Siemens G120 fault codes 4
F07330 - Search Current Measured Too Low
> Meaning: The search current was measured lower than expected.
- Cause: Insufficient search current or a problem with the motor connection.
+ Solution: Increase the search current (P1202). Check the motor connection.
A07400 - VDC_max Controller Active
> Meaning: The VDC_max controller is active.
- Cause: Intervention by the controller may be required.
+ Solution: If the controller should not intervene, increase the ramp-down times. Deactivate the VDC_max controller (for vector control p1240 = 0, for V/f control p1280 = 0).
A07409 - V/f Control, Current Limiting Controller Active
> Meaning: In V/f control mode, the current limiting controller is active.
- Cause: It is activated when the current exceeds the defined limit.
+ Solution: The alarm automatically disappears after one of the following measures is taken:
++ Increase the current limit (p0640).
++ Reduce the load.
++ Increase the ramp-up time for the speed setpoint.
F07426 - Technology Controller Actual Value Limited
> Meaning: The actual value of the technology controller has been limited within certain limits.
- Cause: Setting limits that are not suitable for the signal level.
+ Solution:
++ Set limits suitable for the signal level (p2267, p2268).
++ Check the actual value scaling (p2264).
A07444 - PID Auto Tuning Active
> Meaning: The automatic tuning (auto-tuning) of the PID controller is active.
- Cause: Automatic tuning of the PID controller for better performance.
+ Solution: The alarm automatically disappears after the auto-tuning process is completed.
F07445 - PID Auto Tuning Cancelled
> Meaning: The inverter cancelled the automatic tuning (auto-tuning) of the PID controller due to an error.
- Cause: An error occurred during auto-tuning.
+ Solution: Increase p2355 and restart the auto-tuning process.
F07801 - Motor Overcurrent
> Meaning: An overcurrent condition was detected in the motor.
- Cause: Overloading of the motor or situations like a short circuit.
+ Solution:
++ Check the current limits (p0640).
++ In V/f control, check the current limiting controller (p1340 … p1346).
++ Increase the acceleration ramp (p1120) or reduce the load.
++ Check the motor and motor cables for short circuit and ground fault.
++ Check the motor's star-delta connection and plate parameters.
++ Check the power unit/motor combination.
++ Select the flying restart function for the rotating motor (p1200).
A07805 - Drive: Power Unit Overload I2t
> Meaning: An I2t overload condition was detected in the power unit.
- Cause: Excessive continuous load or an inappropriate load cycle.
+ Solution:
++ Reduce the continuous load.
++ Adjust the load cycle.
++ Check the assignment of the nominal currents of the motor and power unit.
F07807 - Short Circuit Detected
> Meaning: A phase-to-phase short circuit was detected on the motor side of the inverter connection.
- Cause: Short circuit between phases or with the ground.
+ Solution:
++ Check the connections on the motor side of the inverter for phase-to-phase short circuits.
++ Ensure that the line and motor cables are not swapped.
A07850 - External Alarm 1
> Meaning: The "External alarm 1" signal was triggered.
- Cause: An alarm signal from an external source.
+ Solution: The source of this alarm is defined by the parameter p2112. Rectify the cause of the alarm.
F07860 - External Fault 1
> Meaning: A fault occurred in the inverter due to an external fault.
- Cause: A fault condition originating from an external source.
+ Solution: Rectify the external fault causes.
F07900 - Motor Blocked
> Meaning: The motor's ability to rotate is blocked.
- Cause: A mechanical obstacle or excessive load may prevent the motor from turning.
+ Solution:
++ Ensure that the motor can rotate freely.
++ Check the torque limit for the positive rotation direction (r1538); for the negative rotation direction (r1539).
F07901 - Motor Overspeed
> Meaning: The speed of the motor exceeded the allowed limits.
- Cause: Uncontrolled speed increase.
+ Solution: Activate the pre-control of the speed limiting controller (p1401 bit 7 = 1).
F07902 - Motor Jammed
> Meaning: The motor is jammed and unable to move.
- Cause: A mechanical obstacle or insufficient magnetization may prevent the motor from turning.
+ Solution:
++ Check whether the motor data is correctly parameterized and perform motor identification.
++ Check the current limits (p0640, r0067, r0289). If the current limits are too low, the drive cannot be magnetized.
++ Check if the motor cables are disconnected during operation.
A07903 - Motor Speed Deviation
> Meaning: An unexpected deviation occurred in the motor speed.
- Cause: High torque demand or a problem in speed control.
+ Solution:
++ Increase p2163 and/or p2166.
++ Increase the torque, current, and power limits.
A07910 - Motor Overheating
> Meaning: The motor is in an overheating condition.
- Cause: Excessive load, high ambient temperature, or sensor issues.
+ Solution:
++ Check the motor load.
++ Check the motor's ambient temperature.
++ Check the KTY84 or PT1000 sensor.
Reminder: Siemens G120 and other Siemens drive are available for sale at Otomasyon Mall. Please note that some devices are used products, so take this into consideration when purchasing. Once these products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. (04.09.2011)
Please Note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please feel free to share them with us!