than one or two illuminated LEDs. A test record should cover all 32 inputs and the sensor-wiring arrangement being used. Inspect the connector for loose contacts, darkening and added jumpers as well.

OtomasyonAVM resources and PDFs

+ S5 digital input modules

+ OtomasyonAVM S5 PDF archive

+ How NAMUR sensors work

Related topics

+ 6ES5 434-4UA11 — different revision

+ 6ES5 434-7LA12 — different input model

+ 6ES5 437-8EA12 — NAMUR Ex input

+ 6ES5 497-4UA12 — crimp front connector

Browse SIMATIC S5

+ S5 digital inputs · S5 cables and connectors

+ SIMATIC S5 overview · Used Siemens equipment

Siemens and external references

+ Siemens S5-135U/155U system manual — English, C79000-G8576-C199-07; section 8.4.5, p. 8-39: exact-code specifications

+ Same manual, pp. 8-40–8-41 — TTL/CMOS/NAMUR supplies, jumpers, F+/F− and X20