Siemens G120 fault codes 6
F30027 - DC Link Precharge Time Monitoring
> Meaning: A problem was detected in monitoring the DC link precharge time.
- Cause: There may be an issue with the grid voltage or the grid voltage setting.
+ Solution:
++ Check the grid voltage.
++ Check the grid voltage setting (p0210).
F30035 - Input Air Overheating
> Meaning: Overheating was detected in the input air.
- Cause: The fan may not be working, fan filter elements may be clogged, or the ambient temperature may be high.
+ Solution:
++ Check if the fan is working.
++ Check the fan filter elements.
++ Check if the ambient temperature is within the allowed range.
F30036 - Internal Area Overheating
> Meaning: Overheating was detected in the inverter's internal area.
- Cause: Internal air flow may be obstructed or the ambient temperature may be high.
+ Solution:
++ Eliminate factors obstructing internal air flow and check the ambient temperature.
F30037 - Rectifier Overheating
> Meaning: Overheating was detected in the rectifier.
- Cause: The motor load may be excessive or there may be an issue with the line phases.
+ Solution:
++ In addition to the solutions in F30035, check the motor load and line phases.
A30049 - Internal Fan Faulty
> Meaning: A fault was detected in the inverter's internal fan.
- Cause: The internal fan may be malfunctioning or not working.
+ Solution:
++ Check the internal fan and replace it if necessary.
F30052 - Power Module Data Incorrect
> Meaning: An error was detected in the power module data.
- Cause: The power module data may be incorrect or incompatible.
+ Solution:
++ Replace the inverter or update the inverter firmware.
F30053 - FPGA Data Error
> Meaning: An error was detected in the FPGA data.
- Cause: The FPGA data may be corrupted or incorrect.
+ Solution:
++ Replace the inverter.
F30059 - Internal Fan Faulty
> Meaning: A fault was detected in the inverter's internal fan.
- Cause: The internal fan may be malfunctioning or not working.
+ Solution:
++ Check the internal fan and replace it if necessary.
F30074 - Communication Error Between Control Unit and Power Module
> Meaning: A communication error occurred between the control unit and the power module.
- Cause: The external 24 V control unit power supply may have fallen below 95% of the nominal voltage.
+ Solution:
++ Check the connections between the control unit and the power module to rectify the communication error.
A30502 - DC Link Overvoltage
> Meaning: Overvoltage was detected in the DC link.
- Cause: The device supply voltage may be high or the line reactor may be inappropriate.
+ Solution:
++ Check the device supply voltage (p0210).
++ Check the sizing of the line reactor.
F30662 - CU Hardware Error
> Meaning: A hardware error was detected in the control unit.
- Cause: A hardware malfunction in the control unit.
+ Solution:
++ Turn off and restart the inverter, update the firmware, or contact technical support.
F30664 - CU Power On Cancelled
> Meaning: The power-on process of the control unit was cancelled.
- Cause: The power-on process could not be completed due to a problem in the control unit.
+ Solution:
++ Turn off and restart the inverter, update the firmware, or contact technical support.
F30850 - Software Error in Power Module
> Meaning: A software error was detected in the power module.
- Cause: There may be a problem with the software in the power module.
+ Solution:
++ Replace the inverter or contact technical support.
A30920 - Temperature Sensor Error
> Meaning: An error was detected in the temperature sensor.
- Cause: There may be an issue with the sensor's connection.
+ Solution:
++ Ensure that the sensor is properly connected.
A50001 - PROFINET Configuration Error
> Meaning: The PROFINET control is trying to connect with an erroneous configuration telegram.
- Cause: There may be a problem with the PROFINET configuration.
+ Solution:
++ Check if the "Shared Device" feature is enabled (p8929 = 2).
A50010 - PROFINET Station Name Invalid
> Meaning: The PROFINET station name is invalid.
- Cause: The station name may have been entered incorrectly or may contain invalid characters.
+ Solution:
++ Enter the station name correctly (p8920) and activate it (p8925 = 2).
A50020 - PROFINET: Second Control Missing
> Meaning: The "Shared Device" feature is enabled but only one PROFINET control is connected.
- Cause: The connection between the two control devices may not have been established.
+ Solution:
++ Check and establish the connection of the second PROFINET control device if necessary.
Reminder: Siemens G120 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. (04.09.2011)
Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!