Siemens G120 fault codes 5

    A07920 - Torque/Speed Too Low

> Meaning: Torque is below the torque/speed envelope curve.
- Cause: There may be a problem with the connection between the motor and the load or the parameterization may not be suitable.
+ Solution:
 ++ Check the connection between the motor and the load.
 ++ Adapt the parameterization according to the load.

    A07921 - Torque/Speed Too High

> Meaning: Torque is above the torque/speed envelope curve.
- Cause: There may be an excessive load or a problem in speed control.
+ Solution: Apply the above solutions and if necessary, reduce the load or review the parameterization.

    A07922 - Torque/Speed Outside Tolerance
> Meaning: Torque/speed values are outside the defined tolerance.
- Cause: There may be a mismatch in the load or speed control.
+ Solution: Apply the above solutions and if necessary, review the parameterization.

    F07923 - Torque/Speed Too Low
> Meaning: Torque/speed values are lower than expected.
- Cause: There may be a problem with the connection between the motor and the load or the parameterization may not be suitable.
+ Solution:
 ++ Check the connection between the motor and the load.
 ++ Adapt the parameterization according to the load.

    F07924 - Torque/Speed Too High
> Meaning: Torque/speed values are higher than expected.
- Cause: There may be an excessive load or a problem in speed control.
+ Solution: Apply the above solutions and if necessary, reduce the load or review the parameterization.

    A07927 - DC Braking Active
> Meaning: The DC braking process is active.
- Cause: The motor may need to be stopped quickly.
+ Solution: This status is an explanation and does not require a specific solution. The DC braking process is automatically activated when needed.

    A07980 - Rotary Measurement Active
> Meaning: The rotary measurement process is active.
- Cause: The position or speed of the motor may need to be measured.
+ Solution: This status is an explanation and does not have a specific solution. The rotary measurement process is automatically activated when needed.

    A07981 - No Activation for Rotary Measurement
> Meaning: The necessary activations for the rotary measurement process have not been made.
- Cause: The conditions required for performing the rotary measurement process may not have been met.
+ Solution: Confirm pending faults. Set up missing activations (see r00002, r0046).

    A07991 - Motor Data Identification Active
> Meaning: The motor data identification process is active.
- Cause: The characteristics of the motor may need to be identified.
+ Solution: Turn on the motor and identify the motor data.

    F08501 - Setpoint Timeout
> Meaning: The setpoint's defined timeout has been reached.
- Cause: There may be a problem with the PROFINET connection or the controller may not be in RUN mode.
+ Solution:
 ++ Check the PROFINET connection.
 ++ Set the controller to RUN mode.
 ++ If the error recurs, check the monitoring time (p2044).

    F08502 - Monitoring Time, Liveliness Time Expired
> Meaning: The liveliness time for the monitoring time has expired.
- Cause: There may be a problem with the PROFINET connection.
+ Solution: Check the PROFINET connection.

    F08510 - Sent Configuration Data Invalid
> Meaning: The sent configuration data is invalid.
- Cause: There may be a problem with the PROFINET configuration.
+ Solution: Check the PROFINET configuration.

    A08511 - Received Configuration Data Invalid
> Meaning: The received configuration data is invalid.
- Cause: There may be a problem with the PROFINET configuration.
+ Solution: Check the PROFINET configuration.
    A08526 - No Cyclic Connection

> Meaning: A cyclic connection could not be established.
- Cause: The control may not have been activated with cyclic operation or there may be a problem with the "Station Name" and "Station IP" parameters.
+ Solution:
 ++ Activate the control with cyclic operation.
 ++ Check the "Station Name" and "Station IP" parameters (r61000, r61001).

    A08565 - Consistency Error Affecting Adjustable Parameters
> Meaning: A consistency error was detected in adjustable parameters.
- Cause: The IP address, subnet mask, or default gateway may be incorrect. The IP address or station name may be used twice in the network. The station name may contain invalid characters.
+ Solution:
 ++ Check the IP address, subnet mask, and default gateway.
 ++ Check if the IP address or station name is used twice in the network.
 ++ Check if the station name contains valid characters.

