6ES7322-1EL00-0AA0
Siemens 6ES7322-1EL00-0AA0 – SM322 32-Output 120 V AC Module
6ES7322-1EL00-0AA0 is a Siemens SIMATIC S7-300 SM322 digital output module with 32 electronic AC outputs. Its rated load voltage is 120 V AC, with a nominal current of 1 A per channel. When selecting S7-300 digital output modules, consider load voltage, group current, connector arrangement, cabinet space and test condition.
120 V AC load circuits and applications
The permissible load supply range is 93–132 V AC. Do not apply 230 V AC directly. Check equipment nameplate voltages when selecting contactor coils, AC valves and indicator lamps. Evaluate continuous consumption separately from starting current.
Switching commands come from the S7-300 CPU. Address the power supplies for the CPU and auxiliary circuits, and the switched 120 V AC load circuits, according to their respective supply and protection requirements.
Four output groups and current budgeting
The outputs form four isolated groups of eight channels. With horizontal mounting up to 60 °C, the maximum total current is 3 A per group. The 1 A channel rating does not permit all eight channels to switch a combined 8 A simultaneously.
For example, eight 0.5 A loads in one group total 4 A, exceeding the stated 3 A limit. Calculate load distribution from actual operating conditions and identify outputs that operate together. Paralleling outputs to increase current capacity is not supported.
Two front connectors and wide housing
This version uses two 20-pin front connectors and has an 80 mm housing width. Before ordering, check whether both connectors are included, the condition of the covers and the available mounting space. Channel count alone is insufficient to establish terminal compatibility.
Compare output addresses in the PLC program with the installed hardware. Keep cable and connector markings readable to prevent swapping connectors, and disconnect power before removal or installation.
Small loads, protection and fault indication
The minimum load current is 10 mA, with a maximum off-state residual current of 3 mA. Consider these values when selecting low-consumption electronic inputs or lamps. A voltage measured without a load should not be treated as proof of an output fault without appropriate loaded testing.
The module provides a green status LED for each channel and red group fault indicators. Siemens lists output short-circuit protection as unavailable; group fuses alone do not guarantee that electronic outputs will survive a short circuit. Evaluate protection together with the connected loads and wiring.
Diagnostic interrupts are not supported. Use suitable feedback through digital inputs where actual machine status needs monitoring. An output command shown on an HMI is not sufficient evidence that the load is operating.
Assessing a used module
When assessing this model among used Siemens products, check all 32 outputs and all four groups with suitable loads. Investigate outputs remaining on, excessive voltage drop under load, fuse condition and abnormal heating. Qualified personnel should carry out testing with suitable equipment.
Review the nameplate photograph, test results and supplied accessories before purchase. Confirm availability, price and any warranty terms for the actual unit offered.
Related topics and product groups
S7-300 overview | S7-300 CPU modules | Digital input modules
Digital output modules | Function modules | Analog module range
Used Siemens products | Used equipment overview | OtomasyonAVM home
Manufacturer references
Siemens – 6ES7322-1EL00-0AA0 product information | Siemens – technical data sheet (archived copy) | Siemens – S7-300 module manual, section 3.17 (archived copy)