6ES5 430-4UA13

Siemens 6ES5 430-4UA13 – 32-Channel, 24 V DC Digital Input Module

6ES5 430-4UA13 is a compact U-design digital input module for S5-135U/155U controllers in the SIMATIC S5 range. It provides 32 inputs rated at 24 V DC. The field circuitry is galvanically isolated from the system, with all 32 inputs sharing one isolation group. Typical input delay is 4 ms; the specified maximum input frequency is 100 Hz.

The module reads on/off signals from suitably wired inductive sensors, photoelectric sensors and limit switches. Typical signals indicate a detected part, an established position or a closed contact. 32 inputs do not provide 32 independent supply domains or individually isolated channels.

Input levels and field signals

For the 4UA13 revision, logic 0 is −3 to +7 V and logic 1 is +13 to +33 V. Rated input current is 7 mA and typical input resistance is 3.3 kΩ. The delay range is 2.5–6.5 ms; assess short pulses against both input delay and the CPU scan.

Check the PNP/NPN output arrangement before connecting a sensor. The Siemens diagram shows positive voltage being switched onto the input. A contact test needs both a suitable 24 V signal and the correct common return. Do not assume an NPN output will operate with the same wiring.

Supply, front connector and enable circuit

The external L+/L− supply is 24 V DC, with a permitted range of 20–30 V DC. Typical external consumption is approximately 100 mA; typical consumption from the 5 V system bus is also 100 mA. Distinguish the S5 system power supply from field power. Measure a signal switched by a relay contact against the module’s own L− reference.

For the S5 front connector and wiring, terminal 3 is L+ and terminals 21 and 42 are L−. The four input bytes use terminals 4–11, 13–20, 25–32 and 34–41, respectively. When checking sensor connectors, trace both the terminal number and the cable identification.

Terminal 1 is F+ and terminal 2 is F−. With jumper X20 fitted, the enable circuit is active and requires voltage across F+/F−; removing the jumper disables this function. Loss of an active enable supply can prevent program access to the module and cause a CPU QVZ access timeout. Match the jumper arrangement to the installed machine design.

Four-byte addressing

The module occupies four consecutive input bytes. Its addressing switch sets the start address using binary weights; the slot number alone does not determine the address. In PLC programming, STEP 5 input addresses must agree with the physical switch setting.

For example, 80 = 64 + 16 = 50H selects IB80–IB83, covering I80.0–I83.7 in English notation. German STEP 5 notation uses E instead of I. The next unused input byte is 84. Reserve the entire four-byte range in the PLC project. This is an example, not a prescribed machine address.

Revision differences and module function

Although 6ES5 430-4UA14 appears in the same connection table, 4UA13 requires L+ at terminal 3. The 4UA14 exception does not apply to this revision. 6ES5 420-4UA13 is the non-isolated version. A matching channel count and similar front panel are insufficient grounds for treating these modules as interchangeable.

430-4UA13 reads binary field states. Use the appropriate S5 analog modules for continuous measurements and S5 digital output modules for load control. Dimensions are 20 × 255 × 195 mm, approximate weight is 0.4 kg, and rated power dissipation is 8.3 W.

Editor’s note

With an older module, start with the label rather than its general appearance. When selecting a Siemens S5 spare, record the full 4UA13 suffix, addressing switches and X20 position. A clear photograph of the original setup can save a great deal of troubleshooting after replacement.

If every input is unresponsive, check terminal 3 L+, the L− return and the enable arrangement before condemning the board. Voltage at a sensor does not prove that the same signal reaches the module terminal under operating conditions. Work through the connection one point at a time.

If a green LED changes but the program bit does not, pause and check which byte you are monitoring. During PLC troubleshooting, compare the complete four-byte allocation, selected bit and program conditions. An addressing mismatch can look remarkably like a failed input module.

For a used module, test all 32 inputs, not just the first accessible channel. A controlled test connection independent of the installed field sensors lets you compare each LED with its CPU bit. Arrange the test so that changing input states cannot produce unintended machine movement.

Remember the single shared isolation group. Do not distribute unrelated machine references across the inputs without reviewing the circuit design. If the front connector shows oxidation, loose contacts or heat damage, fitting another board may leave the original fault in place. Find the connection problem as well as checking the module.

OtomasyonAVM resources and PDFs

See About Siemens S5 PLC for system context and S5 cables and connectors for the connection accessory group.

+ OtomasyonAVM S5 PDF and manual archive. The technical reference used here is the English S5-135U/155U system manual linked below.

Related topics

+ 6ES5 430-4UA14: compare the terminal 3 supply requirement and revision-specific specifications.

+ 6ES5 420-4UA13: non-isolated 32-input, 24 V DC version; review the isolation difference.

Browse SIMATIC S5

+ S5 digital input modules · SIMATIC S5 system pages · Siemens S5 PLC · Siemens second-hand equipment

Siemens and external references

+ Siemens S5-135U/155U System Manual — C79000-G8576-C199-07, Edition 07, November 1999, English. Section 8.4.2; printed pages 8-32–8-33 / PDF pages 346–347: exact 430-4UA13 specifications and wiring.

+ Same Siemens manual — Section 8.1.2; printed pages 8-5–8-7 / PDF pages 319–321: enable operation and QVZ. Section 8.2.1; printed pages 8-14–8-16 / PDF pages 328–330: addressing switch and four-byte allocation.