Omron P7 fault codes 3
OL1: Motor Overload
- What Happened: The load is too large, causing motor overload.
+ What to Do: Recheck the cycle time, load size, acceleration/deceleration times, V/F pattern, and motor rated current value.
OL2: Drive Overload
- What Happened: The load is too large, causing drive overload.
+ What to Do: Recheck the cycle time, load size, acceleration/deceleration times, V/F pattern, and consider changing to a larger size drive if necessary.
OL3: Overtorque Detection 1
- What Happened: Drive output current is greater than L6-02 for more than the time set in L6-03.
+ What to Do: Ensure the values in L6-02 and L6-03 are appropriate and check the application/machine status to eliminate the fault.
OPR: Digital Operator Connection Fault
- What Happened: The digital operator is not attached or the connector is broken.
+ What to Do: Attach the digital operator, check the connector, verify the setting of o2-06, and if necessary, replace the digital operator.
OV: DC Bus Overvoltage
- What Happened: The DC bus voltage exceeded the trip point.
+ What to Do: Check the input circuit, reduce the input power to within specifications, extend the deceleration time, remove power factor correction capacitors if used, and monitor the DC bus voltage.
PF: Input Phase Loss
- What Happened: Drive input power supply has an open phase or a large imbalance of input voltage.
+ What to Do: Check the input voltage, tighten the terminal screws, and verify parameter L8-06 is set correctly.
PUF: DC Bus Fuse
- What Happened: The DC bus fuse has opened due to a shorted output transistor or terminals.
+ What to Do: Remove power from the Drive, disconnect the motor, perform checks without power, replace the shorted components, and replace the defective fuse.
RH: Dynamic Braking Resistor
- What Happened: The protection of the dynamic braking resistor was triggered.
+ What to Do: Verify the dynamic braking duty cycle, monitor the DC bus voltage, and replace the dynamic braking resistor if necessary.
RR: Dynamic Braking Transistor
- What Happened: The dynamic braking transistor failed.
+ What to Do: Cycle power off and on to the Drive, replace the defective dynamic braking transistor or resistor, and monitor the DC bus voltage.
UV1: DC Bus Undervoltage
- What Happened: The DC bus voltage is less than or equal to L2-05.
+ What to Do: Check the input circuit, increase the input power to within specifications, extend the acceleration time, check the input voltage, and if necessary, replace the Drive.
UV2: Control Power Supply Undervoltage
- What Happened: Undervoltage of the control circuit occurred while running.
+ What to Do: Cycle power off and on to the Drive, repair or replace the Power PCB/Gate Drive PCB, and remove all control wiring to test the Drive.
UV3: Soft Charge Circuit Fault
- What Happened: The pre-charge contactor opened while the Drive was running.
+ What to Do: Cycle power off and on to the Drive, check the condition of the soft charge contactor, and if necessary, repair or replace the Power PCB/Gate Drive PCB.