QY18A

The Mitsubishi QY18A is an 8-point relay output module compatible with the MELSEC-Q Series PLCs, designed to control both AC and DC loads independently. With its relay-based outputs, the QY18A is versatile, supporting high-voltage AC loads up to 240V and DC loads up to 24V. This module is ideal for applications requiring isolated switching of high-power devices such as motors, solenoids, and heaters.


Technical Specifications and Supported Programs

    Output Channels: 8 relay outputs, each independently isolated.
    Voltage Range:
        AC: 240V maximum
        DC: 24V maximum
    Current Specifications:
        Per Point: Maximum of 2A per contact
    Output Type: Relay, providing independent control for each output point, suitable for high-power devices.
    Isolation: Each output channel is individually isolated, preventing cross-interference between loads.
    Response Time: Relay switching, suitable for applications that tolerate slightly slower response times compared to transistor outputs.
    Wiring: Equipped with screw terminals for secure and stable connections in industrial environments.
    Environmental Conditions:
        Operating Temperature: 0-55°C
        Humidity: 10-90% RH (non-condensing)
        Vibration and Shock Resistance: Meets IEC 61131-2 standards for durability and resilience in industrial settings.

Supported Programming Software: The QY18A module is compatible with GX Works2 and GX Developer software, enabling straightforward setup, monitoring, and diagnostics.


Commissioning Notes and Recommendations

    Installation: Ensure the module is properly mounted in the PLC rack, and confirm all wiring follows recommended specifications for both AC and DC output connections.
    Power Verification: Verify that loads connected to each relay output are within the 240V AC or 24V DC limits, and that individual current does not exceed 2A per contact.
    Functional Testing: Use GX Works2 or GX Developer to perform functional tests for each output channel under load to verify proper operation before deploying.
    Maintenance: Regularly inspect the relay contacts and clean terminal connections to ensure consistent performance, as relay contacts can experience wear over time in high-power applications.

By following these guidelines, the QY18A module will provide dependable and versatile output control, suitable for applications requiring isolated switching of AC and DC devices across industrial environments.



>> Mitsubishi QY18A User manual (pdf)

  ----------

+ Mitsubishi Automation Homepage

+ Mitsubishi Electric Contact (for Automation Mall)

+ About Mitsubishi Electric

Reminder: Mitsubishi QY18A and other Mitsubishi PLC modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 07.12.2012 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."