6ES5 932-3SA12
Siemens 6ES5 932-3SA12 – S5-110S housing with power supply, 220/240 V AC, 5 V DC 10 A
Siemens 6ES5 932-3SA12 is the complete 932 housing with power supply for an S5-110S central controller in the SIMATIC S5 family. It supplies 5 V DC at 10 A from a 220/240 V AC input. In a Siemens S5 installation, assess the housing, backplane and supply arrangement together.
The Siemens ordering table identifies 3SA12 as the AC mains version; 3SA22 is 115 V AC and 3SA32 is 24 V DC. For nearby codes such as 6ES5 932-3SA11, compare labels, input arrangements and mechanical construction. Establish separately whether a used housing includes the CPU and other pictured modules.
Input, output and power budget
Input tolerance is +10%/−15% and the frequency range is 48–63 Hz. The output is 5 V DC ±1%, rated 10 A, with 50 W maximum output power. When assessing the S5 power supply, calculate the total installed module load and compare the existing input connection with its label.
The technical table specifies 0.6 A input current at rated load and a 0.8 A fuse; the spare-parts list identifies the fuse as slow-blow. Repeated fuse operation requires investigation of the supply and load. Do not continue testing with a higher-rated fuse.
Housing, mounting and module arrangement
The power supply is fixed to the housing. The manual states that it cannot be withdrawn separately for thermal reasons. Approximate housing-and-supply weight is 9.5 kg. When comparing S5 racks and carriers, inspect mounting points and rear connections.
The housing supplies power; a fitted 6ES5 902-3SA12 CPU executes the application. Do not assume identical supplied contents for an empty housing, a CPU-equipped housing and a complete system. When reviewing the S5 system structure, record every module code separately.
Keep the field voltages of digital input and digital output modules distinct from the 5 V system supply. Check each module's supply and connection requirements, including analog modules. A shared catalogue category does not establish compatibility with this housing.
24 V load-voltage monitoring and connections
This AC version provides a connection for monitoring an external 24 V DC load supply. It is not a 24 V power output. During cable and connector inspection, distinguish mains, 5 V system power and field load power using the installed wiring documentation.
When checking interface modules and communication modules, inspect their connections as well as the power supply. Photograph the housing connections before removal. Do not change terminals or links using a diagram from another S5 model.
Battery, program backup and diagnostics
Include the backup battery and S5 memory modules in the maintenance review. Before removing power, back up the STEP 5 application and required data. Confirm beforehand that the programming software and connection hardware suit the installed S5-110S arrangement.
The front panel includes Power supply OK, Battery low and 24 V low indicators. During PLC troubleshooting, assess these alongside input voltage, loaded 5 V output and external load power. Record the fault before using Reset as a first test action.
Used-unit inspection and modernization
For used Siemens equipment, inspect the backplane, battery holder, mains terminals and loaded supply behaviour as well as the housing. If a used PLC CPU is included, record its full code and test result separately.
Base model and revision comparisons on label photographs. For modernization, assess Derell PLC options as a separate project, mapping existing I/O, field supplies and application functions to the proposed system.
Editor's Note
This order number covers the housing and power supply together. Modules visible in a photograph are not necessarily included. List the housing, CPU, memory and interface parts separately before purchase.
Start with the 3SA12 label and mains connection. Keep it distinct from the 115 V AC and 24 V DC versions. Existing wiring should still be checked against the actual unit.
An unloaded 5 V reading is only part of the test. Check voltage under a suitable load, connection condition and heating. Investigate the supply and module loads before considering any fuse replacement.
Inspect the battery holder, backplane and connectors for leakage, corrosion or heat damage. Have the program and data backup ready, and follow the relevant maintenance procedure before removing power or the battery.
The housing and supply weigh approximately 9.5 kg, so prepare mounting and handling accordingly. Do not force the supply out like a plug-in module. Request a clear supplied-parts list and the actual load-test conditions.
OtomasyonAVM resources and PDF archive
6ES5 932-3SA12 main page · Used Siemens S5 models · Siemens S5 PDF archive
The reference is SIMATIC S5-110S/B Operating Instructions, GWA 4NEB 807 2121-02, in English. The exact 3SA12 specification is on printed page 6 / PDF page 8; installation is on printed page 12 / PDF page 14. It was also compared with the German GWA 4NEB 807 2121-01.
Related topics
6ES5 932-3SA11 · 6ES5 902-3SA12 CPU · S5 rack options · Derell PLC options
Navigation
SIMATIC S5 · S5 power supplies · S5 racks · Used Siemens · Cables and connectors
Siemens and external references
Siemens S5-110S/B – exact 6ES5 932-3SA12 housing and power-supply specification, printed 6
Fixed supply and load-voltage monitoring connection, printed 12 · Indicators and controls, printed 18–19
Exact ordering codes, input versions and fuse list, printed 29