PowerFlex 40P fault codes 2
Hi everyone,
Fault Indication, Clearing, and Auto Restart for Allen Bradley PowerFlex 40P
Fault Indicatio
+ The drive indicates a fault through its integral LED display by showing:
- Flashing fault number
- Flashing fault indicator
+ To regain control of the display, press the Up Arrow key.
Steps to Manually Clear Faults:
+ Address the Fault Condition:
- Identify and correct the condition that caused the fault. Refer to Table 4.B for fault descriptions and corrective actions.
+ Clear the Fault:
- After taking corrective action, clear the fault using one of the following methods:
* Press and hold the Up Arrow key for three seconds.
* Cycle the drive power.
* Set parameter A100 [Fault Clear] to "1" or "2".
* Cycle the digital input if A051-A054 [Digital Inx Sel] is set to option 7 "Clear Fault".
Automatically Clearing Faults
Steps to Automatically Clear Faults:
+ Clear a Type 1 Fault and Restart the Drive:
- Set parameter A092 [Auto Rstrt Tries] to a value other than "0".
- Set parameter A093 [Auto Rstrt Delay] to a value other than "0".
+ Clear an OverVoltage, UnderVoltage, or Heatsink OvrTmp Fault Without Restarting the Drive:
- Set parameter A092 [Auto Rstrt Tries] to a value other than "0".
- Set parameter A093 [Auto Rstrt Delay] to "0".
Auto Restart (Reset/Run)
Description:
+ The Auto Restart feature enables the drive to automatically reset a fault and attempt to restart without user intervention. This is particularly useful for remote or unattended operations.
+ Important Note: Only certain faults can be reset automatically. Type 2 faults, which indicate possible drive component malfunctions, are not resettable. Fault types and descriptions can be found in Table 4.A and Table 4.B respectively.
F63 SW OverCurrent
+ Cause: Programmed A098 [SW Current Trip] has been exceeded.
+ Consequence: Drive will not operate, hardware may be damaged.
+ Solution: Check load requirements and the A098 [SW Current Trip] setting.
F64 Drive Overload
+ Cause: Drive rating of 150% for 1 minute or 200% for 3 seconds has been exceeded.
+ Consequence: Drive may overheat and get damaged.
+ Solution: Reduce the load or extend the Accel Time.
F70 Power Unit
+ Cause: Failure has been detected in the drive power section.
+ Consequence: Drive will not operate, hardware may be damaged.
+ Solution:
- Cycle power.
- Replace the drive if the fault cannot be cleared.
F71 Net Loss
+ Cause: The communication network has faulted.
+ Consequence: Drive will not operate, communication loss occurs.
+ Solution:
- Cycle power.
- Check communications cabling.
- Check network adapter settings.
- Check external network status.
F80 SVC Autotune
+ Cause: The autotune function was either cancelled by the user or failed.
+ Consequence: Drive will not operate, autotune is incomplete.
+ Solution: Restart the procedure.
F81 Comm Loss
+ Cause: RS485 (DSI) port stopped communicating.
+ Consequence: Drive will not operate, communication loss occurs.
+ Solution:
- If the adapter was not intentionally disconnected, check the wiring to the port. Replace wiring, port expander, adapters, or complete drive as required.
- Check the connection.
- If an adapter was intentionally disconnected, reconnect it.
- Turn off using A105 [Comm Loss Action].
- Connecting I/O Terminal 04 to ground may improve noise immunity.
F91 Encoder Loss
+ Cause: Requires differential encoder. One of the two encoder channel signals is missing.
+ Consequence: Drive will not operate, position control is compromised.
+ Solution:
- Check the wiring.
- If P038 [Speed Reference] = 9 "Positioning" and E216 [Motor Fdbk Type] = 5 "Quad Check," swap the encoder channel inputs or swap any two motor leads.
- Replace the encoder.
F100 Parameter Checksum
+ Cause: The checksum read from the board does not match the checksum calculated.
+ Consequence: Drive will not operate, parameters may be corrupted.
+ Solution: Set P041 [Reset To Defaults] to option 1 "Reset Defaults."
F111 Enable Hardware
+ Cause: DriveGuard Safe-Off Option (Series B) board is installed and the ENBL enable jumper has not been removed.
+ Consequence: Drive will not operate, safety system is activated.
+ Solution:
- Remove the ENBL enable jumper.
- Cycle power.
- If the DriveGuard Safe-Off Option (Series B) board has failed, remove power to the drive and replace the board.
F122 I/O Board Fail
+ Cause: Failure has been detected in the drive control and I/O section.
+ Consequence: Drive will not operate, hardware may be damaged.
+ Solution:
- Cycle power.
- Replace the drive if the fault cannot be cleared.
---------------------
+ Powerflex 40P Fault codes page 1
+ Powerflex 40P Fault codes page 2
+ Back to main page "* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 10.02.2013Your shopping cart is empty!