6ES7312-1AE13-0AB0

Siemens 6ES7312-1AE13-0AB0 — SIMATIC S7-300 CPU 312

6ES7312-1AE13-0AB0 is a CPU 312 central processing unit in the Siemens SIMATIC S7-300 family. It provides 32 KB of work memory, an MPI communication interface and a 24 V DC power supply input. A SIMATIC Micro Memory Card is required for operation. When selecting a processor or replacement for an existing installation, compare the complete order numbers within the Siemens S7 PLC products and S7-300 CPU modules ranges.

I/O configuration and module selection

The CPU has no integrated digital or analog I/O; field signals connect through suitable S7-300 signal modules. For analog measurement and control, select appropriate S7-300 analog modules for the required signal type. Check the measurement range, sensor connection and output type alongside the channel count. CPU 312 supports one rack with up to 8 modules; the proposed arrangement must also satisfy CPU compatibility and system power requirements.

32 KB work memory and MMC requirements

Work memory is used to execute the user program, while the MMC provides load memory. Installing a larger card does not increase the 32 KB work memory. The specified maximum MMC capacity for this model is 4 MB. When reviewing cards and connection equipment under PLCs and accessories, match the card order number to the CPU version. Check the existing project's memory usage and retentive data settings before replacement.

MPI communication and network planning

The integrated MPI interface supports 187.5 kbit/s. The CPU has no integrated PROFIBUS DP or PROFINET interface. For programming device and operator panel connections, check interface compatibility, station addresses and communication settings together. If distributed I/O using Siemens ET200 is planned, verify the required network interface and the compatibility of any communication processor with this CPU against the project configuration.

Power supply and replacement checks

The nominal supply is 24 V DC, with a permissible range of 20.4–28.8 V DC. When assessing used PLC power supplies, calculate the combined requirements of the CPU and the other modules. Before replacement, back up the STEP 7 project, hardware configuration and required data. Compare the firmware, MMC contents and module addresses with the existing system. Commissioning checks should cover diagnostic records, panel communication and the expected program behaviour.

PDF files and technical reference

Documentation is available through the S7-300 PDF files page. Refer to the Siemens product record for the model identification. The selected manual must match the order number and firmware version.

Related topics and product groups

S7-300 CPU modules · Siemens S7 PLC products · PLCs and accessories · S7-300 analog modules · Siemens ET200 · Used PLC power supplies · Used products · OtomasyonAVM home