6ES7322-1BP50-0AA0
Siemens 6ES7322-1BP50-0AA0 – SM322 64-Output 24 V DC Sinking Module
6ES7322-1BP50-0AA0 provides 64 digital outputs in the Siemens SIMATIC S7-300 SM322 family. Its nominal ratings are 24 V DC and 0.3 A per channel, with sinking, M-switching outputs. When selecting S7-300 digital output modules, check output polarity, group current, temperature, connection accessories and CPU compatibility.
What a sinking output does
When activated, the output completes the load's current path to M/0 V. The other side of the load connects to the positive supply. The field device's input arrangement and common connection must therefore suit an M-switching output. The description “24 V digital output” alone does not establish polarity compatibility.
When selecting a 24 V DC power supply, calculate simultaneous load demand and starting currents. Match L+ and M connections, group supplies and load polarity to the electrical drawings.
Four groups and temperature-dependent current limits
The module has four isolated groups of 16 channels. With horizontal mounting, maximum group current is 2 A up to 25 °C, 1.6 A up to 40 °C and 1.2 A up to 60 °C. With vertical mounting up to 40 °C, the limit is 1.6 A per group.
The 2 A/group and 8 A/module ratings do not apply at every temperature. At 60 °C with horizontal mounting, total module current is limited to 4.8 A. Operating all 16 channels of one group at 0.3 A would require 4.8 A and exceed the group rating. Distribute loads according to actual simultaneous operation.
Terminal blocks and connecting cables
Field wiring uses two 40-pin terminal blocks and suitable connecting cables. Siemens specifies the 6ES7392-1xN00-0AA0 terminal block and 6ES7392-4Bxx0-0AA0 cable families. The “x” characters represent variants; confirm complete accessory codes and cable lengths before ordering.
Do not assume terminal blocks and cables are included. Inspect connector latches, pins, cable markings and terminal connections. Availability of the module alone does not establish that it can connect directly to the existing cabinet wiring.
Configuration, protection and status monitoring
Check the CPU model and, where applicable, ET 200M interface version against Siemens compatibility information. Prepare the correct module definition and output addresses in the PLC project. Load the STEP 7 hardware configuration before commissioning.
The outputs provide electronic short-circuit protection. Siemens requires an external diode for inductive loads above 200 mA. Select diode polarity and group fuses according to the manual. Paralleling outputs to increase current capacity is not supported.
Green LEDs indicate channel status; diagnostic and interrupt functions are not available. Consider suitable feedback through digital inputs to monitor actual load operation. A command displayed on an HMI does not by itself confirm field-device operation.
Assessing a used module
When assessing this model among used Siemens products, check all 64 channels and all four supply groups with loads wired for sinking outputs. Investigate outputs remaining on, intermittent operation, voltage drop and heating. Evaluate test results together with the applied loads and test duration.
Confirm the nameplate, accessory codes, availability, price and any warranty terms before ordering. Illuminated channel LEDs alone are insufficient evidence of satisfactory loaded operation.
Related topics and product groups
S7-300 overview | S7-300 CPU modules | Digital input modules
Digital output modules | Function modules | Analog module range
Used Siemens products | Used equipment overview | OtomasyonAVM home
Manufacturer references
Siemens – 6ES7322-1BP50-0AA0 data sheet (archived copy) | Siemens – S7-300 module manual, section 3.20 (archived copy) | Siemens – explanation of sinking and sourcing