6ES7314-1AG14-0AB0
Siemens 6ES7314-1AG14-0AB0 — S7-300 CPU 314, 128 kB
6ES7314-1AG14-0AB0 is an S7-300 CPU 314 central processing unit with 128 kB work memory and an MPI interface in the Siemens SIMATIC S7 PLC family. It operates from 24 V DC and requires a SIMATIC Micro Memory Card. When comparing S7-300 CPU modules, assess memory, communication, I/O structure and compatibility with the existing project together.
Work memory and MMC requirements
The 128 kB work memory is not expandable. Load memory uses a SIMATIC MMC with a maximum supported capacity of 8 MB. Installing a larger MMC does not increase the CPU's work memory. Select the card according to the program and project data to be stored.
When purchasing a used CPU, check MMC availability, capacity and existing contents separately. The compatible card and other PLC accessories should be clearly identified in the scope of delivery.
MPI communication and network selection
The X1 interface provides MPI communication using RS-485 hardware, at a maximum transmission rate of 187.5 kbit/s. It supports connections to programming devices and compatible operator panels.
The CPU has no integrated PROFIBUS DP master/slave or PROFINET port. Projects requiring network connectivity need a suitable communication processor and protocol support. For Siemens ET200 stations, assess the CPU, communication module and station interface as a complete configuration.
Field I/O and expansion
This is the standard CPU 314 version, with no integrated digital or analog field I/O. Field connections are provided through appropriate signal modules. When selecting S7-300 analog modules for measurement and control, check signal type, channel count and module supply requirements separately.
Supply voltage and processing performance
Rated supply voltage is 24 V DC, with a permitted range of 19.2–28.8 V DC. Select the power supply according to the combined requirements of the CPU, modules and field loads.
The Siemens manual specifies minimum execution times of 0.06 µs for bit operations and 0.12 µs for word operations. These are individual instruction execution times, not the scan time of the complete program. Program length, communication load and interrupts affect application response time.
Programming and CPU replacement
The STEP 7 hardware catalog must support the CPU's firmware version. Before replacement, compare the complete order number, program backup, MMC, MPI address and I/O addressing. The CPU 314 name alone does not establish full project compatibility between different order numbers.
PDF files and technical reference
For installation and configuration details, visit the S7-300 PDF files page. Manufacturer reference: Siemens CPU 31xC / CPU 31x technical manual — Section 9.3.
Related topics and product groups
S7-300 CPU modules · Siemens S7 PLC products · PLCs and accessories · S7-300 analog modules · Siemens ET200 · Used PLC power supplies · Second-hand products · OtomasyonAVM home