IC694MDL655
IC694MDL655: 24 Volt DC Positive/Negative Logic 32-Point Input Module
The IC694MDL655 is a 24VDC input module that provides 32 discrete input points. These inputs can be configured for either positive or negative logic and can operate at voltage levels up to 30V. The inputs are divided into four isolated groups, with each group consisting of eight input points. Each group has its own common terminal, providing isolation between groups but referencing the same user common connection within each group.
This module does not provide special fault or alarm diagnostics. Field devices can be powered using an external power source or the module's isolated +24VDC output. The front of the module features green LEDs to indicate the ON/OFF status of each input point, and the blue band on the label signifies that MDL655 is a low-voltage module.
This module can be installed in any I/O slot in the RX3i system.
Technical Specifications:
Rated Voltage: 24 volts DC, Positive or Negative Logic
Input Voltage Range: 0-30 volts DC
Inputs per Module: 32 (four groups of eight inputs each)
Isolation:
Field to Backplane and Frame Ground: 250 VAC continuous, 1500 VAC for one minute
Group to Group: 50 VAC continuous, 500 VAC for one minute
Input Current: 7.0 mA (typical ON current at 24VDC)
Input Characteristics:
On-state Voltage: 11.5-30 volts DC
Off-state Voltage: 0-5 volts DC
On-state Current: Minimum 3.2 mA
Off-state Current: Maximum 1.1 mA
On Response Time: Maximum 2 ms
Off Response Time: Maximum 2 ms
Internal Power Consumption:
195 mA (maximum) from the +5V bus on the backplane
224 mA (typical) from the isolated +24V bus on the backplane or from an external 24VDC supply with all inputs ON
Input Points vs. Temperature:
The maximum number of inputs that can be ON simultaneously depends on the ambient temperature.
Wiring:
Connections are made using two 24-pin male connectors (Fujitsu FCN-365P024-AU) on the front of the module. You can either use pre-wired cables (catalog numbers IC693CBL327 and IC693CBL328) or build your own cables. Wiring to field devices is done through mating female connectors with stripped and tinned wires.
Note: If the +24V OUT pin is used to power field devices, the isolation specification changes to:
Field to Backplane and Frame Ground: 50 VAC continuous, 500 VAC for one minute.
The IC694MDL655 is a versatile 32-point input module that can handle both positive and negative logic configurations. With isolated groups of inputs and fast response times, it is ideal for low-voltage industrial environments. This module offers flexibility in powering field devices, either from an external source or through its built-in +24V output, making it a reliable solution for complex input management in RX3i systems.
>> IC694MDL655 input modules User manual (pdf)
----------
+ Ge-Fanuc Contact (for Automation Mall)