Simatic 90U-115U

Siemens SIMATIC S5 CPUs, Central Units and Expansion Racks

Siemens SIMATIC S5 equipment includes compact PLCs, separate CPU modules, central units and expansion racks. This section covers S5-90U, S5-95U/95F, S5-101U and S5-100U CPU records, together with central and expansion units for S5-135U, S5-150U and S5-155U systems.

When selecting a replacement, compare the complete Siemens order number, hardware revision and supply rating. A compact PLC contains its processor, while a modular central rack is populated with a CPU and other modules. An expansion unit provides additional module capacity through the appropriate system connection and requires a central controller.

Siemens SIMATIC S5 compact PLCs, central units and expansion racks

S5-90U and S5-95U compact PLCs

The S5-90U 6ES5 090-8MA01 and S5-95U models 6ES5 095-8MA01, 6ES5 095-8MA02, 6ES5 095-8MA03, 6ES5 095-8MA04 and 6ES5 095-8MA05 belong to the compact controller group. Supply arrangements and hardware features differ between the S5-90U and S5-95U. Check the exact model page for onboard I/O, communications and expansion requirements before connecting a replacement.

S5-95F models 6ES5 095-8FA01, 6ES5 095-8FA02 and 6ES5 095-8FB01 require their specific system configuration. The two paired basic units must have identical order numbers and revision levels. Replacement work must account for the configured system and application validation as well as physical connections.

S5-101U central controllers and expansion units

S5-101U central controller records include 6ES5 101-8UA11, 6ES5 101-8UA12, 6ES5 101-8UA13 and 6ES5 101-8UB13. Check the complete order number for I/O capacity, supply requirements and hardware version. 6ES5 101-8UA23 has triac outputs, while 6ES5 101-8UA33 has transistor outputs; the connected loads and wiring must suit the output technology.

6ES5 101-8UC11 and 6ES5 101-8UC31 are S5-101U expansion units. They are selected with the matching central controller and expansion cable. UC11 is the relay output version and UC31 is the transistor output version. Compare the appropriate wiring diagrams before transferring field wiring.

S5-100U CPU 103

CPU 103, order number 6ES5 103-8MA03, is a processor module for the S5-100U. It executes the user program in a modular system with separately selected I/O modules and bus units. A CPU replacement requires checks of the existing program, compatible memory submodule and connected peripherals.

S5-135U, S5-150U and S5-155U central racks

Central unit and rack records 6ES5 135-3KA13, 6ES5 135-3KA21, 6ES5 135-3KB13, 6ES5 135-3UA11, 6ES5 135-3UA21 and 6ES5 135-3UA41 must be checked individually. The central rack order number identifies different hardware from the CPU fitted inside it. Selection depends on the power supply, backplane, permitted module positions and supplied modules.

The S5-150U central unit 6ES5 150-3SB61 and 188-series records 6ES5 188-3UA11, 6ES5 188-3UA12, 6ES5 188-3UA21, 6ES5 188-3UA22 and 6ES5 188-3UA32 should be assessed in the same way. Confirm whether the offered assembly includes a CPU, power supply, fan assembly and memory submodule. A photograph of a populated rack does not establish which modules are included in the sale.

180, 181, 182, 183, 184 and 185 expansion racks

For expansion unit records 6ES5 180-3AA11, 6ES5 181-3AA11, 6ES5 182-3AA21 and 6ES5 182-3KH61, check the central system, interface requirements and supply arrangement first. Similar rack dimensions or connectors are insufficient evidence that expansion units from different generations are interchangeable.

Check the power supply, cooling and interface modules for 183-series records 6ES5 183-3UA12, 6ES5 183-3UA13 and 6ES5 183-3UA22, and for 6ES5 185-3UA11. With 184U expansion racks 6ES5 184-3UA11 and 6ES5 184-3UA21, the fan supply and the module supply are separate considerations. A running fan alone does not establish that the backplane is correctly powered.

Memory and special function records

This section also links to memory/parameter board 6ES5 234-1AD11 and the IP 240 counter/positioning module 6ES5 240-1AA11. These boards perform different functions from a CPU. For IP 240 replacement, check the application, parameters and documented transition requirements; different order number suffixes do not automatically identify interchangeable versions.

Selecting used S5 equipment

Compare the complete model, quantity, working/faulty condition, readable nameplate photographs and price. The test scope, missing connectors and included modules should be identified separately for each assembly. A power-on check alone does not establish that all I/O channels and communication functions have been tested.

Editor’s note

Start by identifying exactly what you need: a CPU, a complete central unit or a bare rack. Record the nameplates of the assembly and its individual modules separately. This makes a replacement easier to check before purchase.

Before removing a CPU or memory submodule from a working machine, back up the program and existing parameters. Investigate battery warnings and follow the procedure for the specific controller. Do not assume that the stored program will survive removal or an incorrect battery change.

Look closely at the backplane connectors even when a used rack appears clean. Bent pins, corrosion, loose latches and heat damage can cause intermittent faults under vibration. Have the supply outputs and cooling checked under suitable load conditions.

For an S5-101U, distinguish relay, triac and transistor outputs before moving any field wiring. Similar terminals may serve loads with different electrical requirements. Use the wiring diagram for the complete order number.

An S5-95F needs checks of its paired basic unit, revision, connections and application conditions. A RUN indicator alone is insufficient evidence that a system used for safety functions has been validated.

Agree the documented test scope and included items before buying used equipment. Workshop testing is possible, with the method and scope agreed for the particular device. All sales require an invoice; returns are not accepted. To offer S5 equipment for sale, send the model, quantity, condition, nameplate photographs and asking price to otomasyonavm@gmail.com.

OtomasyonAVM resources and PDFs

For system background, see About Siemens S5 PLCs and the SIMATIC S5 main page. For other processor records, see the SIMATIC S5 CPU models section.

Use the S5 system manuals and PDF files archive to locate documentation. S5-90U documents are also available under S5-90U PDF files. Check the family, complete order number and edition covered by each document before using a wiring diagram.

Related topics

Check S5 power supplies, S5 interface modules, S5 memory submodules and S5 cables and connectors when planning a central unit replacement. S5 racks and mounting hardware and S5 positioning modules can be reviewed for the specific system.

Browse SIMATIC S5

+ SIMATIC S5   |   Siemens S5 PLCs   |   S5 module groups   |   Used Siemens equipment   |   All used equipment

Siemens and external references

+ S5-90U/S5-95U System Manual — EWA 4NEB 812 6115-02b; English.

+ S5-101U Operating Instructions — EWA 4NEB 810 2119-02c; English.

+ S5-100U Programmable Controller Manual — EWA 4NEB 812 6120-02b; English.

+ S5-135U/155U System Manual — C79000-G8576-C199-07; 6ES5998-0SH21; English.

+ S5-95F Programmable Controller Manual — EWA 4NEB 812 6220-02; English.

+ Guide for Migrating SIMATIC S5 Projects to SIMATIC S7-1500 and TIA Portal — 105106251; V1.0, 04/2015; English.

+ IP 240 product information and model transition notes — EWA 4NEB 811 6123-10; German.


Refine Search