6ES7 138-4CF01-0AB0

Siemens 6ES7 138-4CF01-0AB0 – ET 200S PM-E F pm PROFIsafe Power Module

Siemens 6ES7 138-4CF01-0AB0 is a PM-E F pm DC 24 V PROFIsafe fail-safe power module for SIMATIC ET 200S stations. It provides safety-controlled disconnection of an approved output group's supply, together with additional fail-safe outputs. Within the Siemens ET 200 family, it belongs to the ET 200 safety modules used in applications requiring a defined safe shutdown.

The module operates from an external 24 V DC supply. It does not convert mains voltage into 24 V DC. Siemens specifies a 30 mm width and an approximate weight of 88 g. When selecting equipment, distinguish the role of these ET 200 power modules from the role of the external power supply feeding the station.

P1/P2 Switching and Additional Fail-Safe Outputs

The module combines relay switching of the P1 and P2 potential buses with two electronic fail-safe outputs, DO0 and DO1. The relay-switched group has a 10 A rating, while each electronic output is rated at 24 V DC / 2 A. Temperature, mounting orientation and load conditions must be considered when establishing the permitted operating current. These figures should not simply be added together to create an overall output rating.

Disconnecting the supply to a group of standard digital output modules serves a different purpose from controlling a load through a dedicated fail-safe output. Before ordering, establish which arrangement the existing project uses. For connected contactors and relays, selection should also consider release behaviour and feedback arrangements alongside coil current.

Understanding the Conditional Safety Ratings

With standard DO modules supplied through P1/P2, the achievable rating is SIL 2 / Category 3 for both P1/P2 and DO0/DO1. With no standard DO modules on P1/P2, suitable applications using DO0/DO1 can achieve SIL 3 / Category 4. The manufacturer's SIL 3 arrangement for the relay outputs has additional conditions, including no standard DO modules and signal changes at least once a day. The complete module therefore cannot be described as providing SIL 3 in every configuration.

The April 2004 Siemens manual covering CF01 identifies 6ES7 132-4BD00-0AA0 for safety-related shutdown of standard outputs to SIL 2. Compatibility must not be assumed for every ET 200S output card. Likewise, using PROFIsafe does not establish the safety rating of an entire machine: the program, wiring and final control elements also form part of the assessment.

Terminal Bases and P/M Switching

The specified terminal bases are TM-P30S44-A0 / 6ES7 193-4CK20-0AA0 with screw terminals and TM-P30C44-A0 / 6ES7 193-4CK30-0AA0 with spring terminals. The electronic module and its terminal base are separate components, so an enquiry should clearly identify which items are required. The guide to spring connectors and screw terminals explains the practical differences between connection methods.

P/M switching involves both the positive and return sides of the load circuit. A load's return conductor should not be moved to another common terminal simply to match an existing cabinet wiring habit. Follow the manufacturer's diagram for the actual application. The circuit's M reference and protective earth also have different purposes; the grounding arrangement should be checked separately from the fail-safe output connections.

Supply, Communication and Diagnostics

Siemens specifies no reverse-polarity protection for this model. Check the external DIN rail power supply, supply polarity and suitable circuit protection together. The electronic short-circuit protection specification should not be treated as a statement that every supply and relay circuit in the cabinet needs no additional protection.

The safety function requires a suitable F-CPU, safety program and supported ET 200S interface. General PLC compatibility is only the starting point: compare the CPU, interface, engineering software and module revision against the actual project. When reviewing PROFIBUS and PROFINET or selecting ET 200 communication interfaces, do not transfer the capabilities of a different revision to CF01 without verification.

The front panel provides a green PWR indicator, a red SF indicator and green output status indicators. During troubleshooting, read these alongside CPU diagnostics and any messages displayed on the operator panel. An indicator alone does not prove that the machine has reached a safe state. Return to operation should follow the project's defined procedure after the cause of the fault has been resolved.

Editor's Advice

Before ordering a replacement, photograph the module label, terminal base and output group to its right. Keep the complete order number, hardware revision, address settings and project backup together in the maintenance record. Identifying which cards receive power through P1/P2 is especially useful when checking suitability. If a similar part number is proposed, verify the application's safety conditions as well as the physical fit.

Technical Documents and Related Topics

For wiring diagrams, safety-rating conditions and commissioning details, visit the Siemens ET 200 manuals and PDF documentation page. Confirm that the selected document explicitly covers 6ES7 138-4CF01-0AB0. The Siemens ET 200 overview explains the wider system, while the ET 200 connection modules section covers related installation components.