Siemens G120 fault codes 3
F01600 - STOP A Initiated
> Meaning: The STOP A function has been activated.
- Cause: The inverter was stopped due to a safety or stop command.
+ Solution: Select STO and then deselect it.
F01625 - Safety Data Liveliness Error
> Meaning: A liveliness error was detected in the safety data.
- Cause: Issues in safety data may arise due to EMC compatibility, overvoltage, or current overload.
+ Solution:
++ Make the electrical cabinet design and cable routing EMC compliant.
++ Check if an unauthorized voltage is connected to the digital outputs.
++ Check if the digital output is loaded with an unauthorized current.
++ Check for additional errors and diagnose if necessary.
++ Select and then deselect the STO safety function.
++ Turn off and restart the inverter's power supply.
F01650 - Acceptance Test Required
> Meaning: An acceptance test needs to be conducted for the inverter, and a test certificate must be created.
- Cause: The inverter needs to be verified for correct operation and compliance with safety standards.
+ Solution: Perform the acceptance test and create the test certificate. Turn off and restart the Control Unit.
F01659 - Parameter Writing Task Rejected
> Meaning: The parameter writing task was rejected because the inverter's safety functions are active.
- Cause: The inverter is intended to be reset to factory settings, but this is not possible while safety functions are active.
+ Solution: Solution with the operator panel:
++ p0010 = 30 Parameter reset
++ p9761 = … Enter the password for safety functions.
++ p0970 = 5 Reset of safety parameters at start-up.
++ After resetting the parameter, the inverter sets p0970 to 5.
++ Then, reset the inverter to factory settings again.
F01662 - Internal Communication Error
> Meaning: An error occurred in the inverter's internal communication.
- Cause: Electrical cabinet design, overvoltage, current overload, or other communication issues.
+ Solution:
++ Make the electrical cabinet design and cable routing EMC compliant.
++ Check if an unauthorized voltage is connected to the digital outputs.
++ Check if the digital output is loaded with an unauthorized current.
++ If checks fail, turn off and restart the inverter's power supply, update the firmware, or contact technical support.
A01666 - Fixed 1 Signal for Safe Confirmation for F-DI
> Meaning: A fixed 1 signal has been set for safe confirmation for F-DI (Frequency-Digital Input).
- Cause: A logical 0 signal is required for the F-DI input for safety reasons.
+ Solution: Set F-DI to a logical 0 signal.
A01698 - Commissioning Mode Active for Safety Functions
> Meaning: The mode for commissioning safety functions has been activated.
- Cause: A commissioning process is required to ensure the correct operation of safety functions.
+ Solution: This message is withdrawn after the safety commissioning process is completed.
A01699 - Shutdown Signal Path Test Required
> Meaning: A shutdown signal path test is required after the "STO" function is deactivated.
- Cause: It is necessary to ensure the correct operation of the shutdown signal path for safety reasons.
+ Solution: After deactivating the "STO" function, the message is withdrawn and the monitoring time is reset.
A01900 - PROFIBUS: Configuration Telegram Error
> Meaning: The PROFIBUS master is trying to connect with an erroneous configuration telegram.
- Cause: There may be an issue with the bus configuration on the PROFIBUS master and slave sides.
+ Solution: Check the bus configuration on both the master and slave sides.
A01910 / F01910 - Field Bus SS Setting Time Exceeded
> Meaning: An alarm occurs when p2040 ≠ 0 ms and one of the following reasons exists:
++ Bus connection interrupted.
++ MODBUS master switched off.
++ Communication error (CRC, parity bit, logical error).
- Cause: The field bus monitoring time (p2040) is excessively low.
+ Solution: Check and adjust the field bus monitoring time (p2040) if necessary.
A01920 - PROFIBUS: Cyclic Connection Interrupted
> Meaning: The cyclic connection with the PROFIBUS master has been interrupted.
- Cause: The connection with the PROFIBUS master has been interrupted.
+ Solution: Establish the PROFIBUS connection and activate the PROFIBUS master with cyclic operation.
F03505 - Analog Input, Wire Break
> Meaning: A wire break was detected at the analog input.
- Cause: There may be an interruption in the connection to the signal source, or the provided signal level may be insufficient.
+ Solution: Check the connection to the signal source. Check the provided signal level. The input current measured by the analog input can be read in r0752.
A03520 - Temperature Sensor Error
> Meaning: An error was detected in the temperature sensor.
- Cause: There may be an issue with the sensor's connection.
+ Solution: Ensure that the sensor is properly connected.
A05000 / A05001 / A05002 / A05004 / A05006 - Power Module Overheating
> Meaning: An overheating condition of the power module was detected.
- Cause:
++ Is the ambient temperature within the defined limit values?
++ Are the load conditions and duty cycle properly configured?
++ Has the cooling system failed?
+ Solution: Review the checklist above and make necessary corrections.
F06310 - Supply Voltage (p0210) Misconfigured
> Meaning: The supply voltage is misconfigured.
- Cause: The supply voltage is set incorrectly.
+ Solution: Check the configured supply voltage and change if necessary (p0210). Check the mains voltage.
F07011 - Motor Overheating
> Meaning: An overheating condition of the motor was detected.
- Cause: The motor may be overloaded, the ambient temperature may be high, or there may be an issue with the sensor connection.
+ Solution: Reduce the motor load. Check the ambient temperature. Check the sensor connection and cables.
A07012 - I2t Motor Model Overheating
> Meaning: Overheating was detected in the I2t motor model.
- Cause: The motor may be overloaded, or the ambient temperature may be high.
+ Solution: Reduce the motor load if necessary. Check the motor's ambient temperature. Check the thermal time constant (p0611) and the overheating error threshold (p0605).
A07015 - Motor Temperature Sensor Alarm
> Meaning: An alarm condition was detected in the motor temperature sensor.
- Cause: There may be an issue with the sensor's connection or parameter assignment.
+ Solution: Ensure that the sensor is properly connected. Check the parameter assignment (p0601).
F07016 - Motor Temperature Sensor Error
> Meaning: An error was detected in the motor temperature sensor.
- Cause: There may be an issue with the sensor's connection or parameterization.
+ Solution: Ensure that the sensor is properly connected. Check the parameterization (p0601).
F07086 / F07088 - Unit Change: Parameter Limit Violation
> Meaning: A parameter limit violation was detected during unit change.
- Cause: The adapted parameter values exceed the limits.
+ Solution: Check the adapted parameter values and correct if necessary.
F07320 - Automatic Restart Cancelled
> Meaning: The automatic restart process was cancelled.
- Cause: Insufficient restart attempts or exceeding expected times.
+ Solution: Increase the number of restart attempts (p1211). Increase the waiting time (p1212) and/or monitoring time (p1213). Generate an ON command (p0840). Increase or turn off the monitoring time of the power unit (p0857). Reduce the waiting time for resetting the error counter (p1213[1]).
A07321 - Automatic Restart Active
> Meaning: Automatic restart (AR) is active.
- Cause: The drive automatically restarts during voltage correction and/or pending error clearance.
+ Solution: This status is an explanation and does not require a specific solution. The drive automatically restarts after voltage correction and error clearance.
Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!