    F13100 - Information Protection: Copy Protection Error
> Meaning: An error occurred while information protection and copy protection for the memory card were active.
- Cause: There was a problem during the control of the memory card.
+ Solution:
 ++ Insert a suitable memory card and temporarily turn off and then turn on the inverter's power supply (POWER ON).
 ++ Disable copy protection (p7765).

    F13101 - Information Protection: Copy Protection Cannot Be Enabled
> Meaning: Copy protection cannot be enabled.
- Cause: A valid memory card may not have been inserted.
+ Solution: Insert a valid memory card.

    F30001 - Overcurrent
> Meaning: An overcurrent condition was detected.
- Cause: Causes may include incorrect motor data, inappropriate motor connection method, incorrect assignment of nominal currents of the motor and Power Module in V/f operation, insufficient line quality, incorrect connection of the line commutation reactor, problems with power cable connections, short circuit or ground fault in power cables, inappropriate power cable length, or problems with line phases.
+ Solution:
 ++ Check and commission the motor data if necessary.
 ++ Check the motor's connection method (Y/Δ).
 ++ Check the assignment of nominal currents of the motor and Power Module in V/f operation.
 ++ Check the line quality.
 ++ Ensure the correct connection of the line commutation reactor.
 ++ Check the power cable connections.
 ++ Check the power cables for short circuit or ground fault.
 ++ Check the power cable length.
 ++ Check the line phases.
 ++ If these steps do not solve the problem, increase the acceleration ramp in V/f operation, reduce the load, or replace the Power Module.

    F30002 - DC Link Voltage Overvoltage
> Meaning: The DC link voltage exceeded the allowed limits.
- Cause: Voltage fluctuations or a faulty grid connection may be the cause.
+ Solution:
 ++ Increase the ramp-down time (p1121).
 ++ Adjust the rounding times (p1130, p1136).
 ++ Activate the DC link voltage controller (p1240, p1280).
 ++ Check the grid voltage (p0210).
 ++ Check the line phases.

    F30003 - DC Link Voltage Undervoltage

> Meaning: The DC link voltage fell below the allowed limits.
- Cause: A voltage drop or a faulty grid connection may be the cause.
+ Solution:
 ++ Check the grid voltage (p0210).

    F30004 - Inverter Overheating
> Meaning: The inverter is in an overheating condition.
- Cause: The inverter fan may not be working, the ambient temperature may be high, or the motor may be overloaded.
+ Solution:
 ++ Check if the inverter fan is working.
 ++ Check if the ambient temperature is within the allowed range.
 ++ Check if the motor is overloaded.
 ++ Reduce the pulse frequency.

    F30005 - I2t Inverter Overload
> Meaning: The inverter is in an I2t overload condition.
- Cause: Exceeding the nominal currents of the motor and inverter.
+ Solution:
 ++ Check the nominal currents of the motor and inverter.
 ++ Reduce the current limit (p0640).
 ++ In V/f operation mode, reduce p1341.

    F30011 - Line Phase Fault
> Meaning: A phase fault was detected at the input of the inverter.
- Cause: There may be a phase loss or a connection error.
+ Solution:
 ++ Check the input fuses of the inverter.
 ++ Check the motor cables.

    F30015 - Motor Cable Phase Fault
> Meaning: A phase fault was detected in the motor cable.

- Cause: There may be a break in the cable or a connection error.
+ Solution:
 ++ Check the motor cables.
 ++ Increase the ramp-up or ramp-down time (p1120).

    F30021 - Ground Fault
> Meaning: A ground fault was detected.
- Cause: There may be problems with power cable connections, the motor, or the current transformer. The cables and contacts of the brake connection should also be checked.
+ Solution:
 ++ Check the power cable connections.
 ++ Check the motor.
 ++ Check the current transformer.
 ++ Check the cables and contacts of the brake connection.

    F30022 - Power Module: VCE Monitoring
> Meaning: A VCE monitoring error was detected in the power module.

- Cause: There may be a fault in the power module.
+ Solution: Check or replace the inverter.



+ G120C User Manuals

+ G120C Error Index

+ G120C Error Codes 2

+ G120C Error Codes 3

+ G120C Error Codes 4

+ G120C Error Codes 5

+ G120C Error Codes 6

++ Siemens Homepage 

Reminder: Siemens G120 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. (04.09.2011)

Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!