Simatic S5 Analog modules
Siemens SIMATIC S5 Analog Input and Output Modules
Siemens SIMATIC S5 analog modules transfer pressure, temperature, level and other process measurements to the PLC, or provide analog control signals to field devices. Analog input modules, analog output modules, range cards and analog processing modules perform different functions. Selection requires the complete 6ES5 order number, signal range, channel count, isolation arrangement and system compatibility.
This section includes modules from different S5 families. Listing a board here does not establish compatibility with every S5 CPU. Preserve suffixes such as 4UA, 7LA and 8MC, together with the hardware version, when opening its technical page.

Signal range and isolation
0–10 V and ±10 V are different ranges, as are 0–20 mA and 4–20 mA. Verify suitability for voltage, current, Pt100 or thermocouple signals. A two-wire transmitter and a separately powered four-wire transmitter must not be assumed to use the same connection.
Galvanic isolation does not necessarily mean that every channel is isolated from every other channel. Check channel isolation, isolation from ground, common analog references and permitted potential differences separately. A raw program value is not automatically a pressure or temperature reading in engineering units.
464 and 466 voltage, current and temperature inputs
Verified input examples: 6ES5 464-8MB11 ±1 V, 6ES5 464-8MC11 ±10 V, 6ES5 464-8MD11 ±20 mA, 6ES5 464-8ME11 4–20 mA and 6ES5 466-8MC11 0–10 V. Similar model numbers do not imply identical signal ranges.
Other 464 technical pages: 6ES5 464-8MA11 · 6ES5 464-8MA21 · 6ES5 464-8MF11 · 6ES5 464-8MF21 · 6ES5 464-8MG11. Check signal type, sensor wiring and any linearization separately for each model. Review the specific system scope of the 8MG11 separately.
Additional 466 input model: 6ES5 466-3LA11. Select its channel arrangement and measuring settings from the documentation for that exact module.
460, 463 and 465 analog input families
460 models: 6ES5 460-4UA11 · 6ES5 460-4UA12 · 6ES5 460-4UA13 · 6ES5 460-7LA11 · 6ES5 460-7LA12 · 6ES5 460-7LA13. Where a version uses measuring range cards, identify both the main module and the fitted range cards.
463 models: 6ES5 463-4UA11 · 6ES5 463-4UA12 · 6ES5 463-4UB12. Check range selection and the integration characteristics for mains interference rejection in the exact-model manual.
465 models: 6ES5 465-3AA13 · 6ES5 465-4UA11 · 6ES5 465-4UA12 · 6ES5 465-4UA13 · 6ES5 465-7LA11 · 6ES5 465-7LA12 · 6ES5 465-7LA13. Channel count, channel use for Pt100 connections and isolation must not be generalized across all versions.
IP 243 analog processing modules
6ES5 243-1AA11 · 6ES5 243-1AA12 · 6ES5 243-1AA13 · 6ES5 243-1AB11 · 6ES5 243-1AB12 · 6ES5 243-1AC11. Versions in this group have different A/D and D/A hardware options. Match hardware scope, configuration and program blocks before applying one version's converter arrangement or functions to another.
470 analog output models
470-4UA: 6ES5 470-4UA11 · 6ES5 470-4UA12 · 6ES5 470-4UA13. 470-4UB: 6ES5 470-4UB11 · 6ES5 470-4UB12 · 6ES5 470-4UB13. 470-4UC: 6ES5 470-4UC11 · 6ES5 470-4UC12 · 6ES5 470-4UC13.
470-7LA: 6ES5 470-7LA11 · 6ES5 470-7LA12 · 6ES5 470-7LA13. 470-7LB: 6ES5 470-7LB11 · 6ES5 470-7LB12 · 6ES5 470-7LB13. 470-7LC: 6ES5 470-7LC11 · 6ES5 470-7LC12 · 6ES5 470-7LC13.
470-8MA: 6ES5 470-8MA11 · 6ES5 470-8MA12. 470-8MB: 6ES5 470-8MB11 · 6ES5 470-8MB12. 470-8MC: 6ES5 470-8MC11 · 6ES5 470-8MC12. 470-8MD: 6ES5 470-8MD11 · 6ES5 470-8MD12.
Check voltage/current output type, unipolar or bipolar range, load resistance, common reference and channel isolation together. The shared 470 prefix does not guarantee identical output characteristics or wiring.
475 and 476 analog output models
6ES5 475-3AA11 · 6ES5 475-5AA11 · 6ES5 476-3AA11. For these older boards, confirm the controller system, output signal and supply connections using the complete order number. Do not assume direct interchangeability with a 470 module.
Ex analog inputs and outputs
6ES5 467-8EE11 is an Ex analog input; 6ES5 477-8EC11 is an Ex analog output. Assess the bus unit, partition and field-circuit conditions in the module's Ex documentation together, rather than selecting it as an ordinary analog board.
498 measuring range cards
Range card models: 6ES5 498-1AA11 · 6ES5 498-1AA21 · 6ES5 498-1AA31 · 6ES5 498-1AA41 · 6ES5 498-1AA51 · 6ES5 498-1AA61 · 6ES5 498-1AA71. These are not independent analog input modules. They complement the measuring range and connection arrangement of a compatible main input module.
Options such as 1AA51 and 1AA71, intended for two-wire or four-wire transmitter arrangements, must not be interchanged merely because both involve 4–20 mA. Record the range card code together with the main module order number.
Connections and auxiliary components
6ES5 498-1AB11 is a contact-protection/RC suppression module, distinct from 498-1AA measuring range cards. 6ES5 712-8AF00 is a 0.5 m cable for IM 316 connections. Neither component provides analog input or output channels.
Testing a used module
Assess input readings at several points using a suitable calibrator, and output accuracy with an appropriate load. Include channel settings, range cards and connectors in the test record. To offer equipment for sale, send the complete model, quantity, working/faulty condition, nameplate photograph and price to otomasyonavm@gmail.com. Sales require an invoice; used items are sold without returns. Equipment can be tested at the workshop.
Editor's Note
Do not select an analog board from its front cover alone. Identify the complete main-module code and every fitted range card. A missing range card can make a healthy main module unsuitable for the job.
If a reading drifts, do not immediately replace the module. First distinguish sensor supply, shielding, reference and scaling problems. A healthy input board cannot correct an incorrect field signal.
A single test point is not enough. Check behaviour near the low, middle and high parts of the range, and test the channels that will be used. One good channel does not establish the condition of the others.
For output tests, look beyond a voltage reading with no load. The intended load and cable arrangement matter too. A stable bench reading should remain consistent under the machine's actual load.
Before removal, photograph and record the wiring, switch positions and range cards. Replacing the board should not depend on guessing its former settings. A clear record can save hours of fault-finding.
OtomasyonAVM Resources and PDFs
For system selection, review the SIMATIC S5 CPU families and S5 module categories. Check the complete order number and edition scope in the applicable manual.
+ Shared Siemens SIMATIC S5 PDF archive
+ S5-115U System Manual — English
+ S5-135U/155U System Manual — English
+ S5-100U Ex I/O Manual — English
+ SIMATIC S5 U Periphery Manual — English
Related Topics
Browse SIMATIC S5
+ Used Siemens automation equipment
Siemens and External References
+ Siemens — S5-100U — analog value processing and module specifications (English)
+ Siemens — S5-115U — analog processing, range cards and connections (English)
+ Siemens — S5-135U/155U — analog I/O and contact-protection circuits (English